1. Press menu  control  Turn To Bypass YES on the operator control and display panel for
manually turn off the inverters, and the UPS transfers to bypass mode.
2. Turn on main switch and off maintenance bypass switch.
3. Two minutes later, remove the fixing screws on both sides of the front panel of the module
and pull the module out from the cabinet.
4. After servicing the module, push the module into the cabinet and tighten the screws on both
sides.
5. Turn on maintenance bypass switch and off main switch.
6. Wait for two seconds. Press menu control  system turn on YES on the operator control
and display panel for two seconds to manually turn on the inverter mode.