DELAY SWITCH SETTING
TIME DELAY
0
0 seconds
1
2 seconds
2
4 seconds
3
6 seconds
4
8 seconds
5
10 seconds
6
15 seconds
7
20 seconds
8&9
Not used and
act as 0
seconds.
The delay is always to enter the alarm condition (failsafe relay de-energized, alarm indicator off).
If the Relay Action switch is set to High, the delay is applied to de-energize the failsafe relay as
the level rises above the High Alarm Point. If the Relay Action switch is set to Low, the delay is
applied to de-energize the failsafe relay as the level drops below the Low Alarm point.
3. SENSITIVITY SETTING. This has already been described in section 3.4. It is primarily used for
horizontal probes, proximity sensors, or Dry Pump monitors. The switch setting is used to add to
or subtract from the calibrated level value to add more immunity from noise and also to allow
calibration to be performed without the level being at the desired alarm point. See the
applications section for more details. Typical applications use a sensitivity setting of 1
THIS COMPLETES THE SETUP AND CALIBRATION PROCEDURE
FOR THE 9820 LEVEL SWITCH