Download MODBUS(R)/TCP Interface Module User`s Manual
Transcript
11 TROUBLESHOOTING Error Code Error Name 734FH Request message size setting error 7351H Automatic communication function start interruption Description The request message size specified in the argument ((S2)+0) of the MBREQ instruction is incorrect. The start of the automatic communication function was interrupted due to the processing of the basic parameter setting. The automatic communication function was started or stopped without the basic parameter being set. 7352H 7353 H 7360H 7361H 7362H Basic parameter not set The automatic communication function was started when parameter setting was being made on GX Configurator-MB at power-on. MELSEC-Q Lit LED Corrective Action COM.ERR. Review the setting of the request message size. COM.ERR. After turning ON the Automatic communication parameter setting request/Automatic communication start request (Y4), do not turn ON the Basic parameter setting request (Y1) until the Automatic communication operation status (X6) turns ON. COM.ERR. Start or stop the automatic communication function with Basic parameter setting existence (X3) on. COM.ERR. When using GX Configurator-MB, switch the power on and then turn on Automatic communication parameter setting request/Automatic communication start request (Y4) after Basic parameter setting existence (X3) has turned on. COM.ERR. Delete the automatic communication parameter setting. (When mounting the QJ71MT91 on the main base unit of a redundant system, the master function cannot be used.) • Refer to the exception code returned from the target slave device, and resolve the problem. • Resolve the problem that occurred in the target slave device. Redundant setting error When the QJ71MT91 on the main base unit of a redundant system is mounted, the automatic communication function of the master function was attempted to be executed. Exception message reception When the automatic communication function or dedicated instruction is used, the target slave device returned an exception code in reply to the request message sent by the QJ71MT91. COM.ERR. Byte count error In the automatic communication function or dedicated instruction, the number of bytes in the received response message is less or more than necessary. COM.ERR. Reference number error The value of the reference number in the response message received by the dedicated instruction is incorrect. COM.ERR. 1) Occurrence 2) 3) 4) 5) On the target slave side, check whether the contents of the returned response message are correct or not. (Continued on next page) 11 - 28 11 - 28