Download Owner Manual - Energy Conscious
Transcript
Front Panel Display Screens and What They Mean Table 5-1 Startup Screens on GT Inverter Front Panel Display Display Duration Description Vph= 130V Clr t < 1.00s 3 seconds Vph: phase-to-neutral (rms) high threshold voltage setting, the threshold at which the inverter disconnects itself from the power grid when abnormally high phase-to-neutral AC voltage is detected. Clr t: clear time. Vpl= 107V Clr t < 2.00s 3 seconds Vpl: phase-to-neutral (rms) low threshold voltage setting, the threshold at which the inverter disconnects itself from the power grid when abnormally low phase-to-neutral AC voltage is detected. Clr t: clear time. Fh= 60.4Hz Clr t < 0.16s 3 seconds Fh: frequency high threshold setting, the threshold at which the inverter disconnects itself from the power grid when abnormally high frequency is detected. Clr t: clear time. Fl= 59.4Hz Clr t < 0.16s 3 seconds Fl: frequency low threshold setting, the threshold at which the inverter disconnects itself from the power grid when abnormally low frequency is detected. Clr t: clear time. Reconnect Delay 3 seconds Setting for the reconnect delay for the protection 305.00s timer. After a fault clears for the specified clear time, the protection timer starts counting down before the inverter attempts to deliver power to the grid. * The voltage and frequency thresholds, clear times and reconnect delay in Table 5-1 can be adjusted for multi-unit installations producing 30 kW or more (with the permission of the local utility) using GTConfigLite software. † The clear time is the total time to disconnect the output from the grid. It is the sum of the debounce time and the hardware delay time. The debounce time is the protection processor waiting time before it declares a fault. This delay is necessary to avoid nuisance trips. The protection timer begins counting down the reconnect delay during startup and the “Reconnecting in sss seconds” screen appears until the timer countdown is complete. 975-0334-01-01 5–3