Download Dimplex WI 40CG Operating instructions
Transcript
CE INSTALLATION and OPERATING INSTRUCTIONS Water-Water Heat Pump for indoor installation WI 40CG Order No.: 452225.66.94 WI 90CG FD 8209 CONTENTS 1 PLEASE READ IMMEDIATELY 3 1.1 1.2 1.3 Important notes Legal requirements and guidelines Energy-saving heat pump operation 2 APPLICABILITY OF THE HEAT PUMP 2.1 2.2 Field of application Mode of operation 3 BASIC UNIT 4 4 ACCESSORIES 5 4.1 4.2 Control cable Heat pump control 5 TRANSPORT 5 6 INSTALLATION SITE 6 6.1 6.2 General notes Sound emission 7 INSTALLATION 7.1 7.2 7.3 Connection of the heating system Connection of the heat source Connection to power supply 8 STARTUP 8.1 8.2 General notes Preparation 9 MAINTENANCE/CLEANING 9.1 9.2 9.3 Maintenance Cleaning the heating side Cleaning the heat source side 10 MALFUNCTIONS/ TROUBLE SHOOTING 10.1 Eliminating minor faults 11 SHUTDOWN 11.1 11.2 Shutdown during summer Final discommissioning/disposal 12 ANNEX 4 6 8 9 10 10 11 2 PLEASE READ IMMEDIATELY 1 PLEASE READ IMMEDIATELY CAUTION ! After cleaning it is essential to neutralize the system by suitable means in order to prevent secondary damages to the heating system. 1.1 Important notes CAUTION ! During transport the heat pump must not be inclined to any side by more than 45°. CAUTION ! The heat pump is not intended to meet the increased heat requirements of de-humidifying a building. Therefore it is necessary to use dedicated equipment provided by the client to generate the extra amount of heat needed for that purpose. CAUTION ! The heat pump is not attached to the wooden grating. 1.2 Legal requirements and guidelines CAUTION ! Disconnect all voltage supplies prior to opening the unit. The heat pump complies with all relevant DIN/ VDE regulations and EEC directives. These are listed in the attached CE conformity statement. CAUTION ! Electric wiring of the heat pump must comply with the applicable VDE, EN and IEC standards. Furthermore, the electrical supply conditions stipulated by the power provider must be observed. Service of the heat pump must be performed by authorized and experienced service personnel only. CAUTION ! The working fluid R407C is free of CFC, does not disturb ozone and is non-combustible. The heat pump must be interconnected with the heat source and the heating system in compliance with the relevant regulations. CAUTION ! Service of the heat pump must be performed by authorized and experienced service personnel only. CAUTION ! Ensure the clockwise rotating field when connecting the supply cable. CAUTION ! 1.3 Energy-saving heat pump operation The covering hood can not be painted. By operating this heat pump you contribute to the protection of our environment. Proper dimensioning of the heating system and the heat source are of prime importance for the efficiency of heat pump operation. Low water inlet temperatures are of particular importance. Therefore, all connected heat consumers must be suitable for low water inlet temperatures. An increase in the heating water temperature by 1 K causes an increase in the electrical power consumption by approx. 2.5%. An underfloor heating system with forward temperatures between 30 and 40 °C is particularly well suited for energy-saving operation. CAUTION ! The well water must be of the water quality specified. CAUTION ! The startup procedure must follow the Installation and Operanting Instructions for the heat pump control. 3 APPLICABILITY OF THE HEAT PUMP BASIC UNIT 2 APPLICABILITY OF THE HEAT PUMP 3 2.1 Field of application The water-water heat pump can be used in existing or new heating plant installations. Water is used as the heat transfer medium. The water may be supplied from a well or similar sources. BASIC UNIT The basic unit consists of the heat pump for indoor installation, covering hood and basic control and is delivered ready for installation. The refrigerating circuit is filled with the refrigerant R407C. The covering hood is lined with sound insulating material. The basic control contains all components that are required for heat pump operation. The power cable and the load cable (accessories) between heat pump and basic control have to be installed by the client. CAUTION ! The well water must be of the water quality specified. The well pump, that is also provided by the client, has to be interfaced with the basic control. Make sure that the rating of the motor protector istalled by the client is sufficient for the pump in use. Under normal conditions an intermediate circuit has to be provided. If the system is to operated without an intermediate circuit it is, independent of the leagl requirements, necessary to perform a water analysis in order to be able to detzermine the compatability of the ground water with the evaporator of the heat pump (refer to the project designing and installation manual for heating heat pumps). 1 2 6 7 3 4 5 2.2 Mode of operation A well pump feeds the water to the evaporator of the heat pump. There its thermal content is transferred to the working fluid (refrigerant) in the refrigeration circuit. Then the working fluid is sucked into the electrically powered condensor, where it is condensed , i.e. "pumped" to a higher temperature level. How-ever, the electric energy used to drive this process is not lost but is also transferred to the working fluid. Finally, the working fluid reaches the liquefier unit where its thermal energy is transferred to the water circulating through the heating water system. Depending on the operating point, the temperature in the heating water system may rise up to 55 °C. 1) 2) 3) 4) Condensor Liquefier Evaporator Dirt trap 5) Flow switch 6) Terminalbox 7) Filter dryer CAUTION ! The working fluid R407C is free of CFC, does not disturb ozone and is non-combustible. CAUTION ! 4 The covering hood can not be painted. ACCESSORIES TRANSPORT 4 ACCESSORIES 4.1 Control cable 5 Two control cables serve to interconnect the heat pump control and the basic control unit as well as the basic control unit and the terminal box of the heat pump. These cables are available in several lengths. 4.2 Heat pump control The use of a heat pump control from our product line is mandatory for the operation of your waterwater heat pump. The heat pump control is a comfortable electronic control device. It is available as an accessory. The heat pump control regulates and monitors the entire heating system in regard to outdoor temperatures, hot water heating process and safety-relevant equipment. The functional method and the operation of the heat pump control is described in detail in the accompanying Installation and Operating Instructions. TRANSPORT A lift truck can be used for transporting the heat pump over smooth surfaces. Carrier belts should be used where it must be transported across uneven surfaces or through staircases. The belts can be inserted directly through the wooden grate. As an alternative the unit may be lifted by means of eyebolts that can be screwed into the corners of the base frame. CAUTION ! The heat pump is not attached to the wooden grate. 45° 45° Eye bolt CAUTION ! The heat pump must not be inclined by more than 45° (to any side). 5 INSTALLATION SITE INSTALLATION 6 INSTALLATION SITE 6.1 General notes 7 The heat pump is intended for indoor installation. The mounting surface must be smooth, solid and load-bearing. If necessary, the heat pump must be levelled by shimming. INSTALLATION 7.1 Connection of the heating system Before connecting the heat pump to the heating system, the heating plant should be flushed thoroughly to prevent any particles to flow through the heating circuit which could impair smooth heatpump operation. The installation site of the heat pump must be chosen so that service work can be performed easily. This is ensured by a free space of about 1 m at the front and both sides of the heat pump. Flexible pressure hoses should be used for connections in order to prevent noise from being conducted to the heating circuit. The completed heating circuit must be filled, ventilated and checked for leakage. Where the risk of frost exists the filled system must remain in operation continuously so that frost damage is precluded. 0,2 m 7.2 Connection of the heat source 1m Wärmepumpe Heat pump 1m Connect the water lines from the well to the flow and return lines of the heat source. For this observe the refrigeration and hydraulic plans. 1m CAUTION ! The well water must be of the water quality specified. 6.2 Sound emission Owing to the sound insulation the heat pump emits very little noise. But placing a suitable decoupled rubber mat underneath the heat pump base frame is recommended in order to prevent any sound conductance to the foundation, especially in case of uneven foundations. 6 INSTALLATION 7.3 Connection to power supply %DVLFFRQWUROXQLW It must be ensured that the the power supply to the terminals of the well pump will not be turned off by the tariff contactor to make sure that the cutoff delay of the well pump remains effective.The motor protector installed by the client must be adjusted according to the data specified by the pump manufacturer. The terminals for the power supply to the well pump are X1-L11/L21/L31. +HDWSXPSFRQWURO /RDGRIKHDWSXPS 3(9$& /RDGRIZHOOSXPS $FFHVVRU\FRQWUROFDEOH 3(9$& 5) /13(9$& H O E &RQWUROFXUUHQW D F O R U W Q R F \ U R V V H F F $ U R V Q H G Q R & 3HULSKHUDO KHDWSXPSFRQWURO 3HULSKHUDO KHDWSXPSDXWRFRQWURO 3 :6 :6 7! 7! +': +'% +'6% (*6 3 3 3 Connection between the basic control unit and the terminal box of the heat pump The connection between the terminal box of the heat pump and the basic control unit as well as between the brine pump and the basic control unit must be provided by the client. +]J +]J 1' Control voltage The basic control unit is powered by the heat pump control via the control cable. A separate cable to the basic control unit is not required. $) 7 ')6 ) :HOOSXPS Select the cable cross section according to the power consumption of the heat pump (see technical specifications) and the power consumption of the used brine circulating pump. All components needed for connecting the electric supply to the heat pump are located in the basic control unit. Mount this unit to a smooth wall surface of the building. A heat pump control is necessary for controlling these components. The wiring of the descrete components contained in the basic control unit and in the heat pump control must be provided by the client (plug connectors). Run the power cables in the existing plastic tubing. Terminals of the condenser: X1-1/2/3/PE X1-4/5/6/PE Power supply for the basic control unit A breaker controlling all poles with at least 3 mm contact gap (e.g. EVU blocking contactor, power contactor) and a three pole automatic circuit breaker separating simultaneously all external leads must be provided in the power feed to the basic control unit. Select the wiring cross section according to the power consumption of the heat pump, the technical power connecting requirements stipulated by the respective power provider and the requirements of VDE 0100. The power consumption of the heat pump is specified in the technical documentation. The terminals (X1-L1/L2/L3 at the circuit breaker) are rated for a maximum wire gauge of 16 mm². Terminals of the well pump: X1-7/8/9/PE 7 INSTALLATION STARTUP Control cable between the basic control unit and the terminal box of the heat pump The control cable between the terminal box of the heat pump and the basic control unit is available as a custom-made cable (see price list). Connect the round 16-pole connector of the control cable to the basic control unit. Slightly rotate the connector ccw and cw to feel for the anti-rotation lock. Then insert the connector until the ring nut of the contactor catches. Turn the ring nut clockwise to secure the connector in its position. Feed both the rectangular connec-tors through the opening in the bottom right corner of the basic control unit and plug them into the matching connectors (non-interchange-able). Use the strain relief to secure the control cable in the basic control unit . Any excessive cable length should be kept in the cable duct or as a loop on the wall. 8 8.1 General notes For reasons of warranty, comissioning of the heat pump should be performed by authorized service personnel. 8.2 Preparation Confirm the following prior to startup: Connection between the heat pump control and the basic control unit (using the 1.5 m control cable, see price list) The power for the heat pump control can be provided from the basic control unit. Plug the round connector of the cable into the basic control unit and connect the two rectangular connectors to the heat pump control. A more detailed description is contained in the instal-lation and operating instructions for the heat pump control. STARTUP - The heat source system and the heating water circuit must have been filled and tested. - The shut-off valves in the well and heating circuits must be in the correct position. - The power supply field must rotate in the cw direction. - The heat pump control must have been prepared according to the relevant installation and operating instructions. CAUTION ! The startup procedure must follow the installation and operating instructions for the heat pump control. CAUTION ! Ensure the clockwise rotating field when connecting the supply cable. (If the field rotates ccw the heat pump generates no power and is very loud.) 8 MAINTENANCE/CLEANING 9 MAINTENANCE/ CLEANING CAUTION ! After cleaning it is essential to neutralize the system by suitable means in order to prevent secondary damages to the heating system. 9.1 Maintenance The heat pump operates maintenance-free. Make sure that the heat source and heating circuits are kept free from impurities to prevent malfunction of the heat pump due to dirt collections in the heat exchangers. Should a malfunction of that type occur, clean the unit as described below. CAUTION ! Attention - heating plant installers Depending on the fill water quality and volume occasional dirt collection (rust sludge, calcerous deposits) may occur especially in case of mixed installations and plastic piping so that the performance of the heating system may be compromized. This is due to the water hardness and the oxygen solved in the fill water and the oxygen in the air that may enter the system at valves, fittings and plastic pipes (oxygen diffusion). To prevent this from happening we recommend the use of a physical water treatment device like e.g. ELYSATOR . CAUTION ! Disconnect all voltage supplies prior to opening the unit. 9.2 Cleaning the heating side 9.3 Cleaning the heat source side Oxygen may cause the formation of oxydation products (rust) in the hot water circuit. Pipe connections must not allow oxygen diffusion which applies particularly to pipes used in underfloor heating. Remnants of lubricants and sealants may also contaminate the heating water. Install the enclosed dirt trap in the heat source inlet of the heat pump in order to protect the evaporator from impurities. After the initial startup the filter screen of the dirt trap should be cleaned regularly in relatively short intervalst. As soon as detectable impurities become less the intervalls can be extended accordingly. If contamination is so bad that the performance of the liquefier in the heat pump is degraded, the installation must be cleaned by a specialist. Based on today's experience we suggest to use 5% phosphorous acid for general cleaning or, if cleaning is required in shorter intervals, 5% formic acid . In both cases the cleaning liquid should be used at room temperature. Scavenging the heat exchanger in the direction opposite to the normal flow is recommendable. In order to prevent acid-containing cleaning liquid from entering the heating water circuit we suggest to connect the scavenging unit directly to the forward and return lines of the liquefier in the heat pump. Following that it is essential to thoroughly rinse the system with a suitable neutralizing agent so that all remnants of the cleaning agent are removed from the system. Handle acids with care. Always follow the instructions of the occupational associations. In case of doubt consult with the manufacturer of the cleaning agent! 9 MALFUNCTIONS/TROUBLE SHOOTING SHUTDOWN 10 MALFUNCTIONS/ TROUBLE SHOOTING 10.1 Eliminating minor faults 11 SHUTDOWN 11.1 Shutdown during summer Heat pumps used exclusively for heating purposes can be shut down for the summer time (no hot water service). This is done by means of the operating mode selector of the heat pump control. Please observe the Installation and Operating Instructions. This heat pump is a maintenance-free highquality product and should run without any problems. Most faults that may occur can be remedied by the user. Please refer to chapter 'Malfunctions and Troubleshooting' in the installation and operating instructions for the heat pump control. Due to the risk of frost damages, shutdown without draining the heating circuit is permissible only in regions where outdoor temperatures do not drop below 0 °C . If you are not successful in eliminating a fault please contact your customer service. CAUTION ! 11.2 Final decommissioning/disposal Service of the heat pump must be performed by authorized and experienced service personnel only. Before removing the heat pump it is necessary to disconnect all cables as well as the connections to the heat source and the heating system. Furthermore, all electrical supplies must be switched off and all valves must be closed. Please observe the applicable environmental regulations in regard to recycling, reuse and disposal of working materials and fluids according to DIN EN 378, when taking the heat pump out of operation. Especially the disposal of refrigerants and refrigeration machine oil must comply with the relevant regulations. 10 ANNEX 12 ANNEXE 12.1 Dimensional drawings 12.1.1 Heat pump ..40C 12.1.2 Heat pump ..90C 12 13 12.2 Equipment data 14 12.3 Performance characteristics/ pressure losses Characteristics ..40C / 2 cond. Characteristics ..40C / 1 cond. Pressure losses ..40C Characteristics ..90C / 2 cond. Characteristics ..90C / 1 cond. Pressure losses ..90C 15 16 17 18 19 20 12.3.1 12.3.2 12.3.3 12.3.4 12.3.5 12.3.6 12.4 12.4.1 12.4.2 12.4.3 12.4.4 12.4.10 Circuit diagrams External basic control unit ..40C Load ..40C Internal terminal box ..40C Terminal assignment incl. heat pump control ..40C Legend ..40C External basic control unit ..90C Load ..90C Internal terminal box ..90C Terminal assignment incl. heat pump control ..90C Legend ..90C 12.5 Hydraulic schematic diagram 31 12.6 CE conformity statement 32 12.7 Warranty certificate 33 12.4.5 12.4.6 12.4.7 12.4.8 12.4.9 11 21 22 23 24 25 26 27 28 29 30 Heat source inlet Heat source outlet Heating water outlet 12 External thread External thread Connections on heating side: Connections on heat source side: Inlet of control cable/load cable Heating water inlet Turning lock ANNEX: 12.1 DIMENSIONAL DRAWINGS 12.1.1 Heat pump ..40C Heat source outlet Inlet of control cable/load cable Heat source inlet Turning lock Connections on heat source side 2" External thread Heating water outlet Heating water inlet ANNEX: 12.1 DIMENSIONAL DRAWINGS 12.1.2 Heat pump ..90C 13 ANNEX: 12.2 EQUIPMENT DATA Equipment data (48,30(17'$7$IRUZDWHUZDWHUKHDWLQJKHDWSXPS 7<3($1'0$5.(7,1*'(6,*1$7,21 02'(/ & & 7\SHRISURWHFWLRQDFFRUGLQJWR(1 ,3 ,3 6LWHRILQVWDOODWLRQ LQGRRUV LQGRRUV 3(5)250$1&('$7$ 7HPSHUDWXUHUDQJHVIRURSHUDWLRQ +HDWLQJZDWHUIORZ & XSWR XSWR &ROGZDWHUKHDWVRXUFH & WR WR +HDWLQJZDWHUWHPSHUDWXUHVZLQJDW%: +HDWLQJHIILFLHQF\SHUIRUPDQFHILJXUHDW:: . N: N: DW:: N: N: DW:: N: N: 6RXQGSRZHUOHYHO G%$ +HDWLQJZDWHUIORZDWLQWHUQDOSUHVVXUHGLIIHUHQFH PñK3D %ULQHIORZDWLQWHUQDOSUHVVXUHGLIIHUHQFHKHDWVRXUFH PñK3D 5HIULJHUDQWWRWDOILOOLQJZHLJKW W\SHNJ 5& 5& ',0(16,216&211(&7256$1':(,*+7 8QLWGLPHQVLRQVZLWKRXWFRQQHFWRUV :[%[/PP [[ [[ 8QLWFRQQHFWRUVIRUKHDWLQJFLUFXLW LQFK *ó´RXWVLGH *´RXWVLGH 8QLWFRQQHFWRUVIRUKHDWVRXUFH LQFK *ò´RXWVLGH *´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haracteristics ..40C / 2 condensers Wasseraustrittstemperatur in [°C] Water outlet temperature [°C] Heating capacity [kW] Heizleistung in [kW] 70 35 50 60 50 40 30 20 Bedingungen: Conditions: Heating water flow 3500 Heizwasserdurchsatz 2,9 l/h m³/h Cold water flow Soledurchsatz 8,49500 m³/hl/h 10 0 Performance figure in heating operation (incl. pump power consumptions) Leistungszahl im Heizbetrieb (incl. der anteiligen Pumpenleistungen) 8 35 7 6 5 5 4 3 2 1 0 Power consumptionin[kW] power consumptions) Leistungsaufnahme [kW](incl. (incl.pump der anteiligen Pumpenleistungen) 12 5 10 35 8 6 4 2 0 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 Soleeintrittstemperatur in [°C] Cold water inlet temperature [°C] 15 ANNEX: 12.3 PERFORMANCE CHARACTERISTICS/PRESSURE LOSSES 12.3.2 Characteristics ..40C / 1 condenser Wasseraustrittstemperatur in [°C] Water outlet temperature [°C] Heating capacity [kW] Heizleistung in [kW] 40 35 35 50 30 25 20 15 Bedingungen: Conditions: Heating water flow 3500 Heizwasserdurchsatz 2,9 l/h m³/h Cold water flow Soledurchsatz 8,49500 m³/hl/h 10 5 0 Performance figure in heating operation (incl. pump power consumptions) Leistungszahl im Heizbetrieb (incl. der anteiligen Pumpenleistungen) 10 9 8 7 6 5 4 3 2 1 0 35 50 Power consumption in [kW] power consumptions) Leistungsaufnahme [kW](incl. (incl.pump der anteiligen Pumpenleistungen) 8 6 50 35 4 2 0 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 Kaltwassereintrittstemperatur [°C] Cold water inlet temperature in [°C] 16 ANNEX: 12.3 PERFORMANCE CHARACTERISTICS/PRESSURE LOSSES 12.3.3 Pressure losses ..40C Pressure loss in [Pa] Druckverlust [Pa] 35000 Druckverluste Pressure losses in Verdampfer the evaporator Water/water 40C at30C 10°C Sole/Wasser bei 10°C 30000 Pressure loss 0,175 bar at Druckverlust 15 kPa bei nominal cold water flow 9500 l/h 25000 Sole-Nenndurchfluß 8,4 m³/h 20000 15000 10000 5000 0 0 1 2 3 4 5 6 7 8 Cold water flow 1000l/h Kaltwasserdurchfluß in [m³/h] 9 10 11 12 Pressure loss in [Pa] Druckverlust [Pa] 30000 Druckverluste Verflüssiger Pressure losses in the liquefier Sole/Wasser bei 10°C Water/water 40C 30C at 35°C 25000 Pressure loss 0,14 bar at nominal Druckverlust 9 kPa bei heating water flow 3500 l/h 20000 Heizwasser-Nenndurchfluß 2,9 m³/h 15000 10000 5000 0 0 0,5 1 1,5 2 2,5 3 Heizwasserdurchfluß in [m³/h] Heating water flow [l/h] 17 3,5 4 4,5 5 ANNEX:12.3PERFORMANCECHARACTERISTICS/PRESSURELOSSES 12.3.4 Characteristics ..90C / 2 condensers Wasseraustrittstemperatur in [°C] Water outlet temperature [°C] Heating capacity [kW] Heizleistung in [kW] 130 120 110 35 50 100 90 80 70 60 50 40 Bedingungen: Conditions: Heizwasserdurchsatz 6,0 l/h m³/h Heating water flow 8000 Cold water flow 20000 Soledurchsatz 16,0 m³/hl/h 30 20 10 0 Performance in heating(incl. operation (incl. pump power consumptions) Leistungszahlfigure im Heizbetrieb der anteiligen Pumpenleistungen) 8 7 35 6 5 5 4 3 2 1 0 Leistungsaufnahme in [kW] (incl. der anteiligen Pumpenleistungen) 25 5 20 35 15 10 5 0 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 Cold water inlet temperature [°C] Soleeintrittstemperatur in [°C] 18 ANNEX: 12.3 PERFORMANCE CHARACTERISTICS/PRESSURE LOSSES 12.3.5 Characteristics ..90C / 1 condenser Wasseraustrittstemperatur in [°C] Water outlet temperature [°C] Heating capacity [kW] Heizleistung in [kW] 100 90 35 50 80 70 60 50 40 30 Bedingungen: Conditions: Heating water flow 8000 Heizwasserdurchsatz 6,0 l/h m³/h Cold water flow 20000 Soledurchsatz 16,0 m³/hl/h 20 10 0 Leistungszahl Heizbetrieb (incl. der anteiligen Pumpenleistungen) Performance im figure in heating operation (incl. pump power consumptions) 8 7 35 6 5 50 4 3 2 1 0 Power consumptionin[kW] power consumptions) Leistungsaufnahme [kW](incl. (incl.pump der anteiligen Pumpenleistungen) 12 10 8 5 6 35 4 2 0 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 Kaltwassereintrittstemperatur [°C] Cold water inlet temperature in [°C] 19 ANNEX: 12.3 PERFORMANCE CHARACTERISTICS/PRESSURE LOSSES 12.3.6 Pressure losses ..90C Pressure loss in [Pa] Druckverlust [Pa] 35000 Druckverluste Pressure losses in Verdampfer the evaporator Sole/Wasser bei 10°C Water/water 90C at70C 10°C 30000 Pressure loss 0,190 at bei Druckverlust 12,5bar kPa nominal cold water flow 20000 l/h 25000 Sole-Nenndurchfluß 16,0 m³/h 20000 15000 10000 5000 0 0 2 4 6 8 10 12 14 16 18 Kaltwasserdurchfluß in [m³/h] Cold water flow 1000l/h 20 22 24 26 Pressure loss in [Pa] Druckverlust [Pa] 20000 Druckverluste Verflüssiger Pressure losses in the liquefier Water/water 90C 70C at 35°C Sole/Wasser bei 10°C Pressure loss 0,13 bar at nominal Druckverlust 6 kPa bei heating water flow 8000 l/h 15000 Heizwasser-Nenndurchfluß 6,0 m³/h 10000 5000 0 0 1 2 3 4 5 6 Heating water flow [l/h] Heizwasserdurchfluß in [m³/h] 20 7 8 9 10 21 PE N L X1 X1 X1 1 F1 1 2 1 3 X8 1 4 3 6 1 4 7 3 6 9 H2 X13-1 X13 A2 K2 A1 X11 X1-N11 X1-11 X11-2 7 11 3 15 1 X2-23 16 2 10 14 6 X11-8 X12-14 A2 K17 A1 X4 / X12 X2 X1 F10 F> X2-24 X12-9 1 3 5 13 K2 X2-11 X2-10 2 /3.6 4 /3.6 6 /3.6 14 /-.5 E11 X12-15 E10 X11-9 X11-7 X2-N 22 K14 X1-24 A6 X1-23 21 K5 31 16 18 K17 X2-N 22 K14 15 /-.5 32 31 32 P< B X13-3 H3 X13-2 X8-3 X12-5 X2-19 F3 X2-17 X11-6 X8-1 X11-4 X12-13 K5 21 1 Q1 13 4 X12-10 X12-1 X2-14 4 X1-22 2 X2-16 A5 X1-20 EGS X12-12 F6 T X2-15 X12-6 X11-3 X1-21 MSZ X11-1 3 A X2 C 14 X1 < 2 X2-18 X12-4 X8-2 21 31 43 1 3 5 13 24 21 K5 22 /-.3 32 /-.4 44 /-.6 2 /3.4 4 /3.5 6 /3.5 14 A2 K5 A1 K15 24 21 14 13 21 31 43 1 3 5 13 A2 K14 A1 K16 K2 X1-19 14 11 B X2-21 P> 16 X2-20 K17 22 /-.3 32 /-.4 44 /-.6 2 /3.4 4 /3.5 6 /3.5 14 X1-N12 X1-12 X8-6 X12-11 K14 X8-4 X1-18 X1-17 K16 X12-2 A4 F2 K15 5 C A 11 X2-22 18 15 14 K5 K14 X12-3 44 43 X1-14 X1-13 X1-16 12 14 22 24 32 34 42 44 41 31 21 /-.4 11 /-.5 A2 A1 K15 K15 X8-5 44 43 X1-15 6 12 14 22 24 32 34 42 44 K16 A2 K16 A1 41 31 21 /-.5 11 /-.5 9 8 3 o.F. o.F. o.F. o.F. o.F. = ohne Funktion bei WPR-Betrieb Heat pump control Wärmepumpenregler 11 12 3 10 14 13 9 8 2 4 8 o.F.= no funktion to heat pump control L 11 L 12 MSZ 16 EGS N 10 Verd.2 14 Verd.1 13 HD Anford. 2 4 X4 1 1 Cod. 5 6 6 ND 5 7 7 EGS 0V 15 7 BOSUP 15 ANNEX: 12.4 CIRCUIT DIAGRAMS 12.4.1 Control ..40C 3/PE 400V Mains Netz 50Hz 3 X1 PE L3 L2 L1 22 X1 PE 2 4 4 S V 2 R U 3 Bl.4 / X2-1;2;3;PE 1 3 4 2 1 3 1 W N7 PE 4 X1 5 4 V S 4 3 4 3 6 Bl.4 / X2-4;5;6;PE U R T 1 2 1 2 K5 F8 6 5 6 5 Basic control unit - Load Basissteuerung - Last W T 6 5 6 5 N8 K14 F9 X1 PE 3 7 3 8 M 2 4 4 K2 22 14 / 1.4 / 2.4 21 13 Q 1 /3,2-5A ( optional ) Brine circulating pump Soleumwälzpumpe 9 5 6 I> I> I> 1 ANNEX: 12.4 CIRCUIT DIAGRAMS 12.4.2 Control of load ..40C 23 Verdichter1 Condenser 1 M 3 M1 PE 3 X2 2 PE M 3 5 6 Verdichter2 Condenser 2 4 4 Bl. 3 / X1-4,5,6,PE X2 1 4 Bl. 3 / X1-1,2,3,PE M2 Terminal box Anschlusskasten Lastleitungen zur Basissteuerung Cables to basic control unit are sind bauseits zu erstellen by customers to prepare X2 PE 13 N 14 E11 11 PE 15 Ölsumpf-Heizungen Crank pit heater for condenser E10 10 X12 Heat pump Wärmepumpe N F6 Thermostat Frostschutz for freeze protection T< 2 4 A C F3 P< B 17 18 19 1 5 R PE 11 A B F2 P> C 20 21 22 2 3 X4 PE Pressostat for Pressostat for low HD-Wächter ND-Begrenzer pressure limiter with hight pressure manual reset 4 1 10 15 16 PE 6 14 12 Zubehör: Accessories: Control cable Steuerleitung 15 Bl. 1u.2 / X8+X11 ANNEX: 12.4 CIRCUIT DIAGRAMS 12.4.3 Heat pump ..40C L 3 Mains load Netz-Last 3/PE 400V 50Hz 4 L 2 24 X2 PE 1 2 3 PE 4 5 6 M3 M 3 N N PE PE 12 12 11 A4 A5 A6 PE PE 13 14 15 16 17 18 19 20 21 22 23 24 Betrieb mit Wärmepumpenregler Operation with heat pump control Anschlusskasten Wärmepumpe Heat pump terminal box Solepumpe Brine pump Wärmepumpe M2 M1 Verdichter Verdichter Condenser Condenser AnschlusskastenHeat pump terminal box X1 PE L N PE 1 2 3 PE 4 5 6 PE 7 8 9 11 X12 X8 X11 X4 N3 H2 Anschlusskasten H3 X13 Wärmepumpe Heat pump terminal box Wärmepumpenregler Heat pump controler Steuerleitung Control cable L 1 Control cable Steuerleitung PE ANNEX: 12.4 CIRCUIT DIAGRAMS 12.4.4 Terminal assignment incl. heat pump control ..40C ANNEX: 12.4 CIRCUIT DIAGRAMS 12.4.5 Legend ..40C A4 A5 A6 Wire jumper for use of heat pump control Wire jumper for use of heat pump control Wire jumper for use of heat pump control E10 E11 Crank pit heater for condenser 1 Crank pit heater for condenser 2 F1 F2 F3 F6 F8 F9 F10 Control fuse Pressostat for high pressure Pressostat for low pressure limiter with manual reset Thermostat for freeze protection Automatic circuit breaker for condenser 1 Automatic circuit breaker for condenser 2 Flow switch H3 Pilot lamp for low pressure fault K2 K5 K14 K15 K16 K17 K11 Contactor for well pump Contactor for condenser 1 Contactor for condenser 2 Relay condenser 1 Relay condenser 2 Time relay - flow switch EVU blocking contactor** M1 M2 M3 M5 M6 Condenser 1 Condenser 2 Well pump* Buffer charging pump** Hot water circulating pump** N3 N7 Heat pump control* Soft start control Q1 Power breaker for brine circulating pump X1 X2 X4 X8 X11 X12 X13 Terminal strip for mains supply Terminal strip for heat pump (terminal box) Control cable connector (N3) Heat pump connector (basic control unit) Heat pump connector (basic control unit) Heat pump connector (terminal box) Pilot lights connector * ** Optionally usable devices or controls Components are to be provided on site 25 26 1 3 5 13 2 /2.4 4 /2.4 6 /2.5 14 /-.5 1 3 5 13 A2 A2 K2 K3 A1 44 43 14 K2 A1 A1 K14 K5 13 K3 2 /2.7 4 /2.8 6 /2.8 14 X12-13 X11-7 X2-N F5 L L N N X11-8 X11-9 K5 X8 1 4 3 6 3 6 9 X2-N E11 X2-11 X12-15 32 31 X11 X2-N E10 X2-10 K14 X11-4 2 X2-16 1 1 4 7 X12-14 X2-30 X2-31 F11 X2-14 4 X12-12 F6 T X2-15 X12-6 X11-3 22 7 21 3 11 15 1 16 2 X4 / X12 10 6 14 21 1 3 5 13 B X2-17 K5 X2-32 C 2 /2.3 4 /2.3 6 /2.3 14/-2 X2-18 K15 21 22 /-.3 1 3 5 13 A2 K5 A1 K5.1 15 K15.1 31 1 3 5 43 A2 K5.1 A1 16 2 /2.3 4 /2.3 6 /2.3 14 18 14 16 14 21 14 13 K14 32 /-.3 2 /2.6 4 /2.7 6 /2.7 44 A2 1 3 5 13 11 Q4 21 /-.5 A2 15 /-.5 K15.1 K15 16 18 12 14 F13 1 X8-5 14 K15.1 A1 X12-3 A2 K15 A1 14 2 /2.6 4 /2.6 6 /2.6 14 K14.1 A2 Q3 X2-22 11 K16.1 C A K14 A1 K14.1 A1 18 15 K16 K2 X8-6 X12-11 B A X12-2 X8-4 X2-20 P> F2 Q2 14 X2-21 11 X2-33 P< F3 X12-4 X8-2 Q1 14 F11 X2-34 F5 X2-35 X12-1 X8-1 11 21 /-.5 A2 9 5 1 6 o.F. o.F. o.F. o.F. o.F. o.F. = ohne Funktion bei WPR-Betrieb o.F.= no funktion to heat pump control HeatWärmepumpenregler pump control 12 L 12 14 13 3 2 11 9 8 4 5 10 X4 6 1 N 10 Verd.2 14 Verd.1 13 HD 0V Cod. 1 ND 7 15 /-.5 K16.1 K16 16 18 12 14 A2 K16 A1 K16.1 A1 F12 2 2 15 EGS 7 BOSUP 15 ANNEX: 12.4 CIRCUIT DIAGRAMS 12.4.6 Control ..90C 27 3 L1 L2 L3 PE Mains Netz 3/PE 400V X1 50Hz X1 PE /1.5 U 2 F12 4 V 4 S 2 R 3 3 W T 6 5 N7 Bl.4 / X2-1;2;3;PE 1 2 -/1.7 1 K5.1 1 3 2 1 4 3 5 6 5 I> I> I> 1 /1.5 K5 14 PE 7 1 3 5 Q1 12 / 1.5 /1.6 K14.1 1 4 3 6 5 X1 8 M 3 2 4 4 14 /1.2 K2 M3* 9 6 I> I> I> 11 X1 PE U 5 F13 V 4 S W 6 T Bl.4 / X2-4;5;6;PE 4 2 -/1.7 1 2 R N8 2 1 4 3 I> I> I> 6 5 /1.5 X1 PE 12 / 1.6 K14 14 11 5 11 3 Q4 1 Q3 12 / 1.6 Basissteuerung Last Basic control unit - -Load 3 4 M 3 4 71 81 91 2 5 /1.2 K3 14 11 Q2 M4* 6 I> I> I> 1 12 / 1.5 ANNEX: 12.4 CIRCUIT DIAGRAMS 12.4.7 control of load ..90C 28 M1 Verdichter1 1 Condenser M 3 PE 3 PE 2 X2 M 3 5 6 M2 N 11 PE 15 for condenser PE X12 14 N Heat pump Wärmepumpe E10 E11 Crank pit heater Ölsumpf-Heizungen 10 X2 Terminal box Anschlusskasten Verdichter2 2 Condenser 4 4 Bl. 3 / X1-4,5,6,PE X2 1 4 Bl. 3 / X1-1,2,3,PE Cables to basic control unit are Lastleitungen zur Basissteuerung bauseits zu to erstellen bysind customers prepare for freeze protection F6 Thermostat Frostschutz T< P< B 5 R PE F3 Pressostat for low ND-Begrenzer Rückstellung pressure limitervonwith manualHand reset C A 2 4 1 4 17 18 19 10 15 16 PE 12 14 6 Accessories: Zubehör: Control cable Steuerleitung 15 Bl. 1u.2 / X8+X11 11 3 B P> C F2 Pressostat HD-Wächter for Rückstellung hight pressure selbsttätig A 20 21 22 PE 2 31 N L N 32 M2 F5 33 M1 34 M2 F11 35 M1 F11 Electronic winding protection Elektronischer Wicklungsschutz Verdichter 1 Verdichter 2Verdichter 1 Verdichter 2 F5 N L N 1 Condenser 1 Condenser 2 Condenser 1 Condenser 2 30 13 X4 ANNEX: 12.4 CIRCUIT DIAGRAMS 12.4.8 Heat pump ..90C 3/PE 400V Mains load Netz-Last 4 29 5 6 PE 7 M 3 8 M 3 9 PE 71 81 91 Betrieb mitwith Wärmepumpenregler Operation heat pump control Wärmepumpe Heat pump terminal box Anschlusskasten M3 M4 Solepumpen Brine pump For pump Beibrine Betrieb mitoperation einer Solepumpe, always to 7;8;9;PE immer connect an 7;8;9;PE anschliessen X2 PE 1 2 3 PE 4 5 6 50Hz 3 PE 4 Wärmepumpe M1 M2 Verdichter Condenser Verdichter Condenser 2 HeatAnschlusskastenpump terminal box PE 1 X12 X8 X11 N3 Wärmepumpe Heat pump terminal box Anschlusskasten Wärmepumpenregler Heat pump controler Steuerleitung Control cable X4 Steuerleitung Control cable L L L X1 PE 1 2 3 ANNEX: 12.4 CIRCUIT DIAGRAMS 12.4.9 Terminal assignment incl. heat pump control ..90C ANNEX: 12.4 CIRCUIT DIAGRAMS 12.4.10 Legend ..90C E10 E11 Crank pit heater for condenser 1 Crank pit heater for condenser 2 F2 F3 F5 F6 F10 F11 F12 F13 Pressostat for high pressure detector Pressostat for low pressure limiter Electronic winding protection for condenser 1 Thermostat for freeze protection Flow switch Electronic winding protection for condenser 2 Temperature detector / N7 Temperature detector / N8 K2 K5 K5.1 K14 K14.1 K15 K15.1 K16 K16.1 Contactor for well pump (M3) Contactor for condenser 1 Starter contactor for condenser 1 Contactor for condenser 2 Starter contactor for condenser 2 Relay for condenser 1 Time-delay relay K5 Relay for condenser 2 Time-delay relay K14 M1 M2 M3 Condenser 1 Condenser 2 Well pump * N3 N7 N8 Heat pump control* Soft start PC board for condenser 1 Soft start PC board for condenser 2 Q1 Q2 Q3 Power breaker for well pump (M3) Power breaker for condenser 1 Power breaker for condenser 2 X1 X2 X4 X8 X11 X12 Terminal strip for basic control unit Terminal strip for heat pump (terminal box) Control cable connector (N3) Heat pump connector (basic control unit ) Heat pump connector (basic control unit ) Heat pump connector (terminal box) * ** Optionally usable components, devices or controls Components are to be provided on site 30 Hot water supply Hot water control / sensor Return line sensor External wall probe Brine pump Return flow collector Ground absorber Heat pump Heat pump control Electric distribution pane 25 26 33 34 42 44 45 WP WPR EV Thermostat valve 19 Cold water supply Overflow valve 18 24 Non- return valve 17 Safety valve Structure- borne noise insulation 16 23 Flexible connection hoses 15 Shutoff valve for manual operation Expansion vessel 12 Shutoff valve for manual operation and drain Hot water circulating pump 5 21 Heating circulating pump 2 20 Heat consumer 1 23 20 17 20 31 N06 (WUP) 5 24 20 17 20 25 T 26 N05 (HUP) 2 Hot water storage 20 WWF B3 18 19 16 23 Warmwasserspeicher 12 20 15 1 15 21 (RLR) B2 WP 15 20 T 33 BufferPufferspeicher storage 15 21 20 WPR 23 12 EV 20 20 42 T 44 43 34 20 20 45 ANNEX: 12.5 HYDRAULIC SCHEMATIC DIAGRAM Hydraulic schematic diagram (Example) ANNEX: 12.6 CE CONFORMITY STATEMENT CE CONFORMITY CERTIFICATE CE The undersigned EC Conformity Certificate KKW Kulmbacher Klimageräte-Werk GmbH Dimplex Divisiom Am Goldenen Feld 18, 95326 Kulmbach, Germany confirms that the unit(s) listed below comply with the requirements stipulated in the EC guidelines owing to their design and type and to the versions put on the market. Any modifications of the unit(s) that are performed without our consent renders this certificate ineffective. Name of the unit(s) EC Guidelines Brine/water heat pumps for indoor installation with R407C Water/water heat pumps for indoor installation with R407C EC guideline on low voltage (73/23/EEC) EC Guideline on EMC (89/336/EEC) Printing equipment guideline (97/23/EEC Type: Harmonized EN SI 30CG EN255:1997 SI 70CG EN 378:1994 DIN EN 603335-1 (VDE 0700, part I):1995-10 EN 60335-1:1994 +A11:1995 WI 40CG DIN EN60335-1/A1 (VDE 0700, part 1/A1):1997-08 EN 60335 1/A1:1996 WI 90CG DIN EN 60335-1/A12 (VDE 0700, part 1/A12):1997-08 DIN EN 60335-1/A13 (VDE 0700, part 1/A13):1998-12 DIN EN 60335-1/A14 (VDE 0700, part 1/A14):1999-05 DIN EN 60335-2-40 (VDE 0700, part 40):1998-07 DIN EN 55014-2 (VDE 0875, part 14-2):1997-10 Requirements of category II DIN EN 55014-1 (VDE 0875, part 14-1):1999-10 1:1993+A1:1997+A2:1999 DIN EN 61000-3-2 (VDE 0838, part 2):1998-10 EN60335-1/A12:1996 EN60335-1/A13:1998 EN60335-1/A14:1998 EN60335-2-40:1997 EN 55014-2:1997 EN 55014EN 61000-3-2:1995+ Corrigendum:1997+A1:1998+A2:1998 DIN EN 61000-3-2/A14 (VDE 0838, part 2/A14):2001-01 EN 61000-3-2:1995/A14:2000 DIN EN 61000-3-3 (VDE 0838, part 3):1996-03 EN 61000-3-3:1995 Order number: 337 337 337 337 800 810 820 830 Kulmbach, May 07, 2002 National standards/guidelines D VBG20 Wolfgang Weinhold Managing Director 32 A CH SVT1 Mathias Huprich Technical Manager ANNEX: 12.7 WARRANTY CERTIFICATE/CUSTOMER SERVICE Warranty certificate (valid in Germany) The following conditions, which describe the terms and conditions of our warranty, do not affect the obligations of the vendor to honor the warranty as specified in the sales contract with the end user. For the units, we offer warranty in accordance with the conditions below: An extension of the warranty to 36 months for heating heat pumps and central ventilating systems, however a maximum of 38 months from the date of delivery from the factory, will be granted in accordance with the following conditions: prerequisite for the granting of the extended warranty is the commissioning, subject to cost, by the authorized system engineering customer service, with the commissioning certificate, within a time of operation (compressor running time) of less than 150 hours. Defects reported in the commissioning certificate must be eliminated without delay. This constitutes the basis for the warranty. The commissioning certificate must be sent to the address below, from which the warranty period extension is also confirmed, within one month of successfully commissioning the unit. We remedy defects to the unit which are demonstrated to be the result of material or manufacturing faults when we are notified of these immediately following the discovery of such defects and within 24 months following delivery to the end user free of charge, subject to the following proviso. In the event that the defect becomes apparent within 6 months following delivery and commissioning (heating heat pump and central apartment ventilating systems) has been successfully performed by the authorized system engineering customer service, it can be assumed that the cause is a material or manufacturing fault. The charge for commissioning includes the commissioning itself and the costs of travel. No liability can be assumed for proper planning, dimensioning and the performnce of work on the overall system. The elimination of defects in the overall system and the service times required are special services. The warranty conditions apply to this unit only when it is purchased by a contractor in one of the member countries of the European Union, is operated in Germany during the time at which the defect occurs, and warranty services can be performed in Germany. The commissioning charge, which is currently 320 net for heating heat pumps and 450 net for ventilating systems, both per unit, is invoiced to the contractor by the system engineering customer service. We reserve the right to make adjustments to these prices. The elimination of the defects which we recognize as legitimate claims against warranty encompasses, subject to our choice, the repair or replacement by flawless parts of the defective parts. We cannot assume extraordinary repair costs arising from the type or location or poor accessibility of the unit. Removed parts which we take back become our property. The warranty period for the rectification of defects and replacement parts ends with the elapsing of the original warranty period for the unit. The warranty does not extend to fragile parts which only impair the value or the usefulness of the unit insignificantly. The original proof of purchase must always be presented. In the event that customer service is required, the authorized system engineering customer service responsible for the customer site must be informed and will provide fast help to deal with the problem. The authorized system engineering customer service responsible for your region can be determined by contacting the service hotline for the Dimplex Division of the KKW Kulmbacher Klimageräte-Werk GmbH. KKW Kulmbacher Klimageräte-Werk GmbH Dimplex Division System Engineering Customer Service Am Goldenen Feld 18 95326 Kulmbach Germany The warranty conditions cannot be honored if the end user or a third party fail to comply with the corresponding VDE provisions, the provisions of the local power supply companies, or our installation and operating instructions, as well as the notes or interconnection diagrams in the configuration documentation, or if the accessories required from us to implement a function are not used. In the event of unauthorized modifications or work performed by the end user or a third party, the manufacturer is no longer liable for the resulting consequences. The warranty extends to the unit and the parts provided by the supplier. Parts not delivered by the supplier and unit/system defects attributable to the use of parts not provided by the supplier do not fall under warranty claims. Telephone: Fax: e-mail: Internet: +49 (0) 9221 709 562 +49 (0) 9221 709 565 [email protected] [email protected] w w w.kkw.de www.dimplex.de The product number (E.Nr.) and the date of production (FD) of the unit are required in order to process the order. This information is given on the nameplate in the field marked with the heavy border. In so far as we are not able to eliminate the defect, or we reject the rectification thereof or unreasonably delay the implementation thereof, the manufacturer will deliver a replacement unit free of charge or remunerate the reduced value. In the case of a replacement delivery, we reserve the right to make appropriate allowance for the use of the unit up to this time. Additional or more extensive claims, in particular such claims resulting the replacement of damage to objects other than the unit are, provided that liability has not been compulsorily ordered by law, excluded. .Customer service address 33 Notes 34 Notes 35 KKW Kulmbacher Klimageräte-Werk GmbH Dimplex Division Am Goldenen Feld 18 D-95326 Kulmbach, Germany Technical modifications reserved Telefax (0 92 21) 709-589 www.dimplex.de 36