Location Considerations
!
CAUTION
Units contain water. Water leaks can cause damage to sensitive equipment
below. Do not mount units over sensitive equipment. A field supplied pan with
drain must be installed beneath cooling units and water/glycol cooled
condensing unit.
Locate the evaporator unit over an unobstructed floor space if possible. This will allow easy access
for routine maintenance or service. Do not attach additional devices (such as smoke detectors,
etc.) to the housing, as they could interfere with the maintenance or service.
When using the optional air grille kit, avoid locating the evaporator unit in confined areas that
affect the air flow pattern. Such locations could cause short cycles, down drafts and air noise.
Avoid locating the unit in an alcove or at the extreme end of a long, narrow room. Avoid installing
multiple units close to each other. This could result in crossing air patterns, uneven loads and
competing operating modes.