Download SED2 Variable Frequency Drives Parameter
Transcript
Parameter Details (Numeric Listing) P2014[2] USS telegram off time Min: Unit: 0 ms Def: 0 Level 3 Max: 65535 Details: Defines a time T_off after which a fault will be generated (F0070) if no telegram is received via the USS channels. Index: P2014[0]: Serial interface COM link P2014[1]: Serial interface BOP link Note: By default (time set to 0), no fault is generated (that is, watchdog disabled). P2040 CB telegram off time Min: Unit: 0 ms Def: 20 Level 3 Max: 65535 Details: Defines time after which a fault will be generated (F0070) if no telegram is received via the link (SOL). Dependency: Setting 0=watchdog disabled. P2041[5] CB parameter Min: Unit: 0 - Def: Level 3 0 Max: 65535 Details: Configures a CB (communication board/module). Index: P2041[0]: CB parameter 0 P2041[1]: CB parameter 1 P2041[2]: CB parameter 2 P2041[3]: CB parameter 3 P2041[4]: CB parameter 4 r2050[8] CO: PZD from CB Min: Unit: - Def: Level 3 - Max: - Details: Displays PZD received from CB (communication board/module). Index: r2050[0]: Received word 0 r2050[1]: Received word 1 r2050[2]: Received word 2 r2050[3]: Received word 3 r2050[4]: Received word 4 r2050[5]: Received word 5 r2050[6]: Received word 6 r2050[7]: Received word 7 Note: The control words can be viewed as bit parameters. Siemens Building Technologies, Inc. 89