Download Intrinsically Safe Pressure and Temperature Transducer
Transcript
www.swagelok.com Intrinsically Safe Pressure and Temperature Transducers (PTX Series) User’s Manual This manual contains important information for the safe and effective operation of the Swagelok® Intrinsically Safe Pressure and Temperature Transducers, PTX series. Users must read and understand its contents before operating the transducer. 2 Instrinsically Safe PTX User’s Manual Contents Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Product Information . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Control Drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Interface Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Safety Safety Summary R ead the entire safety information section and User’s Manual before using this product. Failure to do so can result in serious injury or death. Signal Words and Safety Alert Symbols Used in this Manual WARNINGStatements that indicate a hazardous situation which, if not avoided, could result in death or serious injury. CAUTIONStatements that indicate a hazardous situation which, if not avoided, could result in minor or moderate injury. NOTICEStatements that indicate a hazardous situation which, if not avoided, could result in damage to the equipment or other property. Safety alert symbol indicating a potential personal injury hazard. Safety alert symbol indictating a potential danger to life or of serious injuries due to catapulting parts. Instriniscally Safe PTX User’s Manual Safety Instructions For proper and safe operation, Swagelok intrinsically safe PTX series transducers must be installed, operated, and serviced according to applicable local regulations and these instructions. Otherwise, serious personal injuries, damage or both can occur. Except for adjusting the length of the wires, the electrical connection provided on the transducer must be used as originally supplied and not bypassed. Only qualified persons should work on these instruments. Do not exceed the overpressure rating. Before servicing any installed pressure transducer you must ■ disconnect power ■ depressurize system ■ purge the transducer Residual material may be left in the transducer and system. Introduction The Swagelok Intrinsically Safe Pressure and Temperature Transducer (PTX) is an industrial pressure and temperature transducer for monitoring fluid pressure and temperature in automated fluid systems using a MEMS pressure-sensing technology. The PTX provides two analog outputs to monitor fluid pressure and temperature in automated fluid systems. Each PTX communicates directly with the Swagelok Intrinsically Safe Intelligent Control Module™ (ICM™) unit through one of the analog input connection ports on the ICM. Each PTX can also interface with traditional automation equipment with suitable analog inputs such as Programmable Logic Controller (PLC), Distributed Control System (DCS), or Supervisory Control and Data Acquisition (SCADA) system. The PTX is available with a 1.5 in. Swagelok Modular Platform Component (MPC) surface mount in accordance with ANSI/ISA 76.00.02 or with 1/4 in. or 6 mm Swagelok tube fitting end connections. It is UL® and ATEX certified for use in hazardous areas. 3 4 Instrinsically Safe PTX User’s Manual Product Information Network Connector Plug Power LED Sensor LED PTX Enclosure Screw (2, other is opposite one shown) Network Connector Plug Power LED Sensor LED PTX Enclosure Screw (2, other is opposite one shown) Mounting holes Fig. 1 PTX with MPC Modular Surface Mount Front View Fig. 2 PTX with Swagelok Tube Fitting End Connections Instriniscally Safe PTX User’s Manual Specifications Voltage Current Operating (Ambient) Media Storage Temperature Measurement Full-scale Range Pressure Measurement Overrange Pressure Burst Pressure Temperature Pressure Weight Certifications Ingress Protection Electromagnetic Compatibility Vibration Shock Entity Parameters Power 9 to 28 V (dc), 24 V (dc), nominal < 20 mA (dc) at 24 V (dc) Temperature (environment) Minimum 23°F (–5°C) Maximum 158°F (70°C) Minimum 23°F (-5°C) Maximum 158°F (70°C) Minimum -40°F (–40°C) Maximum 158°F (70°C) Temperature Measurement Measurement Range 23 to 158°F (–5 to 70°C) Accuracy, including: Repeatability ± 9°F (± 5°C absolute accuracy) Hysteresis Nonlinearity Pressure 0 to 50 psig (0 to 3.4 bar) 0 to 250 psig (0 to 17.2 bar) 0 to 500 psig (0 to 34.4 bar) Accuracy, including: Repeatability ± 2 % of full scale pressure of measurement Hysteresis Nonlinearity 2 × full scale 5 × full scale Output Reading to Voltage Conversion -40°F (-40°C) = 0.5 V (dc) 158°F (70°C) = 4.5 V (dc) 0 psig = 0.5 V (dc) full scale = 4.5 V (dc) Miscellaneous Data with MPC process connections 0.83 lb (375 g) with 1/4 in. and 6 mm Swagelok tube 1.27 lb (576 g) fitting end connections ■ ANSI/NFPA Class I, Division 1, Groups A, B, C, D, Temperature Class T4 ■ UL 913 - Edition 8, UL 60079-0 - Edition 6, UL 60079-11 - Edition 6 ■ cUL® - CSA C22.2 NO. 157-92 - Edition 3 ■ ATEX Standards: EN 60079-0, EN 60079-11, EN 60079-26 ■ IEC: IEC 60079-0 - Edition 6, IEC 60079-11 - Edition 6, IEC 60079-26 - Edition 2 IP64 EN 61326-1:2006 ■ RF Emissions: EN 55011 ■ ESD Immunity: EN 61000-4-2 ■ RF Immunity: EN 61000-4-3 ■ EFT Immunity: EN61000-4-4 ■ Conducted Immunity: EN 61000-4-6 Tested to IEC 60068-2-6:2007 ■ 10 to 150 Hz, at 2.04 g ■ 10 sweeps at 0.5 Octave/min Tested to IEC 6068-2-27:1987 ■ 50 g, 11 msec ■ 3 positive and 3 negative pulses each axis See Control Drawing: PTX-V-0011-SCHEDULE Note:Before installing the PTX in a hazardous location, review the control drawing on page 6. This will help ensure all electrical connections to and from the PTX comply with safety requirements. For an electronic copy of this manual, see www.swagelok.com. 5 Fig. 3 PTX-V-0011-SCHEDULE A B C D 4 3 DWG. NO. 1 PTX-V-0011-SCHEDULE 2 4 𝑈𝑈𝑂𝑂 ×𝐼𝐼𝑂𝑂 . ≥ ≥ ≥ ≤ ≤ Associated Apparatus Voc or Vt (or Uo) Isc or It (or lo) Po Ca (or Co) La (or Lo) 4 𝑉𝑉𝑂𝑂𝑂𝑂 ×𝐼𝐼𝑆𝑆𝑆𝑆 = The PTX has been certified to the following standards: UL 913 8th Edition CSA C22.2 No. 157 IEC 60079-0:2011 IEC 60079-11:2012 IEC 60079-26:2009 EN 60079-0:2012+A11:2013 EN 60079-11:2012 EN 60079-26:2007 Certifications No assembly of the PTX is required by the user. Pressure Temperature Transducer Installation Substitution of components may impair intrinsic safety. Associated apparatus must not be used in combination unless permitted by associated apparatus certification. 8 7 THIS PRINT IS THE EXCLUSIVE PROPERTY OF SWAGELOK COMPANY. IT MUST BE RETURNED ON REQUEST ALONG WITH ANY DOCUMENTS CONTAINING INFORMATION OBTAINED FROM THIS PRINT. NEITHER THIS PRINT NOR ANY PART OF IT NOR ANY INFORMATION CONCERNING IT MAY BE COPIED, DISCLOSED TO OTHERS OR USED FOR ANY PURPOSE EXCEPT IN FURTHERANCE OF YOUR BUSINESS WITH SWAGELOK. THE PARTS REFERRED TO ON THIS PRINT MAY BE THE SUBJECT OF PATENTS AND/OR PENDING APPLICATIONS AND MAY NOT BE MANUFACTURED WITHOUT PERMISSION FROM SWAGELOK COMPANY. 6 .031 .015 1 DEGREE 5 -- DIMENSIONS ARE INCHES NEXT TO [MILLIMETERS]. .XX .XXX ANGLES TOLERANCE ON ENGLISH DIMENSIONS UNLESS OTHERWISE SPECIFIED TITLE 4 © Swagelok Company All Rights Reserved 3 MM CHECK/APR BY MJR DRAWN BY APPROVAL/SCHEDULE DRAWING Jul-31-14 DATE Jul-31-14 DATE 1 SCALE 1 of 2 SHEET NONE DW G. PTX-V-0011-SCHEDULE REV. NO . 2 SPECIFICATION: WARNING: ANY CHANGES MADE TO THIS DOCUMENT MUST BE REVIEWED AND APPROVED BY SWAGELOK'S COMPLIANCE DEPARTMENT SWAGELOK PRESSURE TEMPERATURE TRANSDUCER CONTROL DRAWING The ambient operating (Tamb) range for this product is -5C to 70C. Use outside of this range will negate intrinsic safety. Pressure Temperature Transducer Ratings If Po of the associated apparatus is not known, it may be calculated using this formula: 𝑃𝑃𝑂𝑂 = I.S. Equipment Vmax (or Ui) Imax (or Ii) Pmax (or Pi) Ci + Ccable Li + Lcable Table 1 Entity Parameters: Where the cable capacitance per foot are not known, the following values shall be used: Ccable= 60 pF/ ft., Lcable = 0.2 μH/ft. Similarly, the inductance of the field wiring from the intrinsically safe equipment to the associated apparatus shall be calculated and must be included in the system calculations as shown below in Table 1. Cable inductance Lcable plus the intrinsically safe equipment inductance, Li, must be less than the marked inductance La (or Lo). Capacitance of the field wiring from the intrinsically safe equipment to the associated apparatus shall be calculated and must be included in the system calculations as shown in Table 1. Cable capacitance, Ccable, plus intrinsically safe equipment capacitance, Ci, must be less than the marked capacitance Ca (or Co). When required by the manufacturer's control drawing, the associated apparatus must be connected to a suitable ground electrode per the National Electrical Code (ANSI/NFPA 70), the Canadian Electrical Code, or other local installation codes, as applicable. The resistance of the ground path must be less than 1 ohm. Associated apparatus must be installed in accordance with its manufacturer's control drawing and Article 504 of the National Electrical Code (ANSI/NFPA 70), the Canadian Electrical Code, or other local installation codes, as applicable. 5 Associated Apparatus 6 The Entity Concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of open circuit voltage (Voc) and short circuit current (Isc) of the associated apparatus are less than or equal to the maximum voltage (Vmax) and current (Imax) of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than the acceptable capacitance (Ci+Ccable) and inductance (Li+Lcable) respectively for the intrinsically safe apparatus. 7 Entity Parameters DCN-00004165 DESCRIPTION: - 8 DCN REVISIONS REV. A B C D 6 Instrinsically Safe PTX User’s Manual Control Drawing Fig. 3 PTX-V-0011-SCHEDULE continued A B C D DCN-00004165 DCN 8 7 Transducer Connector 1 2 3 4 6 7 8 9 Pin 3 9 8 28 V Vmax 1A Imax 6 0 Ci 0 Li 5 Any associated apparatus power supply with Entity Concept Parameters appropriate for connection to an IS device with Entity concept parameters listed in Table 1. (2) Any IS or Associated Apparatus communication controller with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to IS devices with Entity Concept parameters listed in Table 1. (1) Installation Diagram 4 Non-Hazardous Location Power(2) Communications Controller/ Barrier (1) 3 DWG. NO. 8 7 THIS PRINT IS THE EXCLUSIVE PROPERTY OF SWAGELOK COMPANY. IT MUST BE RETURNED ON REQUEST ALONG WITH ANY DOCUMENTS CONTAINING INFORMATION OBTAINED FROM THIS PRINT. NEITHER THIS PRINT NOR ANY PART OF IT NOR ANY INFORMATION CONCERNING IT MAY BE COPIED, DISCLOSED TO OTHERS OR USED FOR ANY PURPOSE EXCEPT IN FURTHERANCE OF YOUR BUSINESS WITH SWAGELOK. THE PARTS REFERRED TO ON THIS PRINT MAY BE THE SUBJECT OF PATENTS AND/OR PENDING APPLICATIONS AND MAY NOT BE MANUFACTURED WITHOUT PERMISSION FROM SWAGELOK COMPANY. 6 .031 .015 1 DEGREE 5 -- DIMENSIONS ARE INCHES NEXT TO [MILLIMETERS]. .XX .XXX ANGLES TOLERANCE ON ENGLISH DIMENSIONS UNLESS OTHERWISE SPECIFIED TITLE 4 © Swagelok Company All Rights Reserved 3 MM CHECK/APR BY MJR DRAWN BY APPROVAL/SCHEDULE DRAWING Jul-31-14 DATE Jul-31-14 DATE 1 SCALE 2 of 2 SHEET Hazardous Location NONE DW G. PTX-V-0011-SCHEDULE REV. NO . 2 1 PTX-V-0011-SCHEDULE 2 SPECIFICATION: WARNING: ANY CHANGES MADE TO THIS DOCUMENT MUST BE REVIEWED AND APPROVED BY SWAGELOK'S COMPLIANCE DEPARTMENT SWAGELOK PRESSURE TEMPERATURE TRANSDUCER CONTROL DRAWING GND Pressure Power Temperature 5 Signal Power Signal (Temperature) Signal (Pressure) Field Wiring Diagrams All Model Table 2: Entity Parameters by Pin DESCRIPTION: - REV. REVISIONS A B C D Instriniscally Safe PTX User’s Manual 7 8 Instrinsically Safe PTX User’s Manual Installation Mounting A PTX with 1/4 in. or 6 mm Swagelok tube fitting process end connections should be installed in the system according to Swagelok Tube Fitting Instructions for 1 in. (25 mm) and smaller fittings, MS-12-01. Mounting holes are provided on the bottom of the PTX body. See below for dimension information. A PTX with a 1.5 in. Swagelok MPC modular surface mount should be installed in the system according to the surface mount assembly instructions in the MPC Series Modular Platform Components Assembly and Service Instructions, MS‑12‑39. Dimensions, in inches (millimeters), are for reference only and subject to change. NOTICE Removal of the PTX enclosure screws will void the product warranty, damage the Ingress Protection rating, and negate the intrinsically safe hazardous location rating of the PTX. Analog input connector (male DB9) Analog input connector (male DB9) PTX Enclosure Screw (2, other is opposite one shown, also on MPC modular surface mount product) 1.49 (37.8) Top 5.27 5.85 (134) (149) Top 1.625 (41.3) dia 0.59 (15.0) Four mounting holes, 0.21 (5.3) dia Four tapped mounting holes, #10-32 UNF-2C Hole depth: 0.25 (6.4) min 0.43 (10.9) max 2× 46° 44° 1.50 (38.2) 1.50 (38.2) 0.25 (0.64) Front Bottom MPC Modular Surface Mount 2.54 (64.5) Bottom Front Swagelok Tube Fitting End Connections Fig. 4 Product Dimensions Instriniscally Safe PTX User’s Manual Power Supply The instrinsically safe PTX can be used with any power supply capable of providing between 9 and 28 V (dc) and 50 mA per PTX in use. Supplying less than 9 V (dc) to the transducer will result in inaccurate measurements. NOTICE Supplying more than 28 V (dc) can result in damage to the transducer. Hazardous Location Power Supply When used in hazardous locations, a properly rated power supply must be used. The intrinsically safe PTX can be powered by any power supply identified as an intrinsically safe associated apparatus with output parameters of Voc ≤ 28 V (dc) and Isc ≤ 1 A. WARNING A voltage higher than 28 V (dc) is outside the product’s safety rating. Using a voltage outside the safety rating could result in an explosion. Interface Cable Cable Length In non-hazardous locations, cable length is limited by the voltage drop for the power supply and the added noise on the pressure and temperature signal lines. It is recommended that transducer cables not exceed 100 ft (30.4 m) in length in order to minimize these effects. Hazardous Location Cable Length The wire length between intrinsically safe equipment and associated apparatuses is determined by the interaction of the device entity parameters, as described in the following table. The parameter symbols and subscripts are defined in ATEX standards EN 60079-0 and EN 60079-11. Parameter Intrinsically Safe Equipment Must Be Associated Apparatus (ex. power source) Voltage Vmax (or Ui) ≥ Voc (or Vt or Uo) Current Imax (or Ii) ≥ Isc (or It or lo) Power Pmax (or Pi) ≥ Po Capacitance Ci + Ccable ≤ Ca (or Co) Inductance Li + Lcable ≤ La (or Lo) The cable between the two devices has a capacitance and inductance that must be added to that of the intrinsically safe equipment parameter. Once the entity parameters of the devices are known the maximum cable length can be calculated. Where available, the manufacturer’s specification for the cable’s capacitance and inductance can be used. When the cable capacitance and inductance per foot are not known the following values must be used: • Ccable= 60 pF/ft • Lcable = 0.2 μH/ft The ATEX standards define additional safety factor rules that can apply when determining the maximum cable length. These do not apply in this case because the PTX has a capacitance (Ci) and inductance (Li) of zero. 9 10 Instrinsically Safe PTX User’s Manual Example Here is an example of using these parameters to determine the cable length. 1. Construct the entity parameter table for the known values: Intrinsically Safe Equipment (Swagelok PTX) Associated Apparatus (Power Supply) Vmax 28 V ≥ 9.5 V Voc Imax 1A ≥ 1A Isc Pmax - ≥ - Po Ci + Ccable 0 µF + Ccable ≤ 0.5 μF Ca Li + Lcable 0 µH + Lcable ≤ 8 μH La The entity parameters Pmax and Po can be ignored if the voltage and current parameters are compatible. 2. Calculate the maximum allowable cable capacitance and inductance. Ccable,max = 0.5 µF − 0 µF = 0.5 µF Lcable,max = 8 µH − 0 H=8 µH 3. Calculate the maximum cable lengths using the maximum allowable capacitance and inductance. Length related to maximum capacitance = Ccable,max / Ccable/length =0.5 µF / 60 pF/ft = 8 333 ft (2 539 m) Length related to maximum inductance = Lcable,max / Lcable/length = 8 µH / 0.2 µH/ft = 40 ft (12.1 m) The entity parameters will vary from one piece of apparatus to the next so the calculation must be done for each piece of apparatus in use. Cable Bend Radius The cable bend radius will vary according to the cable manufacturer’s recommendations. A bend radius of 6 to 10 times the diameter of the cable is typical. Wiring Diagram The cables for the intrinsically safe PTX should be wired in accordance with Article 504 of the National Electrical Code (ANSI/NFPA 70). The connector for the PTX is a standard male DB-9. The cable will be a socket DB-9 with the pinout as described below. 1 GND 2 7 3 Temperature Output 6 8 4 5 9 Fig. 5 Wiring Diagram Power Input Pressure Output Instriniscally Safe PTX User’s Manual It is recommended the parameter measurement wires have their own connection to ground. A cable with three shielded, twisted pair is optimal to achieve this, as shown in Figure 6. This will ensure that the voltage drop which occurs with the flow of the operating current across the cable does not distort the temperature and pressure measurements. V+ Pin 3 V- Pin 2 Pressure + Pin 8 Pressure - Pin 6 Temperature + Pin 9 Temperature - Pin 7 Fig. 6 Parameter Measurement Wire Setup 1. Install the PTX into your system, see Mounting. 2. Connect the interface cable to the PTX and the network device. 11 Maintenance Additional assembly hardware for the MPC surface mount is available. Refer to Modular Platform Components (MPC), MS‑02-185, for ordering information. There are no field-maintainable parts within the intrinsically safe PTX. Contact your authorized Swagelok representative for assistance. NOTICE Removal of the PTX enclosure screws will void the product warranty, damage the Ingress Protection rating, and negate the intrinsically safe hazardous location rating of the PTX. Troubleshooting Problem Possible Cause Remedy Power LED Off No power applied to the device. Connect power. Green Normal operation. No action needed. Sensor LED If the Power LED is also OFF, indicates no power applied to the device. Connect power. If the Power LED is on, indicates sensor element failure. Replace PTX unit. Normal operation. No action needed. Off Green General Output signal unchanged after change in pressure Mechanical overload through overpressure Replace PTX unit. Signal value too small Diaphragm is damaged, e.g. through impact. Replace PTX unit. Signal value dropping off / too smalll Abrasive/aggressive media; corrosion of diaphragm/ pressure connector; transmission fluid missing Replace PTX unit. Electromagnetic interference source in the vicinity Shield the transducer and the cables. Remove the interference source. Working temperature too high / too low Ensure temperatures within range of the transducer (see Specifications). Working temperature too high / too low Ensure temperatures within range of the transducer (see Specifications). Cable break Check connections and cable. Incorrect wiring or supply voltage Check wiring and supply voltage. Signal value erratic Signal value incorrect No output signal Contact your authorized Swagelok representative for additional assistance. Warranty Information Swagelok products are backed by The Swagelok Limited Lifetime Warranty. For a copy, visit swagelok.com or contact your authorized Swagelok representative. Each product catalog and user manual is up to date at the time of printing; subsequent revisions to individual product catalogs and user manuals will be posted to www.swagelok.com and will supersede the printed version. Swagelok, ICM—TM Swagelok Company UL, cUL—TM UL LLC © 2015 Swagelok Company Printed in U.S.A. January 2015, R0 MS-13-229