Download SED2 Variable Frequency Drives Parameter

Transcript
SED2 VFD Parameter Reference Guide
P0706[2]
Function of digital input 6
Min:
Unit:
0
-
Def:
15
Level 2
Max:
99
Details:
Selects function of digital input 6 ( via analog input).
Enum:
0
1
2
3
4
9
10
11
12
13
14
15
16
17
25
26
27
28
29
33
99
Digital input disabled
ON/OFF1
ON reverse /OFF1
OFF2, coast to standstill
OFF3, quick ramp-down
Fault acknowledge
JOG right
JOG left
Reverse
MOP (motor potentiometer) up (increase frequency)
MOP (motor potentiometer) down (decrease frequency)
Fixed setpoint (Direct selection)
Fixed setpoint (Direct selection + ON)
Fixed setpoint (Binary coded selection + ON)
DC brake enable
Enable Essential Service
Enable PID
Bypass mode command input
External trip
Disable additional freq setpoint
Enable BiCo programming
Index:
P0706[0]: 1st Command data set (CDS)
P0706[1]: 2nd Command data set (CDS)
Note:
Selection 17 (Binary coded selection + ON) is identical to selection 15.
Reference:
See P0701 (function of digital input 1).
40
Siemens Building Technologies, Inc.