Commissioning and Diagnostics
6.8 Diagnostics with STEP 7
Error type
10011B
10101B
19D
21D
Error text
Meaning
HART communication
error (HART
diagnostics)

Reference channel
error



HARD field device is not
responding
Timing error
Remedy


Check the process wiring
Correction of the configuration
internal reference junction: TC 
sensor module defective or not
available.

external reference junction
(RTD): Parameters do not point
to the RTD module
Exchanging or connecting the
TC Sensor Module
Correction of the configuration
10110B
22D
HART other statuses
available
(HART warning)
---
---
10111B
23D
reserved for HART
(HART warning)
---
---
11000B
24D
Actuator disconnection
Intrinsically safe switch signal
switched on at 4 DO
---
11010B
26D
External fault





Encoder error
Encoder supply faulty
Changeover contact error
Actuator error
HART field device error


11011B
27D
HART configuration
modified (HART
warning)
---
---
11101B
29D
HART primary variable
outside the limits
(HART diagnostics)
---
---
11110B
30D
HART auxiliary variable --outside the limits
(HART diagnostics)
---
Replacement of
encoder/actuator/HART field
device
Correction of the process
wiring
Note
Control response
A control response is implemented for assigning parameters in the electronic modules of the
ET 200iSP.
If the electronic module receives a faulty parameter, this is rejected. The electronic then
continues to operate with its already valid parameters (the default parameters from the initial
parameter assignment). No "parameter error" diagnostic messsage is output.
The update interrupt function can be used to check the changed parameters of the electronic
module. Refer to chapter "Interrupts (Page 171) ".
No update interrupt is generated in the case of faulty parameters.
ET 200iSP
Operating Instructions, 01/2010, A5E00247483-04