Transcript
MI 3122 Smartec Z Line-Loop / RCD Testing RCD 5 Measurements 5.1 Testing RCDs Various test and measurements are required for verification of RCD(s) in RCD protected installations. Measurements are based on the EN 61557-6 standard. The following measurements and tests (sub-functions) can be performed: Contact voltage, Trip-out time, Trip-out current, RCD autotest. See chapter 4.1 Function selection for instructions on key functionality. Figure 5.1: RCD test Test parameters for RCD test and measurement TEST IΔN type MUL Ulim RCD sub-function test [RCDt, RCD I, AUTO, Uc]. Rated RCD residual current sensitivity IΔN [10 mA, 30 mA, 100 mA, 300 mA, 500 mA, 1000 mA]. RCD type [ , ], test current waveform plus starting polarity [ , , , ]. Multiplication factor for test current [½, 1, 2, 5 IΔN]. Conventional touch voltage limit [25 V, 50 V]. Notes: Ulim can be selected in the Uc sub-function only. The instrument is intended for testing of General (non-delayed) and S elective (timedelayed) RCDs, which are suited for: Alternating residual current (AC type, marked with symbol), Pulsating residual current (A type, marked with symbol). Time delayed RCDs have delayed response characteristics. As the contact voltage pre-test or other RCD tests influence the time delayed RCD it takes a certain period to recover into normal state. Therefore a time delay of 30 s is inserted before performing trip-out test by default. 24