Download Sharp DP-750 Technical data
Transcript
Programmable Field Bus Controller 750-833 Diagnostics 3.9.1 • 91 Stations Status 1 to 3 see EN 50170 3.9.2 PROFIBUS DP Master Address The PROFIBUS DP master address is located in byte 3 of the slave diagnostics and contains the master address parameterized by the station and to which it has write and read access. 3.9.3 Manufacturer Identification The manufacturer identification is located in bytes 4 and 5 and contains a 16 bit code, intended for the identification of the device or the device class. 3.9.4 Identification based Diagnostics The identification based diagnostics comprises of a bit field containing a bit information for each connected module. The individual bit provides information about the current operating status. A 0 means no fault, a 1 indicates a faulty module status. The controller can be fitted with up to 63 modules, so that the identification based diagnostics including header covers 9 bytes from byte 6 to byte 14. Byte Information 6 0 1 0 0 1 0 0 1 Header byte (9 byte identification based diagnostics incl. header) 7 7 6 5 4 3 2 1 0 Diagnostics allocation to 8 15 14 13 12 11 10 9 8 9 23 22 21 20 19 18 17 16 10 31 30 29 28 27 26 25 24 11 39 38 37 36 35 34 33 32 12 47 46 45 44 43 42 41 40 13 55 54 53 52 51 50 49 48 14 63 62 61 60 59 58 57 56 WAGO-I/O-SYSTEM 750 Bus System Description Field bus controller (n = 0) I/O module n (n = 1 ... 63)