Download V-Cube Installation, Operation and Maintenance
Transcript
Appendix F: Extended Dormant Unit Maintenance Procedure The following procedures must be applied to any unit which is stored for a period exceeding one month, which are required in order to maintain our warranty. Failure to comply with the procedures outlined below may result in damage and will void unit warranty. 1. Unit must be stored indoors in a clean, dry and tempered environment, heated in the winter and air cooled in the summer. Ambient air conditions should be from 50ºF to 75ºF with percentage RH from 10% to 50%. The unit needs to be stored in a warehouse (or some type of enclosure). Note that storing units outdoors is contraindicated and will void our warranty. 2. Unit must be stored on a level surface with the weight of the equipment evenly distributed through its base. The unit location must be free from excessive vibration and accidental impacts. 3. Once the unit has been unloaded in its resting location, the plastic wrapping must be removed from the unit by cutting along the corner edges in order to perform proper inspections and maintenance on the equipment. The plastic wrapping should be kept and re-applied to the unit when the unit will finally be shipped to the jobsite. 4. If applicable, a certified/qualified refrigeration technician should record refrigerant pressures on all compressors at time of storage. Each compressor must maintain refrigerant pressure in the system. 5. If applicable, a certified/qualified refrigeration technician should check refrigerant pressure in each compressor every three months. Refrigerant pressure must be maintained in the system. If zero pressure is found, this indicates a leak in the system. Leak(s) must be identified and repaired. A holding pressure must then be reinstalled. VCES-V-CUBE-IOM-1A 6. Rotate blower impellers by hand every two months; grease fan bearings as required following proper practices. Do not over grease the bearings as this may rupture the seals and lead to premature bearing failure during operation. 7. Ensure that all unit doors are kept closed. 8. Continue above maintenance schedule until unit start-up. For all checks listed above please complete the Extended Dormant Unit Maintenance Checklist below and send a copy to the Venmar CES service department every six months and when unit is put into service. If the unit has been dormant for an extended period after initial start-up, all start-up checks should be repeated before operating the unit. Refer to the V-Cube™ Start-up Report and Checklist in Appendix C and complete these checks. Failure to comply with the above recommendations may result in component failure and surface corrosion on the interior and exterior of the unit. Please note that if the unit is being stored outdoors or remains dormant for an extended period after initial startup, this may result in condensation within the unit which could result in premature degradation of the unit and potential issues within the control panel. In this event, the installation of a desiccant pouch in the control cabinet is highly recommended, all ventilation ducts should be capped/covered to prevent chimney effect, all liquid pipes (water or glycol mixture) should be drained or capped off if necessary and all peripheral electrical penetrations should be properly sealed. 44