UofA Lighting Design Guidelines and Standards
6.1.3
[53]
Final Draft /October 2009
Compact Fluorescent Luminaires
.1
Recessed Downlights (Vertical Orientation)
All CF Source luminaires used must be able to effectively dissipate with the heat
given off by a single compact fluorescent lamp to ensure that excessive heat does
not diminish the lifespan of the lamp or result in lamp socket degradation from
overheating. Heat tests must be performed and documented to confirm the ballast
operates minimum 20°C below the maximum design temperature. Only vertical
lamp luminaires shall be accepted for new installations. Downlights with a square
shaped openings are prohibited from use on University projects. Luminaire
aperature diameters shall not be less than 7” for photometric efficiency and for
maintenance purposes all recesses luminaires regardless of the type shall be
physicall secured to the ceiling structure with metal wire, screws or straps to
prevent movement during lamp change and maintenace. No luminaires shall be
allowed to rest on T-Bar ceiling tiles.
Figure 14 - Recessed Downlights (Vertical Orientation)
Description:
Triple tube compact fluorescent recessed
downlight, vertical orientation, specular
aluminium reflector with high efficiency
electronic ballast. 13 or 18W Quadtube
downlight versions may also be used.
Approved Manufacturer(s):
Portfolio
Model Type(s): C7032/C7042
See Appendix D for list of alternate
manufacturers and part numbers.
Last printed 20/10/2009 9:50:00 AM
Comment: This is a Semi-Final Document and is Posted for Information Only (April 2010)
45
Page 53 of Total 98 Pages