Section 12 – Troubleshooting CFP33 Series Page 12-83 Engine Overspeed Trip NOTE: An engine overspeed trip occurs when the engine’s speed exceeds the value specified on the Factory setting Tag described in Section 2. The trip isolates the fuel supply to the engine and it stops immediately. The trip is indicated on the local control panel and inside the local control panel on the speed switch. Additionally, a trip output is supplied to the fire protection system for remote display. Cause Correction Engine actually operated at too great a speed due to catastrophic load failure such as pipe break, pump mechanical failure, or loss of suction. Correct the cause of the load failure. Engine actually operated at too great a speed due to configuration error. Check rated speed setting as specified on the Factory Setting Tag described in Section 2. Refer to Rated Speed Setpoint Adjustment and Testing in Section 3. Overspeed switch is set at too low a setpoint. Check overspeed speed setting as specified on the Factory Setting Tag described in Section 2. Refer to Overspeed Setpoint Adjustment and Testing in Section 3. Speed switch wiring failure has occurred. Check continuity and insulation from ground for the signal power wiring and ground wiring to the speed switch. Refer to Drawing 10423 Sheet 1 in Section 13. Replace defective components and repair electrical faults. Speed switch failure has occurred. If the speed switch fails to operate as per Overspeed Setpoint Adjustment and Testing in Section 3, replace the speed switch. Refer to Overspeed Switch Removal/Installation in Section 7. Contact an Authorized Cummins Repair Facility. Drawing No. 9774, Section 12, Rev. 02-07