Operating Modes SMA Solar Technology AG 3.4.6 The yellow LED blinks 4 times The yellow fault LED lights up for 5 seconds when the fault occurs, and then starts emitting the following blink code. 3 seconds off and then 4 brief consecutive blinks. This code is emitted 3 times in succession. If this fault is still present, the fault signal starts over again. This code can be caused by either of the following: • Input voltage has exceeded the maximal permissible limit. or • Error in the generator (only applies to SMC 9000TL(RP)-10, 10000TL(RP)-10, 11000TL(RP)-10). Input voltage has exceeded the maximal permissible limit. The voltage of the PV generator has exceeded the inverter's permissible input voltage. NOTICE! DC input voltage too high. Destruction of the inverter. • Please contact your installer, who will immediately disconnect the PV generator from the inverter and check the DC voltage, as described in the inverter installation guide. Error in the Generator In the inverter models Sunny Mini Central 9000TL / 10000TL / 11000TL (with Reactive Power Control) this blink code can occur in combination with the display warning <Disturbance Earthfault>. This signifies that the insulation resistance in the generator is too low. Correction of error by installer Please contact your installer to have the error corrected. 20 SB_SMC-BEN092840 User Manual