Download 6 - Efes otomasyon
Transcript
E6581381 6.17.16 Evasion from Overvoltage and Imput phase failure : Power supply compensation filter : Inhibitor filter : Inhibitor gain : Power supply adjustment gain • 6 Function When connecting input reactor or voltage regulator or the impedance of power supply is too big, the following phenomenon are happened. •Overvoltage trip (, , ) •Input phase failure () •Unusual noise of inverter If these phenomena are occurred, the following parameters~ should be adjusted. When the using machine has specific resonance, the following phenomena are happened. ·Vibration of machine. ·Unusual noise of machine or Peripheral If these phenomena are occurred, the following parameters, should be adjusted. [Parameter setting] Title Function Adjustment range Default setting Power supply compensation filter 0-9999 (µs) 0 Inhibitor filter 0-9999 (µs) 442 Inhibitor gain 0.0– 300.0 (%) Power supply adjustment gain 0.0~2.0 100.0 0.0 At first, please set as 442 and over. Next, set and as bigger value when no effect by setting as 1000 and over. At first, please set F484 as 0.5. Next, F484 as another value when no effect by setting F484 as 0.5. Please set f481 as following value. Power supply frequency is 50Hz: 531 Power supply frequency is 60Hz: 442 Note f481~f483 are invalid, when f484 has a value excluding 0.0. F-70