Download Manual 1.7Mb pdf
Transcript
MI 3125/3125B EurotestCOMBO Line impedance 5.6 Line impedance and prospective short-circuit current / Voltage drop Line impedance is measured in loop comprising of mains voltage source and line wiring. Line impedance is covered by the requirements of the EN 61557-3 standard. The Voltage drop sub-function is intended to check that a voltage in the installation stays above acceptable levels if the highest current is flowing in the circuit. The highest current is defined as the nominal current of the circuit's fuse. The limit values are described in the standard EN 60364-5-52. Sub-functions: Z LINE- Line impedance measurement according to EN 61557-3, ΔU – Voltage drop measurement. See chapter 4.1 Function selection for instructions on key functionality. Figure 5.26: Line impedance Figure 5.27: Voltage drop Test parameters for line impedance measurement Test Selection of line impedance [Zline] or voltage drop [ΔU] sub-function FUSE type Selection of fuse type [---, NV, gG, B, C, K, D] FUSE I Rated current of selected fuse FUSE T Maximum breaking time of selected fuse Lim Minimum short circuit current for selected fuse. See Appendix A for reference fuse data. Additional test parameters for voltage drop measurement ΔUMAX Maximum voltage drop [3.0 % ÷ 9.0 %]. 45