PVI 10kW / PVI 13kW / PVI 15kW
Installation and Operation Manual
Input DC (PV) specifications for PVI 10KW / PVI 13KW / PVI 15KW inverter
Inverter Model
PVI 10KW
PVI 13KW
PVI 15KW
Operating Voltage Range (Power)
205-430
205-430
205-430
VDC
Input voltage MPP range
205-385
205-380
205-380
VDC
CEC full power range
235-380
235-380
235-380
VDC
Maximum open circuit voltage
(under all conditions)
475
475
475
VDC
Maximum input current
52
69
77
ADC
Maximum input power
(inverter limited)
10.6
14
16
kW DC
Maximum recommended
12
15-16
16-18
kW DC
PV power (modules @ STC)
(for 0-5 deg flat roof)
13
17
19
kW DC
DC disconnect for PV positive (+)
included
included
included
Ground fault protection
per UL 1741/2005 NEC 690.5
Ground fault detection, must detect
0.75
0.75
0.75
A
Ground fault interrupt
0.75
0.75
0.75
A
Output to AC grid connection:
The PVI 10KW / PVI 13KW / PVI 15KW is designed to feed power into a standard 60Hz, 3-phase
600V AC utility service or AC provided within a facility by a step down transformer of not less than
15kVA. As required by local codes, there must be a dedicated 3-phase circuit breaker for the PV
inverter connection.
600 VAC
PVI 10KW
30 A
PVI 13KW
30 A
PVI 15KW
30 A
600 VAC
PVI 10KW
528-660 V
PVI 13KW
528-660 V
PVI 15KW
528-660 V
DOCR-060001 rev2
31