Download IR33 uni Manual
Transcript
ENG 3.2 Keypad Pressing the button alone: • If pressed for more than 5 seconds, accesses the menu for setting the type P parameters (frequent); • Mutes the audible alarm (buzzer) and deactivates the alarm relay; • When editing the parameters, pressed for 5 s, permanently saves the new values of the parameters; • When setting the time and the on/off times returns to the complete list of parameters. Pressing together with other buttons • If pressed for more than 5 seconds together with Set, accesses the menu for setting the type C parameters (configuration); • If pressed for more than 5 seconds together with UP, resets any alarms with manual reset (the message ‘rES’ indicates the alarms have been reset); any alarm delays are reactivated; Start up • If pressed for more than 5 seconds at start up, activates the procedure for loading the default parameter values. (UP) Pressing the button alone: • Increases the value of the set point or any other selected parameter Pressing together with other buttons • If pressed for more than 5 seconds together with Prg/mute, resets any alarms with manual reset (the message ‘rES’ indicates the alarms have been reset); any alarm delays are reactivated. (DOWN) Pressing the button alone: • Decreases the value of the set point or any other selected parameter. • In normal operation accesses the display of the second probe, digital inputs and set point. Pressing the button alone: • If pressed for more than 1 second displays and/or sets the set point • Pressing together with other buttons • If pressed for more than 5 seconds together with Prg/mute, accesses the menu for setting the type C parameters (configuration). Tab. 3.b 3.3 Programming 3.3.3 The operating parameters can be modified using the front keypad. Access differs depending on the type: set point, frequently-used parameters (P) and configuration parameters (c). Access to the configuration parameters is protected by a password that prevents unwanted modifications or access by unauthorised persons. The password can be used to access and set all the control parameters. 3.3.1 Setting type P parameters Type P parameters (frequents) are indicated by a code beginning with the letter P, followed by one or two numbers. 1. Press for more than 5 seconds (if an alarm is active, the buzzer is muted), the display shows the code of the first modifiable type P parameter, P1; 2. Press or until reaching the desired parameter. When scrolling, an icon on the display shows the category the parameter belongs to (see the table below and the table of parameters); 3. Press Set to display the associated value; 4. Increase or decrease the value using or respectively, until reaching the desired value; 5. Press Set to temporarily save the new value and return to the display of the parameter code; 6. Repeat operations from 2) to 5) to set other parameters; 7. To permanently save the new values of the parameters, press for 5 s, thus exiting the parameter setting procedure. Setting set point 1 (St1) To change set point 1 (default =20°C): • press Set: the display shows St1 and then the current value of St1; • press or to reach the desired value; • press Set to confirm the new value of St1; • the display returns to the standard view. Important: • If no button is pressed for 10s, the display starts flashing, and after 1 minute automatically returns to the standard display, without saving the changes. • To increase the scrolling speed, press and hold the / button for at least 5 seconds Fig. 3.c 3.3. 2 Setting set point 2 (St2) In operating modes 6, 7, 8 and 9 (see the chapter on Functions) and when c19=2,3,4 and 7 (see the chapter on Control) the controller works with two set points. To change set point 2 (default =40 °C): • press Set: twice slowly: the display shows St2 and then the current value of St2; • press or until reaching the required value; • press Set to confirm the new value of St2; • the display returns to the standard view. Fig. 3.e Fig. 3.d ir33 universale +030220801 - rel. 2.0 - 16.04.2010 20