Transcript
Heat Shrink MV Joints
22kV MXSU-5
Single Core Cable with Wire Shield without Armour
Catalogue
Reference
Voltage
Size Range
Diameter Conductor
Diameter Over Core
Insulation
Diameter Cable
Oversheath
kV
(mm2)
(mm)
(mm)
(mm)
MXSU-5101
22
10 - 35
3.7 - 7.5
15.0 - 22.0
17 - 33
MXSU-5111
22
25 - 95
5.2 - 12.0
17.9 - 26.0
25 - 38
MXSU-5121
22
50 - 150
7.2 - 15.0
20.2 - 29.5
28 - 41
MXSU-5131
22
95 - 240
10.3 - 19.2
23.0 - 33.6
30 - 43
MXSU-5132
22
150 - 300
12.9 - 21.6
25.0 - 35.5
33 - 48
MXSU-5141
22
240 - 400
17.8 - 24.6
29.9 - 38.8
35 - 49
MXSU-5151
22
500
25.5 - 27.6
37.2 - 41.6
48 - 54
MXSU-5161
22
630
29.0 - 32.5
39.2 - 44.7
50 - 58
MXSU-5171
22
800
32.0 - 33.8
44.8 - 46.9
58 - 61
MXSU-5181
22
1000
38.5 - 39.2
49.4 - 53.2
64 - 67
Size Transition Joints including Dual Range Mechanical Connectors
Lower Range
Catalogue
Reference
Voltage
Size Range
Diameter
Conductor
Diameter
Over Core
Insulation
kV
(mm2)
(mm)
(mm)
Upper Range
Diameter
Conductor
Diameter
Over Core
Insulation
(mm)
(mm)
Min. Diameter
Cable Over
Sheath
(mm)
MXSU-5131-T2
22
25/95 - 95/240
5.2 - 12.0
17.9 - 26.0
10.3 - 19.2
23.0 - 33.6
25
MXSU-5141-T4
22
95/240 - 240/400
10.3 - 19.2
23.0 - 33.6
17.8 - 24.6
29.9 - 38.8
30
MXSU-5151-T6
22
185/400 - 500
15.5 - 24.6
27.4 - 38.8
25.5 - 27.6
37.2 - 41.6
35
MXSU-5161-T6
22
185/400 - 630
15.5 - 24.6
27.4 - 38.8
29.0 - 32.5
39.2 - 44.7
35
MXSU-5161-T7
22
500 - 630
25.5 - 27.6
37.2 - 41.6
29.0 - 32.5
39.2 - 44.7
48
MXSU-5171-T8
22
630 - 800
29.0 - 32.5
39.2 - 44.7
32.0 - 33.8
44.8 - 46.9
50
MXSU-5181-T8
22
630 - 1000
29.0 - 32.5
39.2 - 44.7
38.5 - 39.2
49.4 - 53.2
50
3 Core Cable with Wire Shield without Armour
Diameter Conductor
Diameter Over Core
Insulation
Diameter Cable
Oversheath
Catalogue
Reference
Voltage
Size Range
kV
(mm2)
(mm)
(mm)
(mm)
MXSU-5311
22
25 - 95
5.2 - 12.0
17.9 - 26.0
48 - 72
MXSU-5321
22
50 - 150
7.2 - 15.0
20.2 - 29.5
55 - 80
MXSU-5331
22
95 - 240
10.3 - 19.2
23.0 - 33.6
62 - 89
MXSU-5332
22
150 - 300
12.9 - 21.6
25.0 - 35.5
70 - 96
MXSU-5341
22
185 - 400
14.8 - 24.6
27.0 - 38.8
76 - 105
Screened 1 Core to 3 Core Plastic Insulated Cables without Armour 12 & 24kV
Catalogue
Reference
Voltage
Size Range
Diameter Conductor
Diameter Over Core
Insulation
Diameter Cable
Oversheath
kV
(mm2)
(mm2)
(mm)
(mm)
MXSU-5311-1C
22
25 - 95
6 - 12.0
18.5 - 26.0
52.5 - 71.5
MXSU-5321-1C
22
50 - 150
7.2 - 15.0
20.2 - 29.5
55.0 - 80.0
MXSU-5331-1C
22
95 - 240
10.3 - 19.2
23 - 33.6
62.5 - 89.0
MXSU-5332-1C
22
150 - 300
12.9 - 21.6
25 - 35.5
70.0 - 96.0
MXSU-5341-1C
22
240 - 400
15.5 - 24.6
28.1 - 38.8
76.0 - 105.0
te.com/energyPage 93