Download Advantys STB - Schneider Electric
Transcript
Advanced Configuration Features Test Mode When the NIM is operating in test mode, the NIM’s output data process image (including the RTP request block) can be controlled either by the Advantys Configuration Software or by an HMI (depending upon the test mode configured). Standard Modbus commands can be used to access the RTP words. If the NIM is in test mode, the fieldbus master cannot write to the RTP request block in the NIM’s output data process image. RTP Request Block Words Definitions The following table lists RTP request block words: Modbus Address Upper Byte Lower Byte Data Type Attribute 45130 sub-index toggle + length unsigned 16 RW 45131 index (high data byte) index (low data byte) unsigned 16 RW 45132 data byte 2 data byte 1 (LSB) unsigned 16 RW 45133 data byte 4 (MSB) data byte 3 unsigned 16 RW 45134 toggle + CMD Node ID unsigned 16 RW NOTE: The RTP request block is also presented in the manufacturer specific area of the CANopen fieldbus as an object with a dedicated index of 0x4101 and sub-index 1 to 5 (data type = unsigned 16, attribute = RW). The NIM performs range checking on the above bytes as follows: index (high / low byte): 0x2000 to 0xFFFF for write; 0x1000 to 0xFFFF for read z toggle + length: length = 1 to 4 bytes; the most significant bit contains the toggle bit z toggle + CMD: CMD = 1 to 0x0A (see the table Valid Commands, below); most significant bit contains toggle bit z Node ID: 1 to 32 and 127 (the NIM itself) z The toggle+CMD and toggle+length bytes are at either end of the RTP request register block. The NIM processes the RTP request when the same value is set in the respective toggle bits of these two bytes. The NIM processes the same RTP block again only when both values have changed to a new identical value. We recommend that you configure new matching values for the two toggle bytes (toggle+CMD and toggle+length) only after you have constructed the RTP request between them. 31004629 8/2009 125