Download WINDY BOY 5000A / 6000A
Transcript
SMA Solar Technology AG Commissioning 6.3.2 Completion of the Self-test Note the values which are displayed during the self-test. These values must be entered in a test report. The results of each test test are displayed 3 times, one after the other. The respective message is displayed for 10 seconds. In the self-test, the upper and lower disconnection thresholds for each protective function are adjusted on a linear basis with a variation of 0.05 Hz/s and 0.05 Vn/s for frequency and voltage monitoring. As soon as the actual measured value goes outside the permitted range (adjusted disconnection threshold), the inverter disconnects from the power distribution grid. Thus, the inverter determines the reaction time and performs the self-test. Overvoltage Test The inverter begins with the overvoltage test. During the test sequence, the voltage limit applied is shown in the display of the inverter. The voltage is reduced step by step until the disconnection threshold is reached and the inverter disconnects from the power distribution grid. Once the inverter has disconnected from the power distribution grid, the display successively shows the following values: • Disconnection value, • Calibration value, • Reaction time, • Current line voltage. Installation Manual WB5A_6A-IA-IEN114540 51