Download - Power Logic
Transcript
Temperature Monitoring ANSI Code 38/49T Protection Functions Operation This protection is associated with a Pt100 platinum (100 Ω at 32°F or 0°C), Ni100, or Ni120 nickel type resistance temperature detector (RTD), in accordance with the IEC 60751 and DIN 43760 standards. b Picks up when the monitored temperature is greater than the Ts set point b Has two independent set points: v Alarm set point v Tripping set point b When the protection is activated, it detects whether the RTD is shorted or disconnected: v RTD shorting is detected if the measured temperature is less than -31°F (-35°C, measurement displayed “****”) v RTD disconnection is detected if the measured temperature is greater than +401°F (+205°C, measurement displayed “-****”) Note: If an RTD fault is detected, the set point output relays are blocked (the protection outputs are set to zero). Also, "RTD fault" is displayed in the control matrix and an alarm message is generated. Block Diagram MT10878 T < +401 °F RTD T > Ts1 Set Point 1 T > Ts2 Set Point 2 RTD’s Fault T > -95 °F Characteristics Ts1 and Ts2 Set Points °F °C Setting 32–356°F 0–180°C ±2.7°F ±1.5°C Accuracy (1) Resolution 1°F 1°C Pick-Up/Drop-Out Difference 3°C ±0.5° Characteristic Times Operation Time <5s (1) See Connection of MET1482 Module for accuracy derating according to the wiring cross section. © 2007 Schneider Electric. All Rights Reserved. 63230-216-208C1 33 3