Chapter 7 Communications 7-7 Communications Error Codes The Inverter will detect a communications error if normal communications fail or a message data error occurs. The Inverter returns a response that consists of the Slave address, function code with the MSB set to 1, error code, and CRC-16 check block when the communications error is detected. When the Master receives an error code, refer to the following table for troubleshooting and remedying the error. H Errors and Remedies Error code 01 Hex Name Function code error 02 Hex Register number error 03 Hex Data number error 21 Hex Data setting error Probable cause Remedy The function code is set to a code other than 03, 08, or 10 Hex. The specified register number has not been registered. An attempt was made to read the register of the Enter command. The number of write or read registers is not within a range from 1 to 16 (0001 and 0010 Hex). The number of registers of the DSR message multiplied by two does not coincide with the number of bytes of the attached data. The write data is not within the permissible range. The data set is illegal and causes an OPE (OPE1 through OPE9) error. Check and correct the function code. Check and correct the register number. Check and correct the number of registers or the number of bytes. Check the display on the Digital Operator and correct the data. 7-27