Download Circuit-Breakers/Non-Automatic Circuit

Transcript
Circuit-Breakers up to 3200 A, Discontinued Series
Accessories/spare parts
■ Selection and ordering data
For fixed-mounted and withdrawable circuit-breakers
Current transformers for neutral conductor overload protection and ground-fault protection
Only one of the two measuring methods is permissible in conjunction with the electronic trip unit. The overload protection for the neutral conductor takes effect when the current transformer is fitted in the neutral conductor. The ground-fault current is calculated by means of summation current formation of the phases and the neutral conductor. In the case of electronic trip unit version P, overload protection in the
neutral conductor is achievable with 4 transformers (in L1, L2, L3, N) and ground-fault protection by summation current formation, or with a
5th transformer in the neutral point direct measurement of the ground-fault current and overload protection in the neutral conductor (without
summation current formation).
Type of detection (see Page 5/88)
Designation
Electronic trip
unit version
Primary
rated current
of the
transformer
5th and 9th positions of
Order No. for
circuit-breaker
[email protected][email protected]....
Required DT
order
quantity
per circuitbreaker
For 1 set
or 1 unit
PS*
Order No.
Weight
per PU
approx.
kg
Vectorial summation with current
transformer in the neutral conductor
Current transformers for
3-pole circuit-breakers
C, D, E,
H, J
5
For 4-pole circuit-breakers
N, P
the fourth current transformer is fitted
internally. If electronic trip unit version
E is chosen for 4-pole circuit-breakers, the fourth current transformer
must be mounted externally and be
selected from the table opposite.
315 A
400 A
500 A
630 A
0
0
0
0
A
B
C
D
1 unit
C
C
C
C
3WX36 43–1CA00
3WX36 43–1CB00
3WX36 43–1CC00
3WX36 43–1CD00
1 unit
1 unit
1 unit
1 unit
on req.
on req.
on req.
on req.
315 A
1000 A
1250 A
1600 A
1
2
3
4
E
F
G
H
1 unit
C
C
C
C
3WX36 43–1CE00
3WX36 43–1CF00
3WX36 43–1CG00
3WX36 43–1CH00
1 unit
1 unit
1 unit
1 unit
on req.
on req.
on req.
on req.
1250 A
1600 A
2000 A
2500 A
3200 A
5
5
5
6
7
G
H
J
K
M
1 unit
C
C
C
C
C
3WX36 43–1FG00
3WX36 43–1FH00
3WX36 43–1FJ00
3WX36 43–1FK00
3WX36 43–1FM00
1 unit
1 unit
1 unit
1 unit
1 unit
on req.
on req.
on req.
on req.
on req.
630 A
800 A
1000 A
1250 A
1600 A
0
1
2
3
4
D
E
F
G
H
1 unit
C
3WX36 43–2BA00
1 unit
3.000
2000 A
2500 A
3200 A
5
6
7
J
K
M
1 unit
C
3WX36 43–2FA00
1 unit
3.000
315 A
400 A
500 A
630 A
0
0
0
0
A
B
C
D
1 unit
C
C
C
C
3WX36 43–1CA00
3WX36 43–1CB00
3WX36 43–1CC00
3WX36 43–1CD00
1 unit
1 unit
1 unit
1 unit
on req.
on req.
on req.
on req.
800 A
1000 A
1250 A
1600 A
1
2
3
4
E
F
G
H
1 unit
C
C
C
C
3WX36 43–1CE00
3WX36 43–1CF00
3WX36 43–1CG00
3WX36 43–1CH00
1 unit
1 unit
1 unit
1 unit
on req.
on req.
on req.
on req.
1250 A
1600 A
2000 A
2500 A
3200 A
5
5
5
6
7
G
H
J
K
M
1 unit
C
C
C
C
C
3WX36 43–1FG00
3WX36 43–1FH00
3WX36 43–1FJ00
3WX36 43–1FK00
3WX36 43–1FM00
1 unit
1 unit
1 unit
1 unit
1 unit
on req.
on req.
on req.
on req.
on req.
Direct detection of ground-fault
current by means of a current
transformer in the grounded neutral point of the transformer.
Current transformers for 3- and
4-pole circuit-breakers
td
test
C, E, P, J
(3-pole);
E, P, J
(4-pole)
Designation
Rated control supply voltage/
rated operational voltage
AC 50/60 Hz
DC
Storage device
for shunt release
Rated control supply voltage must
match the rated control supply voltage of the shunt release
110–127 V
220–240 V
110–115 V
220–250 V
Function tester
for electronic trip unit
for version B, C, D, E, F, G, V, N, P
110–127/220–240 V –
Order
quantity
For 1 set
or 1 unit
1 unit
D
D
3WX31 56–1JG01
3WX31 56–1JJ01
1 unit
1 unit
0.500
0.500
1 unit
A
3WX36 47–5JA01
1 unit
1.300
Transfer control device
for automatic switchover
between two fixed-mounted or
withdrawable circuit-breakers
(see Page 5/95)
1 unit
D
3WX36 66–7JA00
1 unit
11.400
Door sealing frame
1 unit
A
3WX36 86–0JA00
1 unit
1.000
Also suitable for electronic trip units of
3WN1 and 3WS1 circuit-breakers
5/108
Siemens LV 30 · 2004