E5EK---DRT
7.3 Calibrating Platinum Resistance Thermometers
7.3 Calibrating Platinum Resistance Thermometers
• The calibration procedure is divided into two descriptions, one for group
1 platinum resistance thermometers (Jpt100, Pt100 : -199.9 to 650.0_C)
and group 2 platinum resistance thermometers (Pt100 : -100.0 to
100.0_C).
F Preparation
SOURCE
10
9
21 22 20
19
8
18
7
17
6
16
5
15
4
14
3
13
2
12
1
23
6-dial
11
• Use leads of the same thickness when connecting to the platinum
resistance thermometer.
• In the above figure, 6-dial refers to a precision resistance box.
• Connect (short) the leads from terminal Nos. 11 and 12.
F Calibration: platinum resistance
thermometer 1
Short terminal
Nos. 11 to 13
] is displayed, the 30-minute timer is displayed on the
(1) When [
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.
key to display [
]
(2) First, calibrate the main input. Press the
(300Ω calibration display). Set the 6-dial to 300Ω. When the value
on the No.2 display has stabilized (changes of several digits max.),
press the
key to temporarily save the calibration data.
key to switch to the [
] (0Ω calibration) display.
(3) Press the
Short terminal Nos. 11 to 13. When the value on the No.2 display
has stabilized (changes of several digits max.), press the
key to
temporarily store the calibration data.
(4) Next, calibrate the B-B’ input. Change the wiring as follows.
Make the connection across terminal Nos. 11 and 12 and the 6-dial
as short as possible. Short terminal Nos. 11 and 13.
15
Change wiring.
14
13
12
6-dial
11
Short terminal
Nos. 11 to 13
Continued on next page
(5) Press the
key to display [
] (10Ω calibration display). Set
the 6-dial to 10Ω. When the value on the No.2 display has stabilized
key to temporarily
(changes of several digits max.), press the
store the calibration data.
key to display [
] (0Ω calibration display). Short
(6) Press the
terminal Nos. 11 to 13. When the value on the No.2 display has stakey to tempobilized (changes of several digits max.), press the
rarily store the calibration data.
7--7