6.3.6 Manual valve positioning from the supervisor PMP EEV - ADV Enable manual positioning of the expansion valve Code UOM PMP Min - 0 Max 1 Def. - This is used to enable/disable the positioning of the valve, cancelling the activation of any control function or alarm. • PMP = 0: manual positioning disabled • PMP = 1: manual positioning enabled PMu EEV - ADV Manual valve position Code UOM PMu Min - 0 Max 600 Def. - If manual positioning is enabled, this is used to set the manual opening of the electronic valve. The value is expressed in steps for stepper valves, and as a % for PWM valves. PF EEV - ADV Valve opening steps Code PF UOM - Description Absolute valve position Min Max 480 0 ENGLISH 6.3.7 Read-only status variables Def. - Status variable that only displays, solely from the supervisor, the current position of the electronic valve calculated by the controller. System malfunctions may cause this value to be different from the effective position of the valve. Not used with PWM valves. SH Superheat (Parameters modified from version 2.0) Code UOM Po1 K Description Superheat Min Max - - Def. - Status variable that only displays of the superheat value calculated by MPXPRO and used to control of the valve. PPU Valve opening percentage (Parameters modified from version 2.0) Code PPU UOM % Description Valve opening as a percentage Min - Max - Def. - Status variable that only displays the electronic valve opening as a percentage. tGS Superheated gas temperature (Parameters modified from version 2.0) Code tGS UOM °C/°F Description Evaporator outlet temperature Min - Max - Def. - A@ /Fd - /FE: Assign advanced probe functions, p. 37 Status variable that only displays the evaporator outlet temperature read by the corresponding probe (advanced parameter /Fd). tEu Saturated evaporation temperature (Parameters modified from version 2.0) Code tEu UOM °C/°F Description Saturated evaporation temperature Min - Max - Def. - Status variable that only displays the saturated evaporation temperature calculated by the corresponding evaporation pressure probe or read directly by the NTC probe (advanced parameter /FE). Po6 EEV – ADV PWM expansion valve Ton +Toff Code UOM Min Max Def. Po6 s 1 20 6 This represents the period of modulation (in seconds) for the PWM expansion electronic valve (DC/AC) only. The opening of the PWM valve is controlled based on the same PID parameters, and refers to the period Po6 (in seconds) and not the 480 steps representing the maximum opening of the stepper valve. All the comments made for the stepper valve can thus be applied to the PWM valve, considering these differences. 6.3.8 Power failure The electronic valve requires a power supply to be able to open or close. In the event of power failures, it remains in the current position. Consequently a solenoid valve is required, upstream of each individual evaporator or master-slave network, to close the circuit and ensure the safety of the installation in the event of mains power failures. For further information, see the instruction sheet on the electronic valve (code +050000340). Alternatively, a backup battery can be installed that provides power for enough time to close the valve. When next restarted, the system is automatically rebooted and resumes normal control. 6.4 Compressor This section describe the advanced settings that are useful if MPXPRO is used in non-centralised systems, that is, where the compressor operating times are managed to avoid sudden starts/stops that may cause damage. In this section, the compressor/control output is assumed to be connected directly to a compressor. “MPXPRO” +030220186 - rel. 2.0 - 07.02.2008 51