Download User manual

Transcript
BLCDP-4M12MT-4AO-V
4 Technical data
Type
Ident-No.
BLCDP-4M12MT-4AO-V
6811181
Supply voltage
Admissible range
System power supply
Voltage supply connection
Operating current
Nominal voltage Vi
Nominal voltage Vo
Max. sensor supply Isens
Max. load current Io
24 VDC
18...30 VDC
via separate source
2 x M12, 5-pin
750 mA
24 VDC
24 VDC
4A
4A
Fieldbus transmission rate
Adjustment transmission rate
Fieldbus addressing range
Fieldbus addressing
Service interface
Fieldbus connection technology
Fieldbus termination
9.6 kbps…12 Mbps
auto detetcion
0...99
2 decimally coded rotary switches
RS232 interface
2 x M12, 5-pin, reverse keyed
external
Analolgue outputs
Output type
Type of output diagnostics
Sensor supply
Load resistance, resistive
Load resistance, capacitive
Transmission frequency
Basic fault limit at 23 °C
Repeatability
Temperature coefficient
Resolution
Measured-value display
Edition • 2011-2-23
Operating temperature
Storage temperature
Protection class
housing material
7 / 22011
-10/0 … 10 V
channel diagnostics
24 VDC, 250 mA per channel
> 1 kò
< 1 µF
< 100 Hz
< 0.3 %
< 0.05 %
< 300 ppm/°C of full scale
16 bit
16 bit signed integer
12 bit full range left justified
-40...+70 °C
-40...+85 °C
IP69K
Glass-filled nylon, nickel plated brass connectors
Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com