Chapter 3: Overview Feature Description Form C relay trouble contacts for external notification. Form C contact normally energized. Contacts transfer during a trouble, an alarm trouble, or an AC trouble: 2.0 amps at 24VDC max, resistive load. Non-Supervised. Built-in Sounder To indicate trouble, with a trouble silence switch to silence it. If the trouble is not corrected in 20 hours, the sounder reactivates. (Trouble Silence Switch does not change the state of the Form C Trouble relay.) Remote reporting via output contacts for system trouble, alarm activation, and AC trouble. AC trouble can be configured for report separately or as a system trouble. BATTERY STANDBY MICROPHONE AUX IN NIGHT RING TELEPHONE PAGE PORT BACKGROUND MUSIC SP40S PANEL TROUBLE RELAY CONTROL SYSTEM SPEAKER CIRCUIT CENTRAL AMPLIFIED (40 WATT, SELECTABLE 25V or 70.7V) POWER LIMITED STROBE CIRCUIT 24VDC AT 2A MAX POWER LIMITED STROBE RETURN FOR CINTINUATION OF STROBE CIRCUIT OR EOLR CONSTANT 24VDC AT 0.5A STROBE NAC INPUT (8 TO 33VDC) POWER LIMITED ALARM RELEAY FORM C UP TO 8 CC CIRCUIT INPUTS 120VAC DIGITAL VOICE MESSAGE CHIP ALLOWS RECORDING 8 MESSAGE SEGMENTS AT THE PANEL. THE PANEL COMES WITH 8 STANDARD PRE-RECORDED MESSAGE. TAILORED MESSAGES CAN BE RECORDED AT WHEELOCK. Figure 3-1 Basic Capabilities of the SP40S Panel SP40S Multi-Function Facility Communication System Manual, Revision D 4