Download Dimplex WI 27CS Operating instructions

Transcript
CE
MOUNTING and
OPERATING MANUAL
Water-to-Water Heat Pump
for Indoor Installation
WI
WI
WI
WI
Order No.: 452230.67.03
9CS
14CS
22CS
27CS
FD 8404
1
CONTENTS
1
READ IMMEDIATELY
1.1
1.2
1.3
Important Information
Legal Provisions and Directives
Energy-Efficient Use of the Heat Pump
2
PURPOSE OF THE HEAT
PUMP
3
4
2.1
2.2
Application
Principle of Operation
3
BASELINE UNIT
4
4
TRANSPORT
5
5
INSTALLATION
5
5.1
5.2
General Information
Sound Emissions
6
MOUNTING
6.1
6.2
6.3
6.4
General
Heating-Side Connection
Heat Source-Side Connection
Electrical Connection
7
COMMISSIONING
7.1
7.2
7.3
General
Preparation
Procedure
8
CARE/CLEANING
8.1
8.2
8.3
8.4
Care
Cleaning of Heating Side
Cleaning of Heat Source Side
Water Quality Requirements
9
MALFUNCTIONS/TROUBLESHOOTING
8
10 DECOMMISSIONING
6
7
7/8
8
10.1 Shutdown in Summer
10.2 End-of-Life Decommissioning
11 APPENDIX
9
2
READ IMMEDIATELY
1
READ IMMEDIATELY
1.1 Important Information
CAUTION!
The well water must meet the required
water quality standards.
CAUTION!
The heat pump is not attached to the
wooden pallet.
CAUTION!
The heat pump must not be tilted
more than max. 45 ° (in either direction).
CAUTION!
Do not lift unit by the holes in the panel
assemblies!
CAUTION!
Flush the heating system prior to
connecting the heat pump.
CAUTION!
When connecting the load lines be
sure to observe the clockwise phase sequence.
1.2 Legal Provisions and Directives
This heat pump is in compliance with all relevant
DIN/VDE regulations and EU directives. These
are described in more detail in the EC Declaration
of Conformity.
The electrical connection of the heat pump must
be performed according to and conforming with
all relevant VDE, EN and IEC standards. Beyond
that, all connection requirements of the local
electrical utility company have to be observed.
The heat pump is to be plumbed into the heat
source and heating systems in accordance with
all relevant regulations.
1.3 Energy-Efficient Use of the Heat
Pump
By operating this heat pump, you contribute to the
protection of the environment. An important
prerequisite for energy-efficient operation is the
careful sizing of the heating system and the heat
source. In particular, it is important to keep water
flow temperatures as low as possible. All energy
consumers connected should therefore be suitable
for low flow temperatures. A 1 K higher heating water
temperature corresponds to an increase in power
consumption of approx. 2.5 %. Underfloor heating
systems with flow temperatures between 30 °C and
40 °C are optimally suited for energy-efficient
operation.
CAUTION!
Commissioning of the heat pump
must be performed in accordance with the
operating instructions of the heat pump
controller.
CAUTION!
Any work on the heat pump may be
performed by an authorised and competent
customer service only.
CAUTION!
Before opening the unit, all electrical
circuits must be disconnected from the power
supply.
3
PURPOSE OF HEAT PUMP
BASELINE UNIT
2
PURPOSE OF THE HEAT
PUMP
3
BASELINE UNIT
The water-to-water heat pump is designed for
use in existing or newly built heating systems.
Water, which can be supplied from wells, or the
like, is used as the heat carrier.
The baseline unit consists of a heat pump, ready
for connection, for indoor installation, complete with
housing, control panel and integrated controller.
The refrigeration cycle contains the refrigerant
R407C. The refrigerant is CFC-free, non-ozone
depleting and non-combustible.
To prevent any corrosion damage to the evaporator, the well water must be evaluated in
accordance with DIN 50930 as to the corrosion
risk of metallic materials.
All components required for the operation of the
heat pump are integrated in the control panel.
The power feed for the load and control current
must be field-installed by the customer.
More details are contained in the Project Planning
and Installation Manual for heat pumps for
heating purposes.
The supply lead of the well pump (to be provided
by the customer) must be connected to the control
panel. When so doing, check whether the capacity
of the factory-installed motor protecting device is
adequate for the field-installed pump.
2.1 Application
CAUTION!
The well water must meet the established water quality standards.
1
2
2.2 Principle of Operation
A well pump conveys the water into the evaporator
of the heat pump where it gives off heat to the
refrigerant in the refrigeration cycle.
The refrigerant is then "sucked in" by the
electrically driven compressor, is compressed
and "pumped" to a higher temperature level. The
electrical power needed to run the compressor
is not lost, but most of the generated heat is
transferred to the refrigerant as well.
Subsequently, the refrigerant is passed through
the condenser where it transfers its heat energy
to the heating water.
3
Based on the thermostat setting, the heating
water is thus heated to up to 55 °C.
4
1) Evaporator
2) Control panel
4
3)
4)
Condenser
Compressor
TRANSPORT
MOUNTING
4
TRANSPORT
A lift truck is suited for transporting the unit on a level
surface. If the heat pump needs to be transported
on an uneven surface or carried up or down stairs,
carrying straps may be used for this type of transport.
These straps may be passed directly underneath
the wooden pallet.
CAUTION!
The heat pump is not secured to the
wooden pallet.
5
INSTALLATION
5.1 General Information
As a rule, the unit must be installed indoors on a
level, smooth and horizontal surface. The entire base
frame should thereby make close contact with the
surface in order to ensure adequate sound
insulation. Failing this, additional sound insulation
measures may become necessary.
The heat pump should be located to allow safe and
easy maintenance/service access. This is ensured
if a clearance of approx. 1 m in front of and to each
side of the heat pump is maintained.
1m
1m
1m
CAUTION!
The heat pump must not be tilted
more than max. 45° (in either direction).
For lifting the unit without pallet, the holes provided
in the sides of the frame should be used. The side
panel assemblies must be removed for this
purpose. Any ordinary pipe can be used as a carrying
aid.
CAUTION!
Do not lift unit using the holes provided
in the panel assemblies!
5.2 Sound Emissions
The heat pump offers silent operation due to efficient
sound insulation. To prevent noise transmission to
the foundation, a suitable, sound dampening rubber
mat should be placed underneath the base frame
of the heat pump.
The transmission of noise to the heating system
is prevented by pressure hoses already integrated
into the heat pump.
5
MOUNTING
6
MOUNTING
6.1 General
The following connections need to be established
on the heat pump:
- supply/return flow of well system
- supply/return flow of heating system
- power supply
CAUTION!
The well water must meet the required
water quality standard.
6.4 Electrical Connection
The following electrical connections must be
established on the heat pump.
-
Connection of the control wire to the control panel
of the heat pump via terminal X1: L/N/PE.
-
Connection of the load wire to the control panel
of the heat pump via terminal X5: L1/L2/L3/PE.
-
Connection of the well pump load wire to the
control panel of the heat pump via terminal
X5: L11/L21/L31/PE.
-
Connection of the well pump (to be provided
by the customer) to the control panel of the
heat pump via terminal X1: PE and pump
contactor K2: 2/4/6.
6.2 Heating-Side Connection
CAUTION!
The heating system must be flushed
prior to connecting the heat pump.
Before completing the heat pump connections on
the heating water side, the heating installation must
be flushed in order to remove any impurities that
may be present, as well as residues of sealing
material, and the like. Any accumulation of deposits
in the condenser may result in a total failure of the
heat pump.
Once the installation on the heating side has been
completed, the heating system must be filled, deaerated and pressure-tested.
Heating water minimum flow rate
The heating water minimum flow rate through the
heat pump must be assured in all operating states
of the heating system. This can be accomplished,
for example, by installing a differential pressure-free
manifold or an overflow valve. The procedure for
setting an overflow valve is described in the Chapter
Commissioning.
Frost protection for installations prone to frost
Provided the controllers and circulating pumps are
ready for operation, the frost protection feature of the
controller is active. If the heat pump is taken out of
service or in the event of a power failure, the system
has to be drained. In heat pump installations where
a power failure cannot be readily detected (holiday
house), the heating circuit must contain a suitable
antifreeze product.
6.3 Heat Source-Side Connection
The following procedure must be observed when
making the connection:
When connecting the load wire of the well pump it
must be ensured that the power supply for these
terminals cannot be disconnected by the tariff
contactor in order to ensure the cutout delay of
the well pump.
All electrical components required for the
operation of the heat pump are located on the
control panel.
For detailed instructions concerning the connection
and functioning of the heat pump controller refer to
the operating manual supplied with the controller..
An all-pole disconnecting-device with a contactgap of at least 3 mm (e.g. utility company disable
contactor or power contactor) as well as a 3-pole
circuit breaker with simultaneous tripping of all
external conductors. The required cross-sectional
area of the conductor is to be selected according
to the power consumption of the heat pump, the
technical connection requirements of the relevant
electrical utility company as well as all applicable
provisions. Details on the power consumption of
the heat pump are contained on the product
information sheet and the rating plate. The terminals
are designed for a conductor cross-section of
max. 10 mm˝.
CAUTION!
When connecting the load line, make
sure that the phase sequence is correct (if the
phase sequence is not correct the heat pump will
not perform properly and generate abnormal
noise).
Connect the well lines to the flow and return pipes
of the heat pump.
6
COMMISSIONING
CARE/CLEANING
7
COMMISSIONING
Any malfunctions occurring during operation are
displayed on the heat pump controller and can be
corrected as described in the operating manual of
the heat pump controller.
7.1 General
To ensure proper commissioning it should be
carried out by an after-sales service authorized by
the manufacturer. Only then can an extended
warranty period of 3 years in total be granted (cf.
Warranty service).
7.2 Preparation
Prior to commissioning, the following items need to
be checked:
- All connections of the heat pump must have been
made as described in Chapter 6.
- The heat source system and the heating circuit
must have been filled and tested.
- In the well and heating circuits all valves that
could impair the proper heating water flow
must be open.
- The settings of the heat pump controller must be
adapted to the heating installation in accordance
with the instructions contained in the controller's
operating manual.
7.3 Procedure
The start-up of the heat pump is effected via the
heat pump controller.
CAUTION!
Commissioning of the heat pump
must be performed in accordance with the
mounting and operating manual of the heat
pump controller.
Where an overflow valve is fitted to assure the
minimum heating water flow rate, the valve must be
set in accordance with the requirements of the heating
installation. An incorrect setting may result in various
error symptoms and an increased electric power
consumption. To correctly set the overflow valve, the
following procedure is re-commended:
a) Open all heating circuits and close the overflow
valve. Determine the resulting temperature
difference between supply and return flow.
b) Close all of the heating circuits that may also be
closed during operation (depending on the type
of heat pump usage) so that the most unfavourable operating state - with respect to the water
flow rate - is achieved.
8
CARE/CLEANING
8.1 Care
The heat pump is maintenance-free. To prevent
malfunctions due to sediments in the heat exchangers, care must be taken that no impurities can
enter the heat source system and heating installation. In the event that operating malfunctions due to
contamination occur nevertheless, the system
should be cleaned as described below.
8.2 Cleaning of Heating Side
The ingress of oxygen into the heating water circuit
may result in the formation of oxidation products (rust).
It is therefore important - in particular with respect to
the piping of underfloor heating systems - that the
installation is executed in a diffusion-proof manner.
Also residues of lubricating and sealing agents may
contaminate the heating water.
In the case of severe contamination leading to a
reduction of the performance of the condenser in the
heat pump, the system must be cleaned by a heating
technician.
According to current knowledge, we recommend
cleaning with a 5% phosphoric acid solution or, in
the case that cleaning needs to be performed more
frequently, with a 5% formic acid solution.
In either case, the cleaning fluid should be at room
temperature. It is recommended that the heat
exchanger be cleaned in the direction opposite to the
normal flow direction.
To prevent acidic cleaning agents from entering the
circuit of the heating installation we recommend that
the flushing device be fitted directly to the supply and
return lines of the condenser. To prevent any damage
caused by cleaning agent residues that may be
present in the system it is important that the system
be thoroughly flushed using appropriate neutralising
agents.
The acids must be used with great care, all relevant
regulations of the employers' liability insurance
associations must be adhered to.
If in doubt, contact the manufacturer of the chemicals!
7
CARE/CLEANING
MALFUNCTIONS/TROUBLESHOOTING
DECOMMISSIONING
CAUTION!
Caution - Heating Technicians !
Depending on the filling water quality and
quantity, in particular in the case of mixed
installations and plastic pipes, mineral deposits
(rust sludge, lime) may form, impairing the
proper functioning of the heating installation.
A reason for this is the water hardness and
oxygen dissolved in the filling water as well as
additional oxygen from the air, which may
penetrate via valves, fittings and plastic pipes
(oxygen diffusion). As a preventive measure
it is recommended that a physical water
conditio-ner such as ELYSATOR be used.
8.3 Cleaning of Heat Source Side
A strainer is fitted in the heat source inlet of the
heat pump in order to protect the evaporator
against contamination. Initially, the filter screen
of the strainer should be cleaned at relatively short
intervals. Once there is less contamination, the
intervals can be extended accordingly.
9
MALFUNCTIONS/
TROUBLESHOOTING
This heat pump is a quality product and designed
for trouble-free operation. In the event that a
malfunction occurs nevertheless, you will be able
to correct the problem easily yourself in the
majority of cases. Simply consult the Malfunctions
and Troubleshooting table in the operating
manual of the controller.
Additional malfunctions can be interrogated at the
heat pump controller.
If the problem cannot be corrected by the user,
please contact the after-sales service in charge
(see Warranty Certificate).
CAUTION!
Any work on the heat pump may only
be performed by an authorized and qualified aftersales service.
CAUTION!
Prior to opening the unit, all of its
electric circuits must be disconnected from the
power source.
8.4 Water Quality Requirements
To prevent any so-called "ochredisation" (deposition of iron and manganese) of the heat pump
system from occurring, the ground water must be
free of all substances that could result in mineral
deposits, and the limit values for IRON (< 0.2 mg/
l) and MANGANESE (< 0,1 mg/l) must be complied
with.
The use of surface water or saline water bodies
is not permitted. Consult your local waterworks
for some general information about any possible
ground water usage. Water analyses are prepared
by laboratories specialising in water technology.
No water analysis with respect to any corrosion
of the evaporator is required if the average annual
ground water temperature is not in excess of
13 °C. In this case, only the limit values for iron
and manganese must be met ("ochredisation"
risk).
10
DECOMMISSIONING
10.1 Placing Out of Service in
Summer
Placing the heat pump out of service in summer can
be effected by switching the heat pump controller to
the "Summer" operating mode.
10.2 End-of-Life Decommissioning/
Disposal
Before removing the heat pump, disconnect the
machine from the power supply and close all
valves. Environment-relevant requirements regarding the recovery, recycling and disposal of
service fuels and components in accordance with
all relevant standards must be adhered to. In this
context, particular attention must be paid to the
proper disposal of refrigerants and refrigeration
oils.
8
APPENDIX
11
APPENDIX
11.1
Dimensioned Drawing
.. 9CS to .. 27CS
10
11.2
Equipment Data
11
11.3
11.3.1
11.3.2
11.3.3
11.3.4
11.3.5
11.3.6
11.3.7
11.3.8
Performance Curves / Pressure
Losses
Performance Curves .. 9CS
Pressure Losses .. 9CS
Performance Curves .. 14CS
Pressure Losses .. 14CS
Performance Curves .. 22CS
Pressure Losses .. 22CS
Performance Curves .. 27CS
Pressure Losses .. 27CS
12
13
14
15
16
17
18
19
11.4
11.4.1
11.4.2
11.4.3
11.4.4
11.4.5
11.4.6
11.4.7
11.4.8
Wiring Diagrams
Control .. 9CS to .. 22CS
Load .. 9CS to .. 22CS
Terminal Diagram .. 9CS to .. 22CS
Legend .. 9CS to .. 22CS
Control .. 27CS
Load .. 27CS
Terminal Diagram .. 27CS
Legend .. 27CS
20
21
22
23
24
25
26
27
11.5
Hydraulic Block Diagram
28
11.6
EC Declaration of Conformity
29
11.7
Warranty Certificate
30
9
Heating water supply
Heat pump outlet
Heating water return
Heat pump inlet
Heat source return
Heat pump inlet
Heat source supply
Heat pump outlet
Heat source-side connections:
.. 9/14CS 11/4“ internal/external thread
.. 22/27CS 11/2" internal/external thread
Heating-side connections:
.. 9/14CS 1" internal/external thread
.. 22/27CS 11/4“ internal/1" external thread
APPENDIX: 11.1 DIMENSIONED DRAWING
Dimensioned Drawing
10
APPENDIX: 11.2 EQUIPMENT DATA
Equipment Data
EQUIPMENT DATA for water-to-water heat pumps for heating
1
TYPE AND COMMERCIAL DESCRIPTION
2
MODEL
2.1
Enclosure type acc. to EN 60 529
IP 20
IP 20
IP 20
IP20
2.2
Installation site
indoor
indoor
indoor
indoor
3
PERFORMANCE DATA
3.1
..9CS
..14CS
..22CS
..27CS
Operating temperature limits:
Heating water supply
°C
max. 55
max. 55
max. 55
max. 55
Cold water (heat source)
°C
+7 to +25
+7 to +25
+7 to +25
+7 to +25
3.2
Heating water temperature spread at W10 / W35
K
9,5
8,8
9,6
9,4
3.3
Heating capacity / coeff.of perform.
at W7 / W55 1)
kW / ---
6,9 / 2,5
12,2 / 2,5
19,0 / 3,2
24,6 / 3,2
at W10 / W50 1)
kW / ---
7,7 / 3,2
13,4 / 3,6
20,8 / 3,8
26,4 / 3,8
at W10 / W35 1)
kW / ---
8,3 / 5,1
13,6 / 5,2
21,5 / 5,5
26,4 / 5,1
3.4
Sound power level
dB(A)
53
55
58
59
3.5
Heating water flow rate at internal pressure difference
m³/h / Pa
0,75 / 7000
1,3 / 7000
2,0 / 8000
2,4 / 12500
3.6
Cold water flow rate at internal pressure difference
m³/h / Pa
2,0 / 6200
3,3 / 19000
5,0 / 20000
7,0 / 16000
type / kg
R407C / 1,7
R407C / 1,6
R407C / 3,2
R407C / 4,5
1380 x 600 x 500 1380 x 600 x 500 1380 x 600 x 500 1380 x 600 x 500
(heat source)
3.7
Refrigerant; total charge weight
4
DIMENSIONS, CONNECTIONS AND WEIGHT
4.1
Equipment dimensions without connections 4)
H x W x L mm
4.2
Equipment connections for heating system
inch
G 1" int/ext
G 1" int/ext
G1¼'' int/G1''ext G 1¼'' i / G 1'' a
4.3
Equipment connections for heat source
inch
G 1¼" int/ext
G 1¼" int/ext
G 1½" int/ext
G 1½" int/ext
4.4
Weight of transport unit(s) incl. packaging
kg
147
151
173
221
5
ELECTRICAL CONNECTION
5.1
Nominal voltage; fusing
5.2
Nominal power consumption 1)
W10 W35
V/A
400 / 16
400 / 16
400 / 20
400 / 20
kW
1,62
2,64
3,93
5,15
29
5.3
Starting current with soft starter
A
30 (without SS)
26
27
5.4
Nominal current W10 W35 / cos ϕ
A / ---
2,9 / 0,8
4,8 / 0,8
7,0 / 0,8
6
COMPLIES WITH EUROPEAN SAFETY REGULATIONS
3)
3)
7
OTHER DESIGN CHARACTERISTICS
3)
9,4 / 0,8
3)
7.1
Water inside equipment protected against freezing2)2)
yes
yes
yes
yes
7.2
Performance settings
1
1
1
1
7.3
Controller internal / external
internal
internal
internal
internal
1)
These data characterize the size and performance capability of the system. For economic and
energetic reasons, the balance point and control need to be taken into consideration as well.
Abbreviations have the following meaning, e.g. W10 / W55: heat source temperature 10 °C
and heating water supply temperature 55 °C.
2)
The heating system circulating pump and the controller of the heat pump must be ready for operation at all times.
3)
See EC Declaration of Conformity
4)
Please keep in mind that more space is required for pipe connection, operation and maintenance.
Subject to technical modifications
Edition: 24.03.2004
11
APPENDIX: 11.3 PERFORMANCE CURVES/PRESSURE LOSSES
11.3.1 Performance Curves .. 9CS
Wasseraustrittstemperatur
in [°C]
[°C]
Water outlet temperature in
Heating
capacity
in [kW]
Heizleistung
in [kW]
14
Bedingungen:
Conditions:
Heizwasserdurchsatz
Heating water flow rate0,75
0.75 m³/h
m3/h
3
Cold water flow rate 2.0
mm³/h
/h
Kaltwasserdurchsatz
2,0
12
35
50
10
8
6
4
2
0
Leistungszahl
im Heizbetriebin(incl.
Der anteiligen
Coefficient
of performance
the heating
mode Pumpenleistungen)
(incl. proportional pump energy)
8
7
35
6
50
5
4
3
2
1
0
Power
consumptionin(incl.
pump energy)
Leistungsaufnahme
[kW]proportional
(incl. Der anteiligen
Pumpenleistungen)
5
4
3
50
2
35
1
0
5
7
9
11
13
15
17
19
Cold water inlet temperature in
Kaltwassereintrittstemperatur
in[°C]
[°C]
12
21
23
25
27
APPENDIX: 11.3 PERFORMANCE CURVES/PRESSURE LOSSES
11.3.2 Pressure Losses .. 9CS
Pressure
lossin
in[Pa]
[Pa]
Druckverlust
20000
18000
Druckverluste
Pressure Verdampfer
losses
evaporator
at 10°C
bei 10°C
16000
Pressure loss6,2
6.2kPa
kPabei
at
Druckverlust
cold
water nominal flow rate2,0
2.0 m³/h
m3/h
Kaltwasser-Nenndurchfluß
14000
12000
10000
8000
6000
4000
2000
0
0
0,5
1
1,5
2
2,5
3
Kaltwasserdurchfluß
in [m
[m³/h]
Cold water flow rate in
/h]
3
3,5
4
Druckverlust
Pressure
lossin
in[Pa]
[Pa]
30000
Druckverluste
Pressure Verflüssiger
losses
bei 35°C
condenser
at 35°C
25000
Pressure loss77kPa
kPabei
at
Druckverlust
heating
water nominal flow rate0,75
0.75m³/h
m3/h
Heizwasser-Nenndurchfluß
20000
15000
10000
5000
0
0
0,25
0,5
0,75
1
3
Heizwasserdurchfluß
Heating
water flow ratein
in[m³/h]
[m /h]
13
1,25
1,5
APPENDIX: 11.3 PERFORMANCE CURVES/PRESSURE LOSSES
11.3.3 Performance Curves .. 14CS
Wasseraustrittstemperatur
Water outlet temperature in [°C]
Heating
capacity
in [kW]
Heizleistung
in [kW]
24
22
20
18
50
16
35
14
12
10
8
Bedingungen:
Conditions:
3
Heizwasserdurchsatz
1,3mm³/h
Heating water flow rate 1.3
/h
3
Cold water flow rate 3.33,3
m /h
Kaltwasserdurchsatz
m³/h
6
4
2
0
Coefficient
of performance
in the
heating
mode (incl.
proportional pump energy)
Leistungszahl
im Heizbetrieb
(incl.
Der anteiligen
Pumpenleistungen)
8
7
35
6
5
50
4
3
2
1
0
5
Power
consumption (incl.
proportional
energy)
Leistungsaufnahme
in [kW]
(incl. Der pump
anteiligen
Pumpenleistungen)
4
50
3
35
2
1
0
5
7
9
11
13
15
17
19
Kaltwassereintrittstemperatur
[°C]
Cold water inlet temperature inin[°C]
14
21
23
25
27
APPENDIX: 11.3 PERFORMANCE CURVES/PRESSURE LOSSES
11.3.4 Pressure Losses .. 14CS
Pressure
lossinin[Pa]
[Pa]
Druckverlust
30000
Druckverluste
Pressure
losses
Verdampfer
bei1010°C
evaporator at
°C
25000
Pressure loss19
19kPa
kPabei
at
Druckverlust
cold
water nominal flow rate 3,3
3.3 m³/h
m3/h
Kaltwasser-Nenndurchfluß
20000
15000
10000
5000
0
0
0,5
1
1,5
2
2,5
3
3
Cold water flow rate in
/h]
Kaltwasserdurchfluß
in[m
[m³/h]
3,5
4
4,5
5
1,75
2
2,25
2,5
Pressure
loss in
in [Pa]
[Pa]
Druckverlust
30000
Druckverluste
Pressure
losses
Verflüssiger
bei3535°C
°C
condenser at
25000
Pressure loss77kPa
kPabei
at
Druckverlust
heating
water nominal flow rate1,3
1.3m³/h
m3/h
Heizwasser-Nenndurchfluß
20000
15000
10000
5000
0
0
0,25
0,5
0,75
1
1,25
1,5
Heating
water flow ratein
in [m³/h]
[m3/h]
Heizwasserdurchfluß
15
APPENDIXG: 11.3 PERFORMANCE CURVES/PRESSURE LOSSES
11.3.5 Performance Curves .. 22CS
Water outlet temperature in [°C]
Wasseraustrittstemperatur
Heating
capacity
in [kW]
Heizleistung
in [kW]
34
32
35
50
30
28
26
24
22
20
18
16
14
12
10
Bedingungen:
Conditions:
3
Heizwasserdurchsatz
2,0mm³/h
Heating water flow rate 2.0
/h
3
Cold
water
flow
rate
5.0
m
/h
Kaltwasserdurchsatz 5,0 m³/h
8
6
4
2
0
Coefficient
of performance
in the
heating
mode (incl.
proportional pump energy)
Leistungszahl
im Heizbetrieb
(incl.
Der anteiligen
Pumpenleistungen)
10
9
8
7
6
5
4
3
2
1
0
7
35
50
Power
consumption (incl.
proportional
energy)
Leistungsaufnahme
in [kW]
(incl. Der pump
anteiligen
Pumpenleistungen)
6
50
5
4
35
3
2
1
0
5
7
9
11
13
15
17
19
Cold water inlet temperature inin[°C]
Kaltwassereintrittstemperatur
[°C]
16
21
23
25
27
APPENDIX: 11.3 PERFORMANCE CURVES/PRESSURE LOSSES
11.3.6 Pressure Losses .. 22CS
Pressure
lossin
in[Pa]
[Pa]
Druckverlust
35000
Druckverluste
Pressure
losses
Verdampfer
bei1010°C
°C
evaporator at
30000
Pressure
loss20
20kPa
kPa bei
at
Druckverlust
3
cold
water nominal flow rate 5,0
5.0 m
/h
Kaltwasser-Nenndurchfluß
m³/h
25000
20000
15000
10000
5000
0
0
0,5
1
1,5
2
2,5
3
3,5
4
3
Cold water flow rate in
/h]
Kaltwasserdurchfluß
in[m
[m³/h]
4,5
5
5,5
6
Pressure
lossinin[Pa]
[Pa]
Druckverlust
35000
Druckverluste
Pressure
losses
Verflüssiger
bei3535°C
condenser at
°C
30000
Pressure loss88kPa
kPabei
at
Druckverlust
heating
water nominal flow rate2,0
2.0m³/h
m3/h
Heizwasser-Nenndurchfluß
25000
20000
15000
10000
5000
0
0
0,5
1
1,5
2
2,5
3
Heating
water flow ratein
in [m³/h]
[m /h]
Heizwasserdurchfluß
17
3
3,5
4
APPENDIX: 11.3 PERFORMANCE CURVES/PRESSURE LOSSES
11.3.7 Performance Curves .. 27CS
Wasseraustrittstemperatur
Water outlet temperature in [°C]
Heating
capacity
in [kW]
Heizleistung
in [kW]
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
0
50
35
Bedingungen:
Conditions:
3
Heizwasserdurchsatz
2,4mm³/h
Heating water flow rate 2.4
/h
Cold water flow rate 7.0 7,0
m3/hm³/h
Kaltwasserdurchsatz
Coefficient
of performance
in the
heating
mode (incl.
proportional pump energy)
Leistungszahl
im Heizbetrieb
(incl.
Der anteiligen
Pumpenleistungen)
8
7
3
6
5
50
4
3
2
1
0
8
Power
consumption (incl.
proportional
energy)
Leistungsaufnahme
in [kW]
(incl. Der pump
anteiligen
Pumpenleistungen)
5
6
35
4
2
0
5
7
9
11
13
15
17
19
Kaltwassereintrittstemperatur
[°C]
Cold water inlet temperature inin[°C]
18
21
23
25
27
APPENDIX: 11.3 PERFORMANCE CURVES/PRESSURE LOSSES
11.3.8 Pressure Losses .. 27CS
Pressure
lossinin[Pa]
[Pa]
Druckverlust
50000
45000
Druckverluste
Pressure
losses
evaporator at
°C
Verdampfer
bei10
10°C
40000
Pressure
loss16
16kPa
kPabei
at
Druckverlust
cold
water nominal flow rate 7,0
7.0m³/h
m3/h
Kaltwasser-Nenndurchfluß
35000
30000
25000
20000
15000
10000
5000
0
0
1
2
3
4
5
6
Cold water flow rate in
[m3/h]
Kaltwasserdurchfluß
in [m³/h]
7
8
9
10
Druckverlust
Pressure
lossinin[Pa]
[Pa]
40000
35000
Druckverluste
Pressure
losses
°C
condenser at
Verflüssiger
bei35
35°C
30000
Pressure
loss12,5
12.5kPa
kPabei
at
Druckverlust
heating
water nominal flow rate2,4
2.4m³/h
m3/h
Heizwasser-Nenndurchfluß
25000
20000
15000
10000
5000
0
0
0,5
1
1,5
2
2,5
Heating
water flow rateinin[m³/h]
[m3/h]
Heizwasserdurchfluß
19
3
3,5
4
2A-51F
1A
11M
5K
1M
>P
4F
DN
2A
1A
1K
DH
DI
1
H3
<P
5F
CAV 0
7J
C N
9 O
11
DI DI DI DI DI
C 21 11 01 9
9
1CDI-5J
71J
8J
DI DI DI DI
1 1 C 1
H4 4 31 3
81J
N C N
C 21 O
21
21
3ON/21J 1C-21J
1ON/21J
N C N
C 1 O
31 3 31
6R
4X
SGE
6J
G B B B
N 8 7 6
D
61J
N N C
O O 9
01 9
01F
>F
ssulfhcruD-.ötS
CAV 0
59
69
51F
11M -.ötS
1M -.ötS
2X
CAV42
2A
1A
RPS
SVE
5J
)L( 3F
5F
DI DI DI DI DI DI DI DI DI
C 8 7 6 5 4 3 2 1
1
0G-1J
41J
1C-21J
51J
C N C
7 O 7
7
4C-31J
N C N
C 8 O
8
8
G-1J
3
L EP
4,
A0
Tr
3F
21
opl
.
21
opl
.
N
zH05 - CAV 032 zteN
4,
A0
Tr
2F
7R
1X
CAV 032
CAV 42
1T
CAV42
1N
9J
G-2X
1J
G G
0
CAV 0
01J
1CDI-5J
2R
3X
2J
11J
V+ G B B B
D N 3 2 1
C D
)L( 2F
1A-1K
3J
B B B B
C 5 C 4
4
5
7C-41J
21J
C N N N C
4F 1 O3 O2 O1 1
1A-5K
4J
Y Y Y Y V V
4 3 2 1 G G
0
31J
C N N N C
4 O O O 4
6 5 4
1V
.idreV
2V
20
Mains
APPENDIX: 11.4 WIRING DIAGRAMS
11.4.1 Control .. 9CS to .. 22CS
V
R
U
3
M
W
S
2
1
(compressor supply via utility
company disable contactor)
(not in WI 9CS)
1M
T
4
3
6
5
22K
zH05 - CAV004 EP/3
zteN
)ztühcsrrepS-UVE rebü rethcidreV gnusiepsniE(
3
)tkerid epmupnennurB gnusiepsniE(
Mains power supply
Wiring modification:
In systems without utility
company disable facility,
the direct supply for the well
pump may be dispensed with.
/1X
EP
)SC9 IW ni thcin(
7N
6.1/
1K
3
3
zH05 - CAV004 EP/3
zteN
(direct supply of well pump)
2
3
M
4
1
5X
Mains power supply
11M
6
3
EP
3L
2L
1L
EP
13L
12L
11L
21
Manufacturer
Pump type / Nominal current
A3,2 / 5/A8PS
A4,1 / 4/A5PS
A4,1 / 6/A3PS
A4,1 / 6/A2PS
mortsnneN / pyT-nepmuP
sofdnurG :relletsreH
69
4.1/ 59
)SC72 IW( A5,3-2,2
)SC22- sib SC9 IW( A0,2-4,1
51F
5K
3.1/
5
.nellaftne
epmupnennurB eid rüf
gnusiepsniE etkerid eid nnak
errepS-UVE enho negalnA nI
:nrednä gnuthardreV
gnurefeilsuA ieb gnuthardreV
Wiring upon delivery
APPENDIX: 11.4 WIRING DIAGRAMS
11.4.2 Load .. 9CS to .. 22CS
tr repseg PW = neffo tka tnoK
5R
CAV42
2X
32K
22K
RPS
)L( 3F
.l
o
p
2
1
rablhäw tsi
EW net2 sed noitknuF eiD
tr repseg PW = neffo tka tnoK
3B
<T
J
1
4
C
7
W002
.xam
91M
L1
A1
+)(
1X N -
T1
A2
(-)
J
1
3
C4
21K
He
zsi
t
ba
01E
redo
4J
Y Y Y Y V V
4 3 2 1 G G
0
31J
31M
C N N N C
4 O O O 4
6 5 4
4B
1X
81M
NEP -
<T
ztühcs rrepS -UVE
SVE
5J
.l
o
p
2
1
N
1X
DI DI DI DI DI DI DI DI DI
C 8 7 6 5 4 3 2 1
1
0G-1J
41J
G-1J
CAV 0
gnagnie r repS ret2
2nd shut-off input
Contact open = HP disabled
4X
6J
51J
1X
3F
NEP -
2F
Tr
A0
4,
1X 40,
3
zH05 - CAV 032 zteN
L EP
Tr
A
AM
C N C
7 O 7
7
ZM
N C N
C 8 O
8
8
N1X
EP -
G B B B
N 8 7 6
D
61J
1X
-rehcsiM
sierktpuaH
Utility company shut-off contactor
Contact open = HP disabled
CAV 0
7J
N-
4
C N N N C
9 O O O 9
11 01 9
DI DI DI DI DI
C 21 11 01 9
9
1X
3
12M
The function of the suppl. heating
system can be selected
DI
1
H3
0G-1J
EP -
N-
3
61M
Mixer primary
circuit
71J
AM
N1X
EP -
2
12K
3
9E
W002
.xam
5H
L1
A1
+)(
T1
A2
(-)
N - 1X
11K
11N
7R
11M
.idreV
2V 1V
C N N N C
1 O O O 1
3 2 1
21J
3J
B B B B
C 5 C 4
4
5
02K
2
NEP -
1A-5K
1X
KH
3R
2J
3X
P L
E 3
G G
0
1J
5X
1N
9J
2L 1L
01J
1R
2R
V+ G B B B
D N 3 2 1
C D
01N
11J
)L( 2F
1A-1K
xxxxx
4
zH05 - CAV004 EP/L3
zteN
22
DI DI DI DI
1 1 C 1
H4 4 31 3
81J
N C N
C 21 O
1
21
2
8J
N C N
C 1 O
3 1
31
3
ZM
3
51M
Mains power supply
4
22M
Mains power supply
APPENDIX: 11.4 WIRING DIAGRAMS
11.4.3 Terminal Diagram .. 9CS to .. 22CS
APPENDIX: 11.4 WIRING DIAGRAMS
11.4.4 Legend .. 9CS TO .. 22CS
A1
A2
Wire jumper, must be removed upon installation of a utility company disable contactor
Wire jumper, must be removed if 2nd disable input is used
B3*
B4*
Thermostat, hot water
Thermostat, swimming pool water
E9*
E10*
Electr. immersion heater, hot water
Suppl. heat source (boiler or electr. heating element
F2
F3
F4
F5
F10
F15
Load fuse for N1 relay outputs across J12 at J13
4.0 A slow-acting
Load fuse for N1 relay outputs across J15 to J18
4.0 A slow-acting
Pressostat high pressure
Pressostat low pressure (from ..22CS, F5 is a limiter with manual reset)
Flow control switch
Overload relay for M11 / the overload relay is designed for the pump included in the brine kit
H5*
Fault indicator lamp
J1...J18
Terminal connector at N1
K1
K5
K11*
K12*
K20*
K21*
K22*
K23*
Contactor, compressor
Contactor, primary pump
Electron. relay remote fault indicator (on relay module)
Electron. relay, swimming pool water circulating pump (on relay module)
Contactor for E10
Contactor for E9
Utility company disable contactor
SPR auxiliary relay
M1
M11*
M13*
M15*
M16*
M18*
M19*
M21*
M22*
Compressor
Primary pump
Heating circulating pump
Heating circulating pump
Auxiliary circulating pump
Hot water circulating pump
Swimming pool water circulating pump
Mixer, primary circuit
Mixer heating circuit 2
N1
N7
N10*
N11*
Heat pump controller
Soft start control (not in WI 9CS units)
Remote control station
Relay module
R1
R2
R3
R5
R6
R7
External sensor
Return sensor
Hot water sensor (as an alternative to the hot water thermostat)
Sensor for heating circuit 2
Freeze protection sensor
Coding resistor 10k
T1
Safety isolating transformer 230/24VAC-28VA
X1
X2
X3
X4
X5
Terminal strip mains control L/N/PE-230VAC-50Hz/fuses/N and PE terminal block
Terminal strip 24VAC terminal block
Terminal strip GND terminal block for sensors R1/-2 and -3 at J2
Terminal strip GND terminal block for sensors R5 and -6 at J6
Terminal strip power supply 3L/PE-400VAC-50Hz
Abbreviations:
EVS
SPR
Utility company disable input
Supplementary disable input
MA*
MZ
Mixer OPEN - primary heating circuit
Mixer CLOSED - primary heating circuit
* Components to be supplied by the customer, or available as accessories
23
2A
1A
11M
5K
1M
2A
1A
>P
4F
51
81 61
1K
DN
2A
1A
DI DI DI DI
1 1 C 1
4 4 1 3
H
3
1.1K
<P
2A
2.1K
7J
6R
4X
SGE
6J
G B B B
N 8 7 6
D
61J
C N N N C
9 O O O 9
1 0
1 9
1
DI DI DI DI DI
1 1 9
C 1 1
0
9 2
CAV 0
1A
5F
2.1K
DH
DI
1
3
H
1CDI-5J
71J
8J
81J
N C N
C 2
1 O
1
1
2
2
3ON/21J 1C-21J
1ON/21J
N C N
C 1 O
1 3 1
3
3
2T
1T
41F
2Q
21F
01F
> F
1M
11
2M
11
41
1
2
1M-.ötS
1Q
2X
2A
1A
CAV42
SVE
RPS
11M-.ötS
41
ssulfhcruD-.ötS
CAV 0
1T-41F
1-1X 5F
5J
)L( 3F
4
G-1J
4Y
1
2
1B
>P
1
1A-5K
3
3F
L EP
4,
A0
Tr
21
opl
.
)L( 2F
1X
CAV 032
CAV 42
1T
CAV42
1N
9J
G-2X
1J
G G
0
CAV 0
01J
1CDI-5J
2R
3X
2J
11J
+ G B B B
V
D N 3 2 1
C D
1A2.1K
6ON-31J
21
opl
.
N
zH05 - CAV 032 zteN
4,
A0
Tr
7R
B B B B
C 5 C 4
4
5
3J
C N N N C
1 O O O 1
3 2 1
21J
7C-41J
2F
4F
4J
Y Y Y Y V V
4 3 2 1 G G
0
1C-21J
31J
C N N N C
4 O O O 4
6 5 4
DI DI DI DI DI DI DI DI DI
C 8 7 6 5 4 3 2 1
1
41J
4C-31J 0G-1J
51J
C N C
7 O 7
7
7C-41J
N C N
C 8 O
8
8
2V 1V
.idreV
24
Mains power supply
ANHANG: 11.4 WIRING DIAGRAMS
11.4.5 Control .. 27CS
1M
2
5.1/-
1
8.1/
41
5K
11M
4.1 / 21
11
A5,3-2,2
1Q
6
3
4
1
2
3
M
5
1
> I
2
> I
4
> I
3
6
5
EP
1X
gnurefeilsuA ieb gnuthardreV
EP
13L
12L
5X
3
A3,2 /
A8PS
mortsnneN / pyT-nepmuP
sofdnurG :relletsreH
zH05 - CAV004 EP/3
zteN
)tkerid epmupnennurB gnusiepsniE(
Manufacturer
Pump type / Nominal current
2M
41F
1
2
R
21F
U
3
M
V
S
4
3
11L
3
22K
zteN
zH05 - CAV004 EP/3
)ztühcsrrepS-UVE rebü rethcidreV gnusiepsniE(
3
25
5.1/
1M
6
T
W
7N
8.1/
1.1K
5
.nellaftne epmupnennurB eid rüf
gnusiepsniE etkerid eid nnak
,errepS-UVE enho negalnA nI
:nrednä gnuthardreV
Wiring upon delivery
2
1
2
> I
(direct supply of well pump)
4
3
4
> I
1
Mains power supply
6
5
6
> I
3
Wiring modification:
In systems without utility
company disable facility,
the direct supply for the well
pump may be dispensed with.
8.1/
1K
41
5
5X
(compressor supply via utility company
disable contactor)
5.1 / 21
11
A5,3-2,2
2Q
EP
3L
2L
1L
Mains power supply
APPENDIX: 11.4 WIRING DIAGRAMS
11.4.6 Load .. 27CS
4X
5R
CAV42
2X
32K
22K
RPS
)L( 3F
.l
o
p
2
1
rablhäw tsi
EW net2 sed noitknuF eiD
trrepseg PW = neffo tkatnoK
4B
3B
<T
1X N-
2
02K
eHi
szt
ba
redo
J
1
4
C7
01E
W002
.xam
91M
1L
A1
+)(
KH
C N N N C
4 O O O 4
6 5 4
31J
T1
A2
(-)
J
1
3
C4
21K
1X
11M
W002
.xam
5H
1L
A1
+)(
1T
A2
(-)
N - 1X
11K
11N
7R
1V
3J
3R
11J
2J
3X
5X
9J
1N
1J
G G
0
01J
1R
2R
+ G B B B
V
D N 3 2 1
C D
1A2.1K
4
zH05 - CAV004 EP/L3
zteN x 2
4
P L L L P L L L
E 13 12 11 E 3 2 1
)L( 2F
B B B B
C 5 C 4
5
4
21J
xx xxx
01N
.idreV
2V
C N N N C
1 O O O 1
3 2 1
NEP-
1A-5K
4J
Y Y Y Y V V
4 3 2 1 G G
0
<T
z tühcsrrepS-UVE
SVE
5J
N-
-1X
EP-
81M
31M
DI DI I DI DI DI DI DI DI
C 8 D
7 6 5 4 3 2 1
1
.l
o
p
2
1
1X
N 1
N1X
EP-
0G-1J
41J
G-1J
CAV 0
gnagnierrepS ret2
trrepseg PW = neffo tkatnoK
G B B B
N 8 7 6
D
6J
51J
C N C
7 O 7
7
3F
AM
2F
Tr
A0
4,
ZM
N C N
C 8 O
8
8
N1X
EP-
Tr
A
L EP
3
zH05 - CAV 032 zteN
1X 40,
The function of the suppl. heating
system can be selected
CAV 0
DI DI DI DI DI
1 1
1 0
C 2
1 9
9
7J
61J
1X
12M
4
C N N N C
9 O O O 9
1
1 9
1 0
N-
3
2nd shut-off input
Contact open = HP disabled
DI
1
3
H
0G-1J
N1X
EP-
3
61M
Utility company shut-off contactor
Contact open = HP disabled
DI DI DI DI
1 4
1 C 3
1
4
1
H
3
71J
2
12K
3
9E
26
8J
81J
N C N
C 2
1 O
1
1
2
2
N1X
EP-
NAM
N
N
C C
1 O
1 3
1
3
3
NZM
3
51M
Mains power supply
4
22M
2x Mains power supply
APPENDIX: 11.4 WIRING DIAGRAMS
11.4.7 Terminal Diagram .. 27CS
APPENDIX: 11.4 WIRING DIAGRAMS
11.4.8 Legend .. 27CS
A1
A2
Wire jumper, must be removed upon installation of a utility company disable contactor
Wire jumper, must be removed if 2nd disable input is used
B1
B3*
B4*
Pressostat power adaptation for hot water preparation
Thermostat, hot water
Thermostat, swimming pool water
E9*
E10*
Electr. immersion heater, hot water
Suppl. heating system
F2
F3
F4
F5
F10
F12
F14
Load fuse for N1 relay outputs across J12 and J13
Load fuse for N1 relay outputs across J15 to J18
Pressostat high pressure
Pressostat low pressure limiter with manual reset
Flow control switch
Thermal protector N7
Electronic motor protection compressor 1
H5*
Remote fault indicator lamp
J1...J18
Terminal connector at N1
K1
K1.1
K1.2
K5
K11*
K12*
K20*
K21*
K22*
K23*
Contactor, compressor
Contactor, breakaway starting current limiter of M1
Time relay, delay K1
Contactor for M1
Electron. relay for H5
Electron. relay for M19
Contactor for E10
Contactor for E9
Utility company disable contactor
SPR auxiliary relay
M1
M11*
M13*
M15*
M16*
M18*
M19*
M21*
M22*
Compressor
Primary pump
Heating circulating pump
Circulating pump, heating circuit 2
Auxiliary circulating pump
Hot water circulating pump
Swimming pool water circulating pump
Mixer primary circuit
Mixer heating circuit 2
N1
N7
N10*
N11*
Heat pump controller
Soft start board
Remote control station
Relay module
Q1
Q2
Power circuit-breaker, well pump
Power circuit-breaker, compressor
R1
R2
R3*
R5
R6
R7
External sensor
Return sensor
Hot water sensor (as an alternative to the hot water thermostat)
Sensor for heating circuit 2
Freeze protection sensor
Coding resistor 10k
T1
Safety isolating transformer 230/24VAC-28VA
X1
X2
X3
X4
X5
Terminal strip mains control L/N/PE-230VAC-50Hz/fuses/N and PE terminal block
Terminal strip 24VAC terminal block
Terminal strip GND terminal block for sensors R1/-2 and -3 at J2
Terminal strip GND terminal block for sensors R5 and -6 at J6
Terminal strip power supply 3L/PE-400VAC-50Hz
Y4
Solenoid valve power adaptation for hot water preparation
Abbreviations:
EVS
Utility company disable input
SPR
Supplementary disable input
MA*
Mixer OPEN - primary heating circuit
MZ
Mixer CLOSED - primary heating circuit
4,0 A slow-acting
4.0 A slow-acting
* Components to be supplied by the customer, or available as accessories
27
Shut-off valve with check valve
Heat consumer
Strainer
Temperature sensor
Flexible connecting hose
Well circulating pump
Heating circulating pump
Hot water circulating pump
External wall sensor
Return sensor
Hot water sensor
Cold water
Hot water
Check valve
Thermostat/manual valve
Suction well
Injection well
Expansion vessel
Circulating pump
Safety valve
Overflow valve
Shut-off valve with drain
Shut-off valve
Ground water
direction of flow
Hot water tank
Electric distribution
Heat pump controller
Buffer tank
Heat pump
APPENDIX: 11.5 HYDRAULIC BLOCK DIAGRAM
Hydraulic Block Diagram
28
APPENDIX: 11.6 EC DECLARATION OF CONFORMITY
EC Declaration of conformity
Declaration of Conformity
The undersigned
KKW Kulmbacher Klimageräte-Werk GmbH,
Division Dimplex
Am Goldenen Feld 18
D-95326 Kulmbach
hereby confirm that the design and construction of the product(s) listed below, in the version(s) placed
on the market by us, conform to the relevant basic requirements of the applicable EC directives.
This declaration becomes invalidated if any modifications are made to the product(s) without our
prior authorization.
Designation of the product(s):
EC Directives:
Brine-to-water heat pumps
EC Low Voltage Directive
(73/23/EEC)
EC EMC Directive
(89/336/EEC)
Pressure Equipment Directive
(97/23/EEC)
for indoor installation withR407C
Water-to-water heat pumps
for indoor installation withR407C
Type(s):
Harmonized EN Standards:
SI 5CS
SI 7CS
SI 9CS
SI 11CS
SI 14CS
SI 17CS
SI 21CS
WI 9CS
WI 14CS
WI 22CS
WI 27CS
Requirements of category II
Order No.:
337 280
337 290
337 300
337 310
337 320
337 330
337 340
National Standard/Directives:
338 720
337 350
337 360
337 370
Kulmbach, 07.05.2002
General Manager
29
Technical Director
Notes
Notes
KKW Kulmbacher Klimageräte-Werk GmbH
Division Dimplex
Am Goldenen Feld 18
D-95326 Kulmbach
Subject to technical modifications
Fax (0 92 21) 709-589
www.dimplex.de
32