3 Parameter setting
3.1 Operating principles
3 Parameter setting
3.1 Operating principles
You can adapt the soft starter to your application by setting appropriate
parameters. The possible settings are defined in parameters.
The devices are assigned parameters either via the potentiometers on the
front of the device, or with DS7 soft starters of SmartWire-DT version, via
the interface.
→
Only the standard versions (DS7-340… and DS7-342…) are
described below.
The DS7-34D… communication-enabled version is described in
a separate document.
3.2 Factory settings of the basic device
The soft starters of the DS7 series are factory set so that no settings are
required for standard applications. The following tables shows the most
important settings.
Table 7:
Factory settings DS7
terminal, function
Factory setting
1A
Start/stop
Ramp times
t-Start: ~5 s
t-Stop: 0 s
Start voltage
30 %
Relay K1
Top of Ramp
Relay K2 (for devices from 16 A)
RUN
Publication Title
07/10 MN03901001Z-EN
www.eaton.com
47