Download Pre-Installation
Transcript
Wire Terminations Control Interface Wiring – Drive Terminal Block TB3 Control interface inputs are connected to terminal Block TB3. TB3 is located on the Control Interface Board installed in the drive. All 1336 PLUS II Configured Drives come with a 115V AC Control Interface Card (Option L6) unless otherwise specified. 24V AC/DC control and Contact Closure control are available as options. Encoder feedback is available as an option with any of the three control methods. All control interface cards provide input terminals for access to fixed drive functions that include start, stop, and enable. Four additional inputs are programmed for functions such as reverse, preset speed access, jog, second accel/decel time access and local control selection. The function of each input is defined through programming. For Configured Drives, functions are pre-programmed at the factory for a specific application and configuration and should not require field re-programming. A variety of combinations made up of the following inputs are available. Control Interface Options 115V 24V TTL • Start • 2 Accel/Decel Rates • 2 Stop Mode Selects AC AC/DC Contact • Stop/Clear Fault • 3 Speed Selects • Run Forward Without Encoder • Reverse • Enable • Run Reverse Std. -L5C -L4C Feedback • Digital Potentiometer (MOP) • Auxiliary • Local Control With Encoder -L9EC -L8EC -L7EC Feedback ATTENTION: The drive is intended to be controlled by control input signals that will start and stop the motor. A device that routinely disconnects then reapplies line power to the drive for the purpose of starting and stopping the motor is not recommended. If this type of circuit is used, a maximum of 3 stops in any 5-minute period with a minimum 1-minute rest between each cycle is required. These 5-minute periods must be separated by 10-minute rest cycles to allow the drive precharge resistors to cool. Refer to codes and standards applicable to your particular system for specific requirements and additional information. Start 1 Stop/Fault Reset Common Reverse Jog Auxiliary Common Speed Select 3 Speed Select 2 Speed Select 1 Common Enable Encoder B Encoder NOT A Encoder NOT B Encoder A +12V (200mA Maximum) Encoder Common ATTENTION: User remote speed reference signals are terminated to logic common at TB2 terminals 3 & 4. This puts the negative or common side of these signals at earth ground potential. Control schemes should be examined for possible conflict with this grounding scheme and possible equipment damage. 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 INCLUDED ONLY ON L7EC, L8EC & L9EC OPTIONS The maximum and minimum wire size accepted by TB3 is 2.1 and 0.30 mm2 (14 and 22 AWG). Maximum torque for all terminals is 1.36 N-m (12 lb-in). 1 Configured drives will generally be factory programmed for the control scheme shown (Parameter 241 set to 2, which is a 3-wire control), and all other inputs set to default. Refer to publication 1336 PLUS-5.3 for further information. 104