MI 3122 Smartec Z Line-Loop / RCD
Testing RCD
5 Measurements
5.1 Testing RCDs
Various test and measurements are required for verification of RCD(s) in RCD protected
installations. Measurements are based on the EN 61557-6 standard.
The following measurements and tests (sub-functions) can be performed:
‰ Contact voltage,
‰ Trip-out time,
‰ Trip-out current,
‰ RCD autotest.
See chapter 4.1 Function selection for instructions on
key functionality.
Figure 5.1: RCD test
Test parameters for RCD test and measurement
TEST
IΔN
type
MUL
Ulim
RCD sub-function test [RCDt, RCD I, AUTO, Uc].
Rated RCD residual current sensitivity IΔN [10 mA, 30 mA, 100 mA, 300 mA,
500 mA, 1000 mA].
RCD type [ , ], test current waveform plus starting polarity [ , , , ].
Multiplication factor for test current [½, 1, 2, 5 IΔN].
Conventional touch voltage limit [25 V, 50 V].
Notes:
‰ Ulim can be selected in the Uc sub-function only.
The instrument is intended for testing of General (non-delayed) and S elective (timedelayed) RCDs, which are suited for:
‰
‰
‰
Alternating residual current (AC type, marked with
symbol),
Pulsating residual current (A type, marked with
symbol).
Time delayed RCDs have delayed response characteristics. As the contact voltage
pre-test or other RCD tests influence the time delayed RCD it takes a certain period
to recover into normal state. Therefore a time delay of 30 s is inserted before
performing trip-out test by default.