9. Output/ input terminals ■ ◆Multi-functions relay setting Code No. Function Setting value Factory setting Change during operation Cd29 TIME 0~60000 5 X Cd45 Frequency detect level 0.00~400.00 0.50 X Cd47 Multi-functions relay 1 (MA、MB、MC) 0~10 1 X Cd48 Multi-functions relay 2 (M1、M2、M3) 0~10 1 X Cd49 Multi-functions relay DO 0~10 8 X Description: Set multi-functions output contactor function. Cd29 (TIME): This function must accommodate Cd47, 48=0 setting. When motor starts operation, the time counter is active. Cd45 (Frequency detect level) : accommodate Cd47, 48=6, Cd45 will appoint the action level. 1 HZ OUTPUT CD45 Time MA-MC OPEN CLOSE Time Cd47, 48 could be set the function by Multi-functions ouput contactor, please refer to the list: Setting Function 0 Time counter (accommodate Cd29) 1 Fault 2 Stop 3 Acceleration 4 Speed reached 5 Deceleration 6 Frequency reached (operation frequency>Cd45) 7 Current reached (compare to Cd85 and Cd86 value) 8 Over heating prediction action(Cd82×Cd84) 9 OL fault action 10 No action 62