Download Mitsubishi MUZ-FD12NA- U1 Service manual
Transcript
Revision B: • 7. DATA has been corrected. Please void OBH498 REVISED EDITION-A. SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT No. OBH498 HFC SERVICE MANUAL REVISED EDITION-B utilized R410A Models MUZ-FD09NA MUZ-FD09NAMUZ-FD12NA MUZ-FD12NA- U1 U1 Indoor unit service manual MSZ-FD•NA Series (OBH497) CONTENTS 1. TECHNICAL CHANGES ··································· 3 2. PART NAMES AND FUNCTIONS ····················· 3 3. SPECIFICATION ················································ 4 4. OUTLINES AND DIMENSIONS ························ 6 5. WIRING DIAGRAM············································ 7 6. REFRIGERANT SYSTEM DIAGRAM ··············· 8 7. DATA ·································································· 9 8. ACTUATOR CONTROL ··································· 15 9. SERVICE FUNCTIONS ··································· 16 10. TROUBLESHOOTING ····································· 16 11. DISASSEMBLY INSTRUCTIONS ···················· 32 PARTS CATALOG (OBB498) TM NOTE: RoHS compliant products have <G> mark on the spec name plate. Revision A: • 3. SPECIFICATION has been corrected. Revision B: • 7. DATA has been corrected. 2 1 TECHNICAL CHANGES MUZ-FD09NA MUZ-FD09NA MUZ-FD12NA MUZ-FD12NA - U1 U1 1. New model 2 PART NAMES AND FUNCTIONS MUZ-FD09NA MUZ-FD12NA Air inlet Piping Drain hose Air outlet Drain outlet 3 3 SPECIFICATION Outdoor unit model Capacity Rated (Minimum~Maximum) Capacity Rated Power consumption Rated (Minimum~Maximum) Power consumption Rated MUZ-FD09NA Cooling 1 Heating 47 Heating 17 Cooling 1 Heating 47 Heating 17 EER 1 [SEER] 3 Cooling Heating HSPF IV (V) 4 COP Heating 1 Power supply Max. fuse size (time delay) Min. circuit ampacity Fan motor Model Compressor Btu/h Btu/h Btu/h W W W 1 2 1 2 V , phase , Hz A A F.L.A R.L.A L.R.A Refrigeration oil cc. (Model) Refrigerant control Sound level 1 Cooling Heating dB(A) dB(A) W D H in. in. in. Ib. Defrost method Dimensions Weight External finish Remote controller Control voltage (by built-in transformer) Refrigerant piping Liquid Refrigerant pipe size (Min. wall thickness) Gas Indoor Connection method Outdoor Between the indoor & Height difference outdoor units Piping length Refrigerant charge (R410A) VDC in. in. ft. ft. MUZ-FD12NA 9,000 (2,800~9,000) 12,000 (2,800~12,000) 10,900 (3,000~18,000) 13,600 (3,000~21,000) 12,500 13,600 650 (160~650) 960 (160~960) 750 (150~2,400) 980 (150~2,400) 1,730 1,780 13.8 [23.0] 12.5 [22.0] 10.55 (7.4) 10.55 (7.4) 4.26 4.07 208/230 , 1 , 60 15 12 0.56 SNB130FQAH 8.6 10.8 450 (NEO22) Liner expansion valve 48 48 49 49 Reverse cycle 31-1/2 11-1/4 21-5/8 80 Munsell 3Y 7.8/1.1 Wireless type 12 - 24 Not supplied 1/4 (0.0315) 3/8 (0.0315) Flared Flared 40 65 2 lb. 9 oz. NOTE: Test conditions are based on ARI 210/240. 1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB) (Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB 2: (Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB 4 Rated frequency Rated frequency Maximum frequency Test condition 3, 4 ARI Mode Indoor air condition (°F) Dry bulb Wet bulb Test Outdoor air condition (°F) Dry bulb Wet bulb "A" Cooling Steady State at rated compressor Speed 80 67 95 (75) "B-2" Cooling Steady State at rated compressor Speed 80 67 82 (65) 80 67 82 (65) Low ambient Cooling Steady State at minimum compressor Speed 80 67 67 (53.5) Intermediate Cooling Steady State at Intermediate compressor Speed 5 80 67 87 (69) Standard Rating-Heating at rated compressor Speed 70 60 47 43 Low temperature Heating at rated compressor Speed 70 60 17 15 70 60 62 56.5 70 60 47 43 Frost Accumulation at rated compressor Speed 70 60 35 33 Frost Accumulation at Intermediate compressor Speed 5 70 60 35 33 SEER "B-1" Cooling Steady State (Cooling) at minimum compressor Speed Max temperature Heating at minimum compressor Speed HSPF (Heating) High temperature Heating at minimum compressor Speed 5: At Intermediate compressor Speed = ("Cooling rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed". OPERATING RANGE (1) POWER SUPPLY Rated voltage Outdoor unit Guaranteed voltage (V) 208/230 V 1 phase 60 Hz Min. 187 208 230 Max. 253 (2) OPERATION Intake air temperature (°F) Mode Condition Standard temperature Maximum temperature Cooling Minimum temperature Maximum humidity Standard temperature Heating Maximum temperature Minimum temperature Indoor Outdoor DB 80 90 67 WB 67 73 57 DB 95 115 14 70 80 60 67 70 60 47 75 5 15 (- U model) 78 % WB — — — — 5 43 65 4 14 (- U model) 4 OUTLINES AND DIMENSIONS MUZ-FD09NA MUZ-FD12NA Unit: inch REQUIRED SPACE 1-3/4 15-3/4 Drain hole 1-5/8 . or 13-9/16 11/16 Air out 12 ~ 12-3/4 Air in Air in 4 in . or re 14 mo . or 8 in 13/16 Oval hole 29/32 11-1/4 17/32 Open two sides of left, right, or rear side. Liquid pipe Gas pipe 5-7/8 2 11-1/32 handle 11-29/32 5-15/16 6-23/32 19-11/16 31-1/2 e mor mo re 7/8 13/32 4 in 1-9/16 2- 3/8 21-5/8 Basically open 4 inch or more without any obstruction in front and on both sides of the unit. 2-23/32 6 :1/4 (flared) :3/8 (flared) in. or m ore 5 WIRING DIAGRAM MUZ-FD09NA MUZ-FD12NA 7 6 REFRIGERANT SYSTEM DIAGRAM MUZ-FD09NA MUZ-FD12NA Unit: inch 4-way valve Refrigerant pipe ø3/8 (with heat insulator) Muffler Stop valve (with service port) Discharge temperature thermistor RT62 Service port Flared connection Outdoor heat exchanger Muffler Service port Outdoor heat exchanger temperature thermistor RT68 Ambient temperature thermistor RT65 Compressor Defrost thermistor RT61 Capillary tube O.D. 0.118 × I.D. 0.071 × 23-5/8 (ø3.0 × ø1.8 × 600) Expansion valve Flared connection Stop valve (with strainer) Refrigerant pipe ø1/4 (with heat insulator) Strainer #100 R.V. coil heating ON cooling OFF Capillary tube O.D. 0.118 × I.D. 0.079 × 9-7/16 (ø3.0 × ø2.0 × 240) Refrigerant flow in cooling Refrigerant flow in heating MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE Model MUZ-FD09NA MUZ-FD12NA Refrigerant piping: ft. Max. Length Max. Height difference A B 65 Piping size O.D: in. Gas Liquid 3/8 1/4 40 Indoor unit Max. Height difference B Max. Length A Outdoor unit ADDITIONAL REFRIGERANT CHARGE (R410A: oz.) NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation. Model Outdoor unit precharged MUZ-FD09NA MUZ-FD12NA 2 lb. 9 oz. Refrigerant piping length (one way): ft. 30 40 50 60 25 0 1.62 4.86 8.10 11.34 65 12.96 Calculation: X oz. = 1.62 / 5 oz. / ft. × (Refrigerant piping length (ft.) - 25) NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation. 8 7 DATA MUZ-FD09NA MUZ-FD12NA 7-1. PERFORMANCE DATA 1) COOLING CAPACITY Indoor air Model MUZ-FD09NA MUZ-FD12NA 71 67 63 71 67 TC 11.0 10.4 9.8 14.7 13.9 75 SHC 6.9 7.9 8.8 8.8 10.2 Outdoor intake air DB temperature (˚F) 85 95 105 TPC TC SHC TPC TC SHC TPC TC SHC 0.58 10.3 6.5 0.63 9.7 6.1 0.68 9.0 5.6 0.55 9.7 7.4 0.60 9.0 6.8 0.65 8.4 6.4 0.52 9.1 8.1 0.58 8.5 7.6 0.62 7.7 6.9 0.85 13.7 8.2 0.94 12.9 7.7 1.01 12.0 7.2 0.81 13.0 9.5 0.89 12.0 8.8 0.96 11.2 8.1 115 TPC TC SHC TPC 0.72 8.3 5.2 0.75 0.69 7.7 5.8 0.72 0.66 7.0 6.3 0.69 1.06 11.0 6.6 1.10 1.02 10.3 7.5 1.07 63 13.1 11.3 0.77 12.1 10.5 0.85 0.98 IWB (˚F) 11.3 9.7 0.92 10.3 8.9 9.4 8.1 TPC 0.78 0.77 0.74 1.02 1.00 0.97 TC 12.4 12.7 13.0 15.5 15.8 16.2 1.02 NOTE: 1. IWB : Intake air wet-bulb temperature TC : Total Capacity (x103 Btu/h) SHC : Sensible Heat Capacity (x103 Btu/h) TPC : Total Power Consumption (kW) 2. SHC is based on 80˚F of indoor Intake air DB temperature. 2) COOLING CAPACITY CORRECTIONS Refrigerant piping length (one way: ft.) 25 (std.) 40 65 MUZ-FD09NA 1.0 0.954 0.878 MUY-FD12NA 3) HEATING CAPACITY Indoor air Model MUZ-FD09NA MUZ-FD12NA IDB (˚F) 75 70 65 75 70 65 5 TC 4.8 5.2 5.5 6.0 6.5 6.8 15 TPC 0.44 0.42 0.41 0.58 0.55 0.53 TC 6.3 6.7 6.9 7.9 8.4 8.6 TPC 0.56 0.54 0.52 0.73 0.71 0.68 Outdoor intake air WB temperature (˚F) 25 35 43 TC TPC TC TPC TC TPC 7.9 0.66 9.4 0.73 10.6 0.77 8.2 0.64 9.6 0.71 10.9 0.75 8.6 0.62 10.0 0.69 11.2 0.73 9.9 0.86 11.8 0.96 13.3 1.00 10.2 0.84 12.0 0.93 13.6 0.98 10.7 0.81 12.4 0.91 14.0 0.96 45 TC 11.0 11.2 11.6 13.7 14.0 14.4 55 TPC 0.81 0.80 0.78 1.06 1.04 1.02 NOTE: 1. IDB : Intake air dry-bulb temperature TC : Total Capacity (x103 Btu/h) TPC : Total Power Consumption (kW) 2. Above data is for heating operation without any frost. How to operate with fixed operational frequency of the compressor. 1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL mode or EMERGENCY HEAT mode before starting to operate the air conditioner. 2. The compressor starts with operational frequency. 3. The fan speed of the indoor unit is High. 4. This operation continues for 30 minutes. 5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on the remote controller. 9 7-2. PERFORMANCE CURVE Cooling MUZ-FD09NA MUZ-FD12NA SHF at rating condition = 0.76 Airflow = 307 CFM 11 10 WB te mpera ture (° F ) 9 71 67 63 8 Total power consumption (kW) 7 0.7 e air r intak Indoo 0.6 ture mpera WB te (°F) 75 85 95 71 67 63 105 14 ir W B te 13 mpe 12 ratu re (° F) 11 10 71 67 63 9 0.5 65 Indo or in take a 15 Total capacity ( 103 Btu/h) Indoo r inta ke air 12 Total power consumption (kW) Total capacity ( 103 Btu/h) 13 SHF at rating condition = 0.73 Airflow = 350 CFM 115 1.2 1.1 1.0 0.9 r Indoo e air intak ture mpera WB te (°F) 71 67 63 0.8 0.7 65 Outdoor intake air DB temperature (°F) 75 85 95 105 115 Outdoor intake air DB temperature (°F) Heating MUZ-FD12NA MUZ-FD09NA Airflow = 381 CFM 8 e tak r in oo d n I 6 °F) F) re (° 16 14 B air D take or in Indo 12 10 tu pera tem 65 70 75 8 6 4 Total power consumption (kW) Airflow = 420 CFM 18 Total capacity ( 103 Btu/h) 10 ( ure rat pe em t DB air 65 70 75 0.8 D ke air r inta Indoo ) re (°F peratu B tem 0.6 75 70 65 Total power consumption (kW) Total capacity ( 103 Btu/h) 12 75 70 65 1.0 0.9 F) re (° tu 0.8 air take or in Indo 0.7 0.6 DB te ra mpe 0.5 5 15 25 35 45 55 Outdoor intake air WB temperature (°F) 0.4 5 15 25 35 45 55 Outdoor intake air WB temperature (°F) This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships between frequency and capacity. 10 7-3. CONDENSING PRESSURE Cooling Data is based on the condition of indoor humidity 50 %. Air flow should be set to High speed. MUZ-FD09NA (PSIG) 580 500 460 420 86 80 75 70 °F) re ( atu per 380 oor Ind 340 m B te D 300 260 68 70 75 80 85 90 95 100 105(°F) (PSIG) 180 175 170 165 160 155 150 145 140 135 130 125 120 68 70 rature (°F) Indoor DB tempe 86 Suction pressure Condensing pressure 540 Outdoor ambient temperature 80 75 70 75 80 85 90 95 Outdoor ambient temperature 100 105(°F) MUZ-FD12NA (PSIG) 580 500 460 86 80 75 70 ) °F re ( 420 atu per m B te D oor Ind 380 340 300 260 68 70 75 80 85 90 95 100 105(°F) (PSIG) 180 175 170 165 160 155 150 145 140 135 130 125 120 68 70 Suction pressure Condensing pressure 540 Outdoor ambient temperature 11 rature (°F) Indoor DB tempe 86 80 75 70 75 80 85 90 95 Outdoor ambient temperature 100 105(°F) Heating Data is based on the condition of outdoor humidity 75%. Air flow should be set to High speed. Data is for heating operation without any frost. MUZ-FD09NA (PSIG) 400 (PSIG) 170 360 B rD doo Condensing pressure 340 75 70 65 In 320 300 280 260 240 75 70 65 160 °F) re( atu per m e t 150 140 Suction pressure 380 58Hz 130 120 110 Ind 100 B rD oo ( re atu er p tem °F ) 58Hz 90 220 80 200 180 70 160 60 50 140 5 10 15 20 25 30 35 40 45 50 55 60 65 70(°F) 5 10 15 20 25 30 35 40 45 50 55 60 65 70(°F) Outdoor ambient temperature Outdoor ambient temperature MUZ-FD12NA (PSIG) 400 (PSIG) 170 380 °F) per em Bt rD doo 340 320 150 70 65 In 140 130 300 280 260 240 58Hz 220 Suction pressure Condensing pressure 75 a 360 75 70 65 160 ( ture 120 B rD oo Ind 110 100 e( tur ra e p tem °F ) 58Hz 90 80 200 180 70 160 60 50 140 5 10 15 20 25 30 35 40 45 50 55 60 65 70(°F) 5 10 15 20 25 30 35 40 45 50 55 Outdoor ambient temperature Outdoor ambient temperature 12 60 65 70(°F) 7-4. STANDARD OPERATION DATA Model Item Unit Total Capacity Btu/h 10,900 — 0.76 — 0.73 — 0.650 0.750 0.960 0.980 Rated frequency Hz 35 43 51 54 MSZ-FD09NA V, phase, Hz kW Input Fan motor current Outdoor unit A MSZ-FD12NA 208/230 , 1 , 60 0.018 0.024 0.024 0.19/0.17 0.25/0.23 MUZ-FD09NA 0.030 0.25/0.23 0.32/0.29 MUZ-FD12NA V, phase, Hz kW 0.632 0.726 0.936 0.950 Comp. current A 2.96/2.68 3.39/3.06 4.40/3.97 4.43/4.01 Fan motor current A Power supply 208/230 , 1 , 60 0.35/0.32 Condensing pressure PSIG 376 355 402 392 Suction pressure PSIG 154 108 148 104 Discharge temperature ˚F 143 144 161 159 Condensing temperature ˚F 112 108 117 115 Suction temperature ˚F 51 46 51 45 Comp. shell bottom temperature ˚F 144 128 146 129 Ref. pipe length ft. 80 70 25 Refrigerant charge (R410A) Intake air temperature Indoor unit 13,600 kW Input Discharge air temperature 2 lb. 9 oz. DB 80 70 ˚F 67 60 67 60 DB ˚F 59 100 56 105 WB Fan speed (High) Intake air temperature ˚F WB Airflow (High) Outdoor unit 12,000 Input Power supply Electrical circuit 9,000 MSZ-FD12NA Cooling Heating SHF Indoor unit Refrigerant circuit MSZ-FD09NA Cooling Heating ˚F 56 — 54 — rpm 1,020 1,120 1,120 1,220 CFM 307 (Wet) 381 350 (Wet) 420 DB ˚F 95 47 95 47 WB ˚F — 43 — 43 Fan speed rpm 810 870 810 870 Airflow CFM 1,102 1,187 1,102 1,187 13 7-5. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY MUZ-FD09NA Correction of Cooling total input 0.5 0 50 100 Capacity correction factors Input correction factors Capacity correction factors 1.0 1.0 0.5 150 (Hz) Correction of Heating total input Correction of Heating capacity 2.0 1.5 0 50 100 Input correction factors Correction of Cooling capacity 1.5 1.5 1.0 0.5 0 150 (Hz) 50 100 3.0 2.0 1.0 150 (Hz) The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor 0 50 100 150 (Hz) The operational frequency of compressor MUZ-FD12NA Correction of Cooling total input 0.5 0 50 100 150 (Hz) Capacity correction factors Input correction factors Capacity correction factors 1.0 1.0 0.5 0 Correction of Heating total input Correction of Heating capacity 1.5 1.5 50 100 150 (Hz) Input correction factors Correction of Cooling capacity 1.5 1.0 0.5 0 50 100 150 (Hz) The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor 2.0 1.0 0 50 100 150 (Hz) The operational frequency of compressor 7-6. TEST RUN OPERATION (How to operate fixed-frequency operation) 1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice). 2. Test run operation starts and continues to operate for 30 minutes. 3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode. 4. Indoor fan operates at High speed. 5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies). 6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller. 14 8 ACTUATOR CONTROL MUZ-FD09NA MUZ-FD12NA 8-1. OUTDOOR FAN MOTOR CONTROL The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running. 5 seconds 15 seconds ON Compressor OFF ON Outdoor fan motor OFF 8-2. R.V. COIL CONTROL Heating . . . . . . . . . . . . . . . . . ON Cooling . . . . . . . . . . . . . . . . . OFF Dry . . . . . . . . . . . . . . . . . . . . OFF NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor. <COOL> <HEAT> 5 seconds Compressor ON OFF R.V.coil ON OFF 5 seconds Outdoor fan ON OFF motor 8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR Sensor Discharge temperature thermistor Indoor coil temperature thermistor Defrost thermistor Purpose Protection Cooling: Coil frost prevention Heating: High pressure protection Cooling: High pressure protection Heating: Defrosting Fin temperature thermistor Protection Outdoor heat exchanger temperature thermistor High pressure protection Ambient temperature thermistor Low ambient temperature operation Compressor LEV ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ 15 Actuator Outdoor fan motor ○ ○ ○ ○ R.V. coil Indoor fan motor ○ ○ 9 SERVICE FUNCTIONS MUZ-FD09VA MUZ-FD12VA 9-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature <JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board. (Refer to 10-6-1.) Jumper JS Defrost finish temperature Soldered (Initial setting) 41°F (5°C) None (Cut) 50°F (10°C) 9-2. PRE-HEAT CONTROL SETTING PRE-HEAT CONTROL When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside temperature. The pre-heat control prevents this interference. The pre-heat control turns ON when outside temperature is 68°F (20 °C) or below. When pre-heat control is turned ON, compressor is energized. (About 50 W) <JK> To activate the pre-heat control, cut the JK wire of the inverter P.C. board. (Refer to 10-6.1) NOTE: When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary. 10 TROUBLESHOOTING MUZ-FD09NA MUZ-FD12NA 10-1. CAUTIONS ON TROUBLESHOOTING 1. Before troubleshooting, check the following 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for miswiring. 2. Take care of the following during servicing 1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, then after confirming the horizontal vane is closed, turn off the breaker and/or disconnect the power plug. 2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board. 3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor. 4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components. 5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires. Lead wiring Housing point 3. Troubleshooting procedure 1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing on and off before starting service work. 2) Before servicing check that the connector and terminal are connected properly. 3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration. 4) Refer to 10-2. and 10-3. 16 10-2. FAILURE MODE RECALL FUNCTION Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details can be recalled. 1. Flow chart of failure mode recall function for the indoor/outdoor unit Operational procedure The cause of abnormality cannot be found because the abnormality does not recur. Setting up the failure mode recall function Turn ON the power supply. <Preparation of the remote controller> While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. First, release RESET button. And release the other two buttons after all LCD in operation display section of the remote controller is displayed after 3 seconds. 1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received. Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1 Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of POWER lamp. 2 Judgment of indoor/outdoor abnormality No (OFF) Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnormalities that can not be recalled with this way. Confirm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to 10-2.2) Yes (Blinks) Before blinking, does POWER lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnormal. Yes No The indoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point with the indoor unit failure mode table. (Refer to indoor unit service manual.) Make sure to check at least two consecutive blinking cycles. 2 The outdoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point with the outdoor unit failure mode table. (Refer to 10-2.3) Make sure to check at least two consecutive blinking cycles. 3 Releasing the failure mode recall function Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller. Repair the defective parts. Deleting the memorized abnormal condition After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above. Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above. NOTE: 1. Make sure to release the failure mode recall function once it is set up, otherwise the unit cannot operate properly. 2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized. 2. Blinking pattern when the indoor unit is abnormal: Blinking at 0.52.5-second OFF second interval Blinking at 0.52.5-second OFF second interval ON OFF Beeps Repeated cycle Beeps Repeated cycle 3.Blinking pattern when the outdoor unit is abnormal: Blinking at 0.52.5-second OFF 3-second ON second interval Beeps Repeated cycle 2.5-second OFF 3-second ON Blinking at 0.5second interval ON OFF No beep Repeated cycle Beeps No beep Repeated cycle 17 Beeps Repeated cycle 2. Flow chart of the detailed outdoor unit failure mode recall function Operational procedure The outdoor unit might be abnormal. Confirm if outdoor unit is abnormal according to the following procedures. Confirm that the remote controller is in the failure mode recall function. With the remote controller headed towards the indoor unit, press TOO COOL or TOO WARM button to adjust the set temperature to 77˚F (25˚C). 1 Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of POWER lamp. 2 1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received. No (OFF) Yes (Blinks) The outdoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point with the outdoor unit failure mode table (10-2.3.). Make sure to check at least two consecutive blinking cycles. 2 The outdoor unit is normal. Releasing the failure mode recall function Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller. Release the failure mode recall function according to the left mentioned procedure. Repair the defective parts. Deleting the memorized abnormal condition After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" (10-2.1.). Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above. NOTE: 1. Make sure to release the failure mode recall function once it is set up, otherwise the unit cannot operate properly. 2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized. 2.Blinking pattern when outdoor unit is abnormal: 2.5-second OFF 3-second ON Blinking at 0.5second interval 2.5-second OFF 3-second ON Blinking at 0.5second interval ON OFF No beep Repeated cycle No beep Repeated cycle Beeps 18 Beeps Repeated cycle 3. Outdoor unit failure mode table POWER lamp (Indoor unit) Abnormal point (Failure mode / protection) Condition Correspondence — — — — — Overcurrent protection stop is continuously performed 3 times within 1 minute after the compressor gets started. • Reconnect connectors. • Refer to 10-5. "How to check inverter/ compressor". • Check stop valve. ○ ○ Thermistor shorts or opens during compressor running. • Refer to 10-5. "Check of outdoor thermistors". Defective outdoor thermistors can be identified by checking the blinking pattern of LED. ○ ○ • Reconnect compressor connector. • Refer to 10-5. "How to check inverter/ compressor". • Check stop valve. — ○ • Reconnect compressor connector. • Refer to 10-5. "How to check inverter/ compressor". — ○ — ○ — ○ — ○ — ○ ○ ○ — ○ OFF None (Normal) 2-time flash 2.5 seconds OFF Outdoor power system 3-time flash 2.5 seconds OFF Discharge temperature thermistor Defrost thermistor 1-time flash every 2.5 seconds Fin temperature thermistor 3-time flash 2.5 seconds OFF P.C. board temperature thermistor 4-time flash 2.5 seconds OFF Ambient temperature thermistor 2-time flash 2.5 seconds OFF Overcurrent 11-time flash 2.5 seconds OFF 4-time flash 2.5 seconds OFF 5-time flash 2.5 seconds OFF — Large current flows into intelligent power module. Compressor synchronous 12-time flash abnormality (Compressor start- 2.5 seconds OFF up failure protection) Waveform of compressor current is distorted. Discharge temperature Temperature of discharge temperature thermistor exceeds 241°F (116°C), compressor stops. Compressor can restart if discharge temperature thermistor reads 212°F (100°C) or less 3 minutes later. • Check refrigerant circuit and refrigerant amount. • Refer to 10-5. "Check of LEV". Temperature of indoor coil thermistor exceeds 158°F (70°C) in HEAT mode. Temperature of defrost thermistor exceeds 158°F (70°C) in COOL mode. • Check refrigerant circuit and refrigerant amount. • Check stop valve. Temperature of fin temperature thermistor on the inverter P.C. board exceeds 167 ~ 176°F (75 ~ 80°C), or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 158 ~ 167°F (70 ~ 75°C). • Check around outdoor unit. • Check outdoor unit air passage. • Refer to 10-5. "Check of outdoor fan motor". — 6-time flash 2.5 seconds OFF High pressure 7-time flash 2.5 seconds OFF Fin temperature/ P.C. board temperature 8-time flash 2.5 seconds OFF Outdoor fan motor — 7-time flash 2.5 seconds OFF — 9-time flash Nonvolatile memory data 2.5 seconds OFF 10-time flash Discharge temperature 2.5 seconds OFF 5-time flash 2.5 seconds OFF 11-time flash DC voltage 2.5 seconds OFF Each phase current of compressor Outdoor fan has stopped 3 times in a • Refer to 10-5. "Check row within 30 seconds after outdoor fan of outdoor fan motor". start-up. Refer to 10-5. "Check of inverter P.C. board". Nonvolatile memory data cannot be read properly. • Replace the inverter P.C. board. Temperature of discharge temperature thermistor has been 122°F (50°C) or less for 20 minutes. • Refer to 10-5. "Check of LEV". • Check refrigerant circuit and refrigerant amount. 8-time flash 2.5 seconds OFF DC voltage of inverter cannot be detected normally. 9-time flash 2.5 seconds OFF Each phase current of compressor cannot be detected normally. • Refer to 10-5. "How to check inverter/ compressor". — ○ • Reconnect compressor connector. • Refer to 10-5. "How to check inverter/ compressor". — ○ ○ ○ — 12-time flash Overcurrent Compressor open- 10-time flash 2.5 seconds phase 2.5 seconds OFF OFF 14-time flash Stop valve (Closed valve) 2.5 seconds OFF Indoor/ unit outdoor unit Outdoor failure mode failure mode recall function recall function LED indication (Outdoor P.C. board) 14-time flash 2.5 seconds OFF Large current flows into intelligent power module (IPM). The open-phase operation of compressor is detected. The interphase short out occurs in the output of the intelligent power module (IPM). The compressor winding shorts out. Closed valve is detected by compressor • Check stop valve current. NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-3.). 19 10-3. TROUBLESHOOTING CHECK TABLE No. 1 Symptom LED indication Outdoor unit 1-time flash every does not oper- 2.5 seconds ate. 2 3 6-time flash 2.5 seconds OFF 11-time flash 2.5 seconds OFF 14-time flash 2.5 seconds OFF 4 5 6 7 8 'Outdoor unit 2-time flash stops and 2.5 seconds OFF restarts 3 minutes later' is repeated. 3-time flash 2.5 seconds OFF 4-time flash 2.5 seconds OFF 9 10 5-time flash 2.5 seconds OFF 11 8-time flash 2.5 seconds OFF 12 10-time flash 2.5 seconds OFF 13 14 unit 15 Outdoor operates. 12-time flash 2.5 seconds OFF 13-time flash 2.5 seconds OFF 1-time flash 2.5 seconds OFF 3-time flash 2.5 seconds OFF 16 17 4-time flash 2.5 seconds OFF Abnormal point/ Condition Correspondence Condition Outdoor power sys- Overcurrent protection stop is continuously performed 3 times • Reconnect connector of comprestem within 1 minute after the compressor gets started, or failure of sor. restart of compressor has repeated 24 times. • Refer to 10-5. "How to check inverter/compressor". • Check stop valve. Outdoor thermistors Discharge temperature thermistor, fin temperature thermistor, • Refer to 10-5. "Check of outdoor defrost thermistor, P.C. board temperature thermistor or ambi- thermistors". ent temperature thermistor shorts or opens during compressor running. Outdoor control sys- Nonvolatile memory data cannot be read properly. tem (POWER lamp of the indoor unit lights up or flashes 7 times.) Serial signal The communication fails between the indoor and outdoor unit for 3 minutes. Stop valve/ Closed valve is detected by compressor current. Closed valve Outdoor unit Outdoor unit is defective. (Other abnormality) High pressure protection Indoor coil thermistor exceeds 158°F (70°C) in HEAT mode. Defrost thermistor exceeds 158°F (70°C) in COOL mode. • Check refrigerant circuit and refrigerant amount. • Check stop valve. Compressor synThe waveform of compressor current is distorted. • Reconnect connector of compreschronous abnormalsor. ity • Refer to 10-5. "How to check inverter/compressor". Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds • Refer to 10-5. "Check of outdoor after outdoor fan start-up. fan motor. • Refer to 10-5. "Check of inverter P.C. board. Each phase current Each phase current of compressor cannot be detected nor• Refer to 10-5. "How to check inof compressor mally. verter/compressor". DC voltage DC voltage of inverter cannot be detected normally. • Refer to 10-5. "How to check inverter/compressor". Frequency drop by Current from power outlet is nearing Max. fuse size. The unit is normal, but check the current protection following. Frequency drop by Temperature of indoor coil thermistor exceeds 131°F (55°C) in • Check if indoor filters are clogged. • Check if refrigerant is short. high pressure proHEAT mode, compressor frequency lowers. • Check if indoor/outdoor unit air cirtection culation is short cycled. Frequency drop by Indoor coil thermistor reads 46°F (8°C) or less in COOL mode, defrosting in COOL compressor frequency lowers. mode Frequency drop by discharge temperature protection Temperature of discharge temperature thermistor exceeds 232 • Check refrigerant circuit and refrig°F (111°C), compressor frequency lowers. erant amount. • Refer to 10-5. "Check of LEV". • Refer to 10-5. "Check of outdoor thermistors". Inverter P.C. board (Parts side) 0.5-second ON 0.5-second ON 2.5-second OFF • Refer to 10-2.2. "Flow chart of the detailed outdoor unit failure mode recall function". Large current flows into intelligent power module. • Reconnect connector of compresWhen overcurrent protection occurs within 10 seconds after sor. compressor starts, compressor restarts after 15 seconds. • Refer to 10-5. "How to check inverter/compressor". • Check stop valve. Discharge tempera- Temperature of discharge temperature thermistor exceeds 241 • Check refrigerant circuit and refrigture overheat protec- °F (116°C), compressor stops. Compressor can restart if diserant amount. tion charge temperature thermistor reads 212°F (100°C) or less 3 • Refer to 10-5. "Check of LEV". minutes later. Fin temperature Temperature of fin temperature thermistor on the heat sink • Check around outdoor unit. /P.C. board temexceeds 167 ~ 176°F (75 ~ 80°C) or temperature of P.C. board • Check outdoor unit air passage. perature thermistor temperature thermistor on the inverter P.C. board exceeds 158 • Refer to 10-5. "Check of outdoor overheat protection ~ 167°F (70 ~ 75°C). fan motor". The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF. Flashing (Example) When the flashing frequency is “2”. OFF • Refer to 10-5. "How to check miswiring and serial signal error. • Check stop valve. Overcurrent protection NOTE: 1. The location of LED is illustrated at the right figure. Refer to 10-6.1. 2. LED is lighted during normal operation. ON • Replace inverter P.C. board. 2.5-second OFF 20 LED Flashing → No. Symptom LED indication Outdoor unit 18 operates. 7-time flash 2.5 seconds OFF 8-time flash 2.5 seconds OFF PAM protection PAM: Pulse Amplitude Modulation 9-time flash 2.5 seconds OFF Inverter check mode The connector of compressor is disconnected, inverter check mode starts. 19 20 Abnormal point/ Condition Condition Low discharge tem- Temperature of discharge temperature thermistor has been perature protection 122°F (50°C) or less for 20 minutes. The overcurrent flows into IGBT (Insulated Gate Bipolar transistor: TR821) or the bus-bar voltage reaches 320 V or more, PAM stops and restarts. 21 Correspondence • Refer to 10-5. "Check of LEV". • Check refrigerant circuit and refrigerant amount. This is not malfunction. PAM protection will be activated in the following cases: 1 Instantaneous power voltage drop (Short time power failure) 2 When the power supply voltage is high. • Check if the connector of the compressor is correctly connected. Refer to 10-5. "How to check inverter/compressor". 10-4. TROUBLE CRITERION OF MAIN PARTS MUZ-FD09NA MUZ-FD12NA Part name Defrost thermistor (RT61) Check method and criterion Figure Ambient temperature Measure the resistance with a tester. thermistor (RT65) Refer to 10-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, the chart of thermistor. Outdoor heat exchanger temperature thermistor (RT68) Discharge temperature thermistor (RT62) Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up. Fin temperature thermistor (RT64) Refer to 10-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, the chart of thermistor. Measure the resistance between terminals using a tester. (Winding temperature: -4 ~ 104°F (-20 ~ 40°C)) WHT 2 3 U-V U-W V-W 1.52 ~ 2.17 Ω Measure the resistance between lead wires using a tester. (Part temperature: 14 ~ 104°F (-10 ~ 40°C)) V WHT 2 Color of lead wire RED – BLK BLK – WHT WHT – RED 1 W Normal Compressor Outdoor fan motor RED BLK U RED BLK 3 Normal 1 W 11 ~ 16 Ω V U Measure the resistance using a tester. (Part temperature: 14 ~ 104°F (-10 ~ 40°C)) R. V. coil (21S4) Normal 970 ~ 1380 Ω Measure the resistance using a tester. (Part temperature: 14 ~ 104°F (-10 ~ 40°C)) WHT LEV RED Normal 22 BLU 37 ~ 54 Ω YLW Color of lead wire WHT – RED RED – ORN YLW – BRN BRN – BLU BRN Expansion valve coil (LEV) ORN 10-5. TROUBLESHOOTING FLOW A How to check inverter/compressor Disconnect the connector (CN61) between compressor and the intelligent power module (IPM). See 10-5. Check the voltage between terminals. Are the voltages balanced? Yes No Replace the inverter P.C. board. See 10-5. Check the compressor. “Check of open phase”. “Check of compressor”. B Check of open phase ● With the connector between the compressor and the intelligent power module disconnected, activate the inverter and check if the inverter is normal by measuring the balance of voltage between the terminals. Output voltage is 50 - 130 V. (The voltage may differ according to the tester.) << Operation method>> Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERATION: Refer to 7-6.) <<Measurement point>> at 3 points BLK (U) - WHT (V) Measure AC voltage between the lead wires at 3 points. BLK (U) - RED (W) WHT(V) - RED (W) NOTE: 1. Output voltage varies according to power supply voltage. 2. Measure the voltage by analog type tester. 3. During this check, LED of the inverter P.C. board flashes 9 times. (Refer to 10-6.1.) C Check of compressor Refer to 10-5. “Check of compressor winding”. Is the compressor normal? Yes Refer to 10-5. “Check of compressor operation time”. Does the compressor operate continuously? Yes No No Replace the compressor. Refer to 10-5. OK. 23 “Check of compressor start failure”. D Check of compressor winding ● Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance between the compressor terminals. <<Measurement point>> at 3 points BLK - WHT Measure the resistance between the lead wires at 3 points. BLK - RED WHT - RED <<Judgement>> Refer to 10-4. 0[Ω] ················· Abnormal [short] Infinite [Ω] ········ Abnormal [open] NOTE: Be sure to zero the ohmmeter before measurement. E Check of compressor operation time <<Judgement>> ●Connect the compressor and activate the inverter. Then measure the time until the inverter stops due to over current. <<Operation method>> Start heating or cooling operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERATION: Refer to 7-6.) <<Measurement>> Measure the time from the start of compressor to the stop of compressor due to overcurrent. 0 second Compressor starts 1 second Abnormal (IPM failure) (Compressor winding short) 2 seconds Abnormal (Compressor lock out) (Starting defect) 10 seconds Abnormal (Poor contact,) (Outdoor P.C. board defect) (Disconnected connector) Abnormal (Refrigerant circuit defect) (Closed valve) 10 minutes Normal F Check of compressor start failure Confirm that 1~4 is normal. • Electrical circuit check 1. Contact of the compressor connector (including CN61) 2. Output voltage of inverter P.C. board and balance of them (See 10-5. ) 3. Direct current voltage between DB61(+) and (-) on the inverter P.C. board 4. Voltage between outdoor terminal block S1-S2 Does the compressor run for 10 seconds or more after it starts? Yes Check the refrigerant circuit. Check the stop valve. No After the compressor is heated with a drier, does the compressor start? 1 No Replace the compressor. Yes 1 Heat the compressor with a drier for about 20 minutes. Do not recover refrigerant gas while heating. Compressor start failure. Activate pre-heat control. (Refer to 9-2. "PRE-HEAT CONTROL SETTING") Heating part 24 G Check of outdoor thermistors Disconnect the connector of thermistor in the outdoor P.C. board (see below table), and measure the resistance of thermistor. Is the thermistor normal? (Refer to 10-6.1.) Yes No Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board. Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch. Does the unit operate for 10 minutes or more without showing thermistor abnormality? Yes No Replace the inverter P.C. board. OK. (Cause is poor contact.) Thermistor Symbol Connector, Pin No. Defrost RT61 Between CN641 pin1 and pin2 Discharge temperature RT62 Between CN641 pin3 and pin4 Fin temperature RT64 Between CN642 pin1 and pin2 Ambient temperature RT65 Between CN643 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3 Board Inverter P.C. board H Check of R.V. coil First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4. In case CN721 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector although no signal is being transmitted to R.V. coil. Check if CN721 is connected. Unit operates COOL mode even if it is set to HEAT mode. Disconnect connector (CN61) between the compressor and the intelligent power module. Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode). Is there 230 VAC between CN721 and on the inverter P.C. board 3 minutes after the power supply is turned ON? No Replace the inverter P.C. board. Yes Replace the 4-way valve. Unit operates HEAT mode even if it is set to COOL mode. Disconnect connector (CN61) between the compressor and the intelligent power module. Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode). Is there 230 VAC between CN721 and on the inverter P.C. board 3 minutes after the power supply is turned ON? No Replace the 4-way valve. 25 Replace the inverter Yes P.C. board. I Check of outdoor fan motor Disconnect CN932 from the inverter P.C. board, and measure the resistance of the outdoor fan motor. Is the outdoor fan motor normal? (Refer to 10-4.) Yes No Replace the outdoor fan motor. Replace the inverter P.C. board. J Check of power supply Disconnect the connector (CN61) between compressor and intelligent power module. Turn ON power supply and press EMERGENCY OPERATION switch. Rectify indoor/outdoor connecting wire. Does POWER lamp on the indoor unit light up? Yes No Is there voltage 280 ~ 370 VDC between DB61 (+) and DB61 (–) on the inverter P.C. board? (Refer to 10-6.1.) No Yes Check the electric parts in main circuit. Yes Is there voltage 208/230 VAC between the indoor terminal block S1 and S2? Dose LED on the inverter P.C. board light up or flash? (Refer to 10-6.1.) Yes If light up, OK. If flash, refer to 10-3. No No Replace the indoor electronic control P.C. board. Replace the inverter P.C. board. 280 ~ 370 VDC DB61 Inverter P.C. board (Solder side) 26 K Check of LEV (Expansion valve) Turn ON the power supply. <Preparation of the remote controller> While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. First, release RESET button. And release the other two buttons after all LCD except the set temperature in operation display section of the remote controller is displayed after 3 seconds. Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1 1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received. Expansion valve operates in full-opening direction. Do you hear the expansion valve "click, click·······"? Do you feel the expansion valve vibrate on touching it ? No Is LEV coil properly fixed to the expansion valve? No Yes Does the resistance of LEV coil have the characteristics? Yes (Refer to 10-4.) No Replace the LEV coil. Yes OK. Properly fix the LEV coil to the expansion valve. Measure each voltage between connector pins of CN724 on the inverter P.C. board. 1. Pin (-) — Pin (+) 2. Pin (-) — Pin (+) 3. Pin (-) — Pin (+) 4. Pin (-) — Pin (+) Is there about 3 ~ 5 VAC between each? NOTE: Measure the voltage by an analog tester. Yes Replace the expansion valve. NOTE: After check of LEV, do the undermentioned operations. 1. Turn OFF the power supply and turn ON it again. 2. Press RESET button on the remote controller. 27 No Replace the inverter P.C. board. L Check of inverter P.C. board Check the outdoor fan motor. (Refer to 10-5. .) Is the fuse (F901) blown on the inverter P.C. board? Yes No Inverter P.C. board (Solder side) Check the connection of the connectors (CN932) of the outdoor fan motor. If the connection is poor, make it correct. CN932 Operate the outdoor unit by starting EMERGENCY OPERATION. Check the LED indication on the inverter P.C. board. Does the LED flash 10 times? Yes (10-time flash) No Check the corresponding parts following LED indication. (Refer to 10-3.) Replace the inverter P.C. board. 28 M How to check miswiring and serial signal error Turn OFF the power supply. Is there rated voltage in the power supply? Check the power supply. No Yes Turn ON the power supply. Is there rated voltage between outdoor terminal block S1 and S2? Yes Check the wiring. No Press EMERGENCY OPERATION switch once. Does AREA-L lamp light up? <Confirmation of the power to the indoor unit> No Yes Is serial signal error indicated 6 minutes later? No Yes Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire? No Yes Correct them. A Turn OFF the power supply. Check once more if the indoor/outdoor B connecting wire is not miswiring. Short-circuit outdoor terminal block S2 and S3. 1 1. Miswiring may damage indoor electronic control P.C. board during the operation. Be sure to confirm the wiring is correct before the operation starts. 3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board or the outdoor electronic control P.C. board is normal, LED blinks 6 times after 3 minutes. Turn ON the power supply. Does the LED on the inverter P.C. board or the outdoor electronic control P.C. board repeat "3.6-second-OFF and 0.8-secondON quick blinking"? 3 Yes A • Turn OFF inverter-controlled lighting equipment. • Turn OFF the power supply and then turn ON again. • Press EMERGENCY OPERATION switch. Is serial signal error indicated 6 minutes later? Yes B • Reinstall either the unit or the light each other away. • Attach a filter No on remote control receiving section of the indoor unit. Turn OFF the power supply. Remove the short-circuit between outdoor terminal block S2 and S3. Turn ON the power supply. Is there amplitude of 10 to 20 VDC between outdoor terminal block S2 and S3? <Confirmation of serial signal> Yes Is there rated voltage between indoor terminal block S1 and S2? <Confirmation of power voltage> Yes No (Lighted or not lighted) 2. Be careful of the residual voltage of smoothing capacitor. No Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, Yes intermediate connection, poor contact to the terminal block? No No Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, Yes intermediate connection, poor contact to the terminal block? No Replace the indoor electronic control P.C. board. Be sure to release the failure-mode recall function after checking. 29 Replace the inverter P.C. board or the outdoor electronic control P.C. board. 2 Replace the indoor/ outdoor connecting wire. Replace the indoor/ outdoor connecting wire. N Electromagnetic noise enters into TV sets or radios Is the unit grounded? Yes Is the distance between the antennas and the indoor unit within 9.91 ft., or is the distance between the antennas and the outdoor unit within 9.91 ft.? Ground the unit. No Yes Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit. Yes Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit. Yes Replace or repair the antenna. Replace or repair the coaxial cable. Yes Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas. No Is the distance between the TV sets or radios and the indoor unit within 3.28 ft., or is the distance between the TV sets or radios and the outdoor unit within 9.91 ft.? No Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the antenna wiring? No Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close? No Even if all of the above conditions are fulfilled, the electromagnetic noise may enter, depending on the electric field strength or the installation condition (combination of specific conditions such as antennas or wiring). Check the followings before asking for service. 1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave) 2. Channel, frequency, broadcast station affected by the electromagnetic noise 3. Channel, frequency, broadcast station unaffected by the electromagnetic noise 4. Layout of: indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver 5. Electric field intensity of the broadcast station affected by the electromagnetic noise 6. Presence or absence of amplifier such as booster 7. Operation condition of air conditioner when the electromagnetic noise enters in 1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise. 2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise. 3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise. 4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise. 30 10-6. TEST POINT DIAGRAM AND VOLTAGE 1. Inverter P.C. board MUZ-FD09NA MUZ-FD12NA Smoothing capacitor (C63) DB61 DC260 ~300 V (-) (+) Back side of unit Smoothing capacitor (C62) Smoothing capacitor (C61) Fuse (F701) 250 V 3.15 A Fuse (F801) 250 V 3.15 A AC 208/230 V R.V. coil (CN721) 208/230 VAC Fuse (F901) 250 V 3.15 A Output to drive compressor (LDU, LDV, LDW) 100 Discharge temperature thermistor /RT62 (CN641) Defrost thermistor /RT61(CN641) Ambient temperature thermistor /RT65 (CN643) Outdoor heat exchanger temperature thermistor /RT68(CN644) Fin temperature thermistor /RT64 (CN642) Front side of unit Output to drive outdoor fan motor (CN932) AC 208/230 V LEV connector (CN724) Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68) 200 80 Fin temperature thermistor(RT64) 160 Discharge temperature thermistor(RT62) 60 600 50 40 30 20 10 14 32 50 68 86 Temperature(°F) 104 140 Resistance(kΩ) 70 700 Resistance(kΩ) Resistance(kΩ) Jumper wire for pre-heat control setting (JK) 180 90 0 -4 Jumper wire for changing defrost setting (JS) 500 400 300 120 100 80 60 200 40 100 20 0 32 50 68 86 104 122 140 158 176 194 212 230 248 Temperature(°F) 31 0 32 50 68 86 104 122 140 158 176 Temperature(°F) 11 DISASSEMBLY INSTRUCTIONS <"Terminal with locking mechanism" Detaching points> The terminal which has the locking mechanism can be detached as shown below. There are two types (refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching. (1) Slide the sleeve and check if there is a locking lever or not. Sleeve Locking lever (2) The terminal with this connector has the locking mechanism. Slide the sleeve. Pull the terminal while pushing the locking lever. Hold the sleeve, and pull out the terminal slowly. Connector 11-1. MUZ-FD09NA MUZ-FD12NA NOTE: Turn OFF power supply before disassembling. OPERATING PROCEDURE PHOTOS 1. Removing the cabinet Photo 1 (1) Remove the screw fixing the service panel. (See Photo 1.) (2) Pull down the service panel and remove it. (See Photo 1.) (3) Remove the screws fixing the conduit cover. (See Photo 2.) (4) Remove the conduit cover. (See Photo 2.) (5) Disconnect the power supply wire and indoor/outdoor connecting wire. (6) Remove the screws fixing the top panel. (See Photo 1.) (7) Remove the top panel. (See Photo 1.) (8) Remove the screws fixing the cabinet. (9) Remove the cabinet. (10) Remove the screws fixing the back panel. (11) Remove the back panel. Screws of the top panel Screw of the cabinet Screws of the top panel Back panel Screw of the service panel Photo 2 Hooks Screw of the conduit cover Conduit cover Screws of the cabinet Conduit plate 32 Service panel OPERATING PROCEDURE PHOTOS 2. Removing the inverter assembly, inverter P.C. board (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P.C. board> CN721 (R.V.coil) CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature thermistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV) (3) Remove the compressor connector (CN61). (4) Remove the screws fixing the relay panel. (See Photo 3.) (5) Remove the inverter assembly. (See Photo 4.) (6) Remove the screw of the ground wire and screw of the T.B.support. (See Photo 4.) (7) Remove the inverter P.C. board from the inverter assembly. Photo 3 Screws of the relay panel Photo 4 (Inverter assembly) Heat sink Inverter P.C. board Screw of the T.B.support T.B.support 3. Removing R.V. coil (1) Remove the cabinet and panels. (Refer to 1.) (2) Remove the R.V. coil. (See Photo 5.) Screw of the ground wire 4. Removing the discharge temperature thermistor, defrost thermistor and outdoor heat exchanger temperature thermistor. Photo 5 R.V. coil (1) Remove the cabinet and panels. (Refer to 1.) (2) Pull out the discharge temperature thermistor from its holder. (See Photo 5.) (3) Pull out the defrost thermistor from its holder. (See Photo 6.) (4) Pull out the outdoor heat exchanger temperature thermistor from its holder. (See Photo 6.) Discharge temperature thermistor 33 OPERATING PROCEDURE PHOTOS Photo 6 5. Removing outdoor fan motor (1) (2) (3) (4) (5) (6) Remove the cabinet and panels. (Refer to 1.) Disconnect the connectors for outdoor fan motor. Remove the propeller nut. (See Photo 7.) Remove the propeller. (See Photo 7.) Remove the screws fixing the fan motor. (See Photo 7.) Remove the fan motor. Outdoor heat exchanger temperature thermistor 6. Removing the compressor and 4-way valve (1) Remove the cabinet and panels. (Refer to 1.) (2) Remove the inverter assembly. (Refer to 2.) (3) Recover gas from the refrigerant circuit. NOTE: Recover gas from the pipes until the pressure gauge shows 0 PSIG. Defrost thermistor Photo 7 (4) Detach the welded part of the suction and the discharge pipe connected with compressor. (5) Remove the nuts of compressor legs. (6) Remove the compressor. (7) Detach the welded part of pipes connected with 4-way valve. (See Photo 8.) Propeller Screws of the outdoor fan motor Propeller nut Photo 8 Welded parts of 4-way valve 34 35 TM HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN © Copyright 2008 MITSUBISHI ELECTRIC CO.,LTD Distributed in Nov. 2008. No. OBH498 REVISED EDITION-B 5 Distributed in Mar. 2008. No. OBH498 REVISED EDITION-A 7 Distributed in Jan. 2008. No. OBH498 7 Made in Japan New publication, effective Nov. 2008 Specifications subject to change without notice.