Download Eurotubi Pressfitting System - Technical Guide
Transcript
In water heating systems the “closed circuit” must be guaranteed, so that the oxygen is not able to be introduced from external sources. In these conditions carbon steel pipes are not subject to internal corrosion. Any small amount of oxygen that penetrates when filling, during the heating of the water, is freed and must be evacuated from the system through the vent valves. Furthermore special additives must be used, which stop oxygen from causing corrosion. However, such systems must always be kept filled, even when not operating, or should be emptied and kept dry, to avoid both air and water being in contact with the metal, a situation that can lead to corrosion. On this point, after the system has been emptied, it is worth passing forced dry air through the interior, to ensure complete drying. Resistance to bimetallic corrosion Carbon steel components can also be used in mixed installations with non-ferrous metals, such as copper, aluminum, etc. Importantly, direct contact between carbon steel and stainless steel must be avoided, as this situation may give rise to bimetallic corrosion. This risk can be reduced by inserting a non-ferrous joint between the two metals or it can be completely eliminated by using non-ferrous spacers at least 50 mm in length. It is absolutely forbidden to create systems with joints in stainless steel and carbon steel pipes, or vice versa. Resistance to external corrosion Carbon steel components present an external galvanised or hot zinc plated coating which, however, does not guarantee on its own a long lasting and effective protection from corrosion. Protection from corrosive agents must be obtained through insulation, painting or plastic coating on the pipes. In the absence of protection, a prolonged exposure to moisture, particularly for chased installations, may cause internal corrosion. It is therefore necessary to cover the pipes with a closed-cell coating or with anti-corrosion tape, making sure that no part remains uncovered or detachment areas form between the insulating material and the pipe, where condensation may generate. Felt sheathing must not be used as it holds moisture and encourages corrosion. 10.4. Carbon steel installations for sprinkler fire fighting and other applications Carbon steel does not require additional anticorrosion protection in any of the other applications foreseen for its use. Note. Please bear in mind that Eurotubi advises against using carbon steel for cooling system due to the considerable risks of corrosion induced by condensation on the cold pipes. 11.SYSTEM COMMISSIONING 11.1 Testing After installation and before covering, insulation or painting, the system must undergo testing to ensure its suitable carrying capacity and seal integrity. The test method and result must be necessarily documented in a report (see annexes 1-4 of this guide).