Technical Information
The tables below show the various technical aspects to be taken into account at the time of installation.
Aerosol temperature and time of action
Discharge Discharge
Ref.
Model
outlets length (m)
1 FP-8
1
0.5
2 FP-20E/FP-20S
2
0.3
3 FP-40S
2
1.2
4 FP-80/FP-80S
2
2.0
4 FP-100S
1
1.0
5 FP-100S w/n
1
1.0
6 FP-200M
1
2.0
7 FP-200S
1
2.0
8 FP-200S w/n
1
1.5
9 FP-500S
1
2.5
10 FP-500S w/n
1
2.0
11 FP-1000M
2
3.0
12 FP-1200
1
3.5
13 FP-2000
1
3.5
14 FP-3000
1
4.0
15 FP-5700
1
8.0
L1
L2
L3
w/n
o
Discharge temperature ( C)
L1,(m)
L1-L2,(m)
L2-L3,(m)
0-0.1
0.1-0.2
0.2-0.3
0
0-0.1
0.1-0.2
0
0-0.1
0-0.3
0
0-0.1
0.1-0.3
0
0-0.2
0.2-0.4
0
0-0.1
0.1-0.2
0
0-0.3
0.3-1.4
0
0-0.3
0.3-1.4
0
0-0.1
0.1-0.3
0
0-0.5
0.5-1.8
0
0-0.1
0.1-0.5
0-1.0
1.0-1.5
1.5-2.5
0
0
0-1.0
0
0
0-1.0
0
0-0.5
0.5-1.5
0
0-0.5
0.5-1.5
= Distance in metres between the outlet and the point where the temperature is
= Distance in metres between the outlet and the point where the temperature is
= Distance in metres between the outlet and the point where the temperature is
= with nozzle
Discharge duration
(sec)
Min.
Max.
3
6
3
6
5
10
4
8
5
10
5
10
10
15
5
10
5
10
5
10
5
10
20
25
10
15
10
15
15
20
15
20
o
> 300 C
o
< 200 C
o
< 75 C
Important!
The distances shown under discharge length are those to be regarded as a maximum to obtain a rebound of
discharge onto the surface (such as the floor) that then guarantees a good homogeneous spread of the aerosol
in the protected compartment.
The temperatures shown under discharge temperature relate to the distances. In cases of storage of materials,
cables, sensitive parts and/or the presence of persons, prevent them from coming into contact with discharges
the heat of which is such that it can give rise to damage and/or injury.