1.6.D. External Maintenance Bypass (EMB) Operation (Optional)
There is an optional External Maintenance Bypass which supplies the critical load with unconditioned
input power . The purpose of this option is to route power to the critical load while the UPS’ rectifier and
inverter are de-energized, and during Start-up before the system is fully operational (refer to Figure 4).
With the External Maintenance Bypass there is a hard wired bypass that can be operated after the Static
Bypass Switch has been operated, making it possible to isolate the entire UPS for service and maintenance. The internal control system determines the operation of the normal and External Maintenance
Bypass paths, with the load powered from the inverter being the normal operation.
Figure 4 Single Line Drawings –External Maintenance Bypass Operation
Micro Emergency Lighting Inverter User’s Manual
#018-1000-01
15