Actual signals and parameters 229
All parameters
No.
Name/Value
Description
Def/FbEq
TIMED FUNC 3 See selection TIMED FUNC 1.
11
TIMED FUNC 4 See selection TIMED FUNC 1.
12
DI1(INV)
Inverted digital input DI1. 0 = active, 1 = inactive.
-1
DI2(INV)
See selection DI1(INV).
-2
DI3(INV)
See selection DI1(INV).
-3
DI4(INV)
See selection DI1(INV).
-4
DI5(INV)
See selection DI1(INV).
-5
Defines the offset for the external PID controller output.
When PID controller is activated, controller output starts
from the offset value. When PID controller is deactivated,
controller output is reset to the offset value.
Parameter 4230 TRIM MODE must be set to NOT SEL.
0.0%
4229 OFFSET
0.0…100.0%
4230 TRIM MODE
NOT SEL
Value in percent
1 = 0.1%
Activates the trim function and selects between the direct
and proportional trimming. With trimming it is possible to
combine a corrective factor to the drive reference. See
section Reference trimming on page 119.
NOT SEL
No trim function selected
0
PROPORTION Active. The trimming factor is proportional to the rpm/Hz
AL
reference before trimming (REF1).
1
DIRECT
2
4231 TRIM SCALE
Active. The trimming factor is relative to a fixed maximum
limit used in the reference control loop (maximum speed,
frequency or torque).
Defines the multiplier for the trimming function. See section 0.0%
Reference trimming on page 119.
-100.0…100.0% Multiplier
1 = 0.1%
4232 CORRECTION Selects the trim reference. See section Reference trimming PID2REF
SRC
on page 119.
PID2REF
PID2OUTPUT
PID2 reference selected by parameter 4210 (ie signal 0129 1
PID 2 SETPNT value)
PID2 output, ie signal 0127 PID 2 OUTPUT value
2
44 PUMP
PROTECTION
Set-up of pump protection.
4401 INLET PROT
CTRL
Enables, and selects the mode of, the primary supervision
of pump/fan inlet pressure.
Note: Inlet protection is active only when the active
reference is PID.
NOT SEL
NOT SEL
Primary inlet pressure supervision not used
0
ALARM
Detection of low inlet pressure generates an alarm on the
control panel display.
1
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]