7 Troubleshooting Cooling air outlet too high / High dew point Condenser dirty No Yes Overload protector (SK/HT) tripped Yes Ambient temperature over 122°F (50°C) Clean condenser Reduce temperature Yes Clean condenser Yes Fan does not work Yes Repair fan Reduce compressed air quantity or air temperature No Yes Compressor components perished Yes Repair fan No Low current consumption No English Yes Condenser dirty No High refrigerant discharge pressure High pressure drop on air side Heat exchanger fouled No with debris Ice formation on evaporator (low evaporation pressure) Insufficient refrigerant: repair any leaks and recharge the circuit Repair or replace compressor Yes Fan does not work No Compressor winding insulation partially perished (compressor too hot) Fan pressure switch (PV) calibration error or damaged Yes Yes Yes No Excessive thermal load (compressor head too hot) Excessive current consumption Compressor noisy No REMEDY CAUSE FAULT Clean heat exchanger (blow compressed air in opposite direction to operating air flow). Fit/renew prefilter Replace pressure switch Yes Clean condenser By-pass air flow keeping air inlet open. Open condensate drain valve manually. Restart appliance checking setting of expansion valve. Yes No Condenser dirty No Fan does not work Replace fan No No Seek external assistance SPE004-062 5/6