Download D5040 - Facilities and Operations
Transcript
Note: Information Contained in this Document is Currently Undergoing Revision - Contact U of A Design & Technical Services to Review Any Issues Observed UofA Lighting Design Guidelines and Standards 6.1.3 [53] Final Draft /October 2009 Compact Fluorescent Luminaires .1 Recessed Downlights (Vertical Orientation) All CF Source luminaires used must be able to effectively dissipate with the heat given off by a single compact fluorescent lamp to ensure that excessive heat does not diminish the lifespan of the lamp or result in lamp socket degradation from overheating. Heat tests must be performed and documented to confirm the ballast operates minimum 20°C below the maximum design temperature. Only vertical lamp luminaires shall be accepted for new installations. Downlights with a square shaped openings are prohibited from use on University projects. Luminaire aperature diameters shall not be less than 7” for photometric efficiency and for maintenance purposes all recesses luminaires regardless of the type shall be physicall secured to the ceiling structure with metal wire, screws or straps to prevent movement during lamp change and maintenace. No luminaires shall be allowed to rest on T-Bar ceiling tiles. Figure 14 - Recessed Downlights (Vertical Orientation) Description: Triple tube compact fluorescent recessed downlight, vertical orientation, specular aluminium reflector with high efficiency electronic ballast. 13 or 18W Quadtube downlight versions may also be used. Approved Manufacturer(s): Portfolio Model Type(s): C7032/C7042 See Appendix D for list of alternate manufacturers and part numbers. Last printed 20/10/2009 9:50:00 AM Comment: This is a Semi-Final Document and is Posted for Information Only (April 2010) 45 Page 53 of Total 98 Pages