Download E5EK Digital Controller CompoBus/D (DeviceNet) Type User`s Manual
Transcript
E5EK---DRT 7.3 Calibrating Platinum Resistance Thermometers 7.3 Calibrating Platinum Resistance Thermometers • The calibration procedure is divided into two descriptions, one for group 1 platinum resistance thermometers (Jpt100, Pt100 : -199.9 to 650.0_C) and group 2 platinum resistance thermometers (Pt100 : -100.0 to 100.0_C). F Preparation SOURCE 10 9 21 22 20 19 8 18 7 17 6 16 5 15 4 14 3 13 2 12 1 23 6-dial 11 • Use leads of the same thickness when connecting to the platinum resistance thermometer. • In the above figure, 6-dial refers to a precision resistance box. • Connect (short) the leads from terminal Nos. 11 and 12. F Calibration: platinum resistance thermometer 1 Short terminal Nos. 11 to 13 ] is displayed, the 30-minute timer is displayed on the (1) When [ No.2 display and counts down. This timer serves as a guide for the aging time when aging is required. key to display [ ] (2) First, calibrate the main input. Press the (300Ω calibration display). Set the 6-dial to 300Ω. When the value on the No.2 display has stabilized (changes of several digits max.), press the key to temporarily save the calibration data. key to switch to the [ ] (0Ω calibration) display. (3) Press the Short terminal Nos. 11 to 13. When the value on the No.2 display has stabilized (changes of several digits max.), press the key to temporarily store the calibration data. (4) Next, calibrate the B-B’ input. Change the wiring as follows. Make the connection across terminal Nos. 11 and 12 and the 6-dial as short as possible. Short terminal Nos. 11 and 13. 15 Change wiring. 14 13 12 6-dial 11 Short terminal Nos. 11 to 13 Continued on next page (5) Press the key to display [ ] (10Ω calibration display). Set the 6-dial to 10Ω. When the value on the No.2 display has stabilized key to temporarily (changes of several digits max.), press the store the calibration data. key to display [ ] (0Ω calibration display). Short (6) Press the terminal Nos. 11 to 13. When the value on the No.2 display has stakey to tempobilized (changes of several digits max.), press the rarily store the calibration data. 7--7