Download MPPT 60-150 User Manual
Transcript
Configuring Battery Characteristics and Battery Charging Table 3-3 Custom Battery Menu Values Setting Values Default Description 12V: 10.0–16.0V 24V: 20.0–32.0V 36V: 30.0–48.0V 48V: 40.0–64.0V 60V: 50.0–72.0V 13.5V 27.0V 40.5V 54.0V 67.5V Sets the float voltage for a custom battery type. 12V: -45–0mV/degC 24V: -90–0mV/degC 36V: -135–0mV/degC 48V: -180–0mV/degC 60V: -225–0mV/degC -27mV -54mV -81mV -108mV -135mV Battery temperature compensation for a custom battery type. This setting is the reference that the BTS uses to adjust the charging voltage when the temperature falls above or below 25 °C. See “Battery Temperature Compensation”. See “Default Battery Charging Settings” on page A–2 for default settings for standard battery types. CAUTION: Equipment damage The XW SCC is incapable of determining battery type and cannot warn against or disallow incorrect settings. The settings for bulk, absorption, float and equalization charge must be checked carefully against the battery specifications. Incorrect settings may damage the battery or shorten battery life. 975-0400-01-01 3–9