6. Redundancy with NX3030 CPU Simple Failure with Unavailability Some components, as they aren’t doubled, don’t even tolerate a simple failure without causing some kind of unavailability. In a redundant CPU using CPU NX3030, this is related to the following components: PROFIBUS remotes (slaves) in a non-redundant PROFIBUS network Ethernet remotes (slaves) in a non-redundant network I/O Modules The failure intolerance of a non-redundant PROFIBUS network can be solved if a redundant PROFIBUS network is used, which is advisable in systems that demand a high failure tolerance. Figure 6-1 shows an example of a redundant PROFIBUS network architecture. Likewise intolerance to failure of a non-redundant Ethernet network can be solved by using a redundant Ethernet network configuration with NIC Teaming. Regarding the I/O module unavailability, it must be observed that it doesn’t imply total system unavailability. It constitutes a partial unavailability, only in the control mesh that uses this I/O module. Even though there’s no redundancy prevision for I/O modules, the user application can manage it in special cases. E.g. the user can insert 3 analog input modules in 3 different PROFIBUS remotes, and implement a vote scheme between analog inputs triples, for a critic system. However, as mentioned, such solutions must be managed by the user. There’s no automatic support for them. Such solutions, generally speaking, also imply in the field transducers and actuators redundancy. Simple Failure without Unavailability Causing a Switchover Some redundant components tolerate simple failures without causing unavailability, but do cause switchover: Racks (NX9001, NX9002 or NX9003). Power Supply (NX8000). CPUs (NX3030) NX4010 modules NX5001 modules (PROFIBUS masters) in non-redundant PROFIBUS network configuration NX5000 module (Ethernet) in configurations without NIC Teaming PROFIBUS slave interface in a redundant remote (PO5063V5, PO5065 or AL-3416). In this case, different from the previous, the switchover happens inside the remote, between the PROFIBUS A and B networks ATTENTION: In case of failure of the CPU NX3030 or NX4010 module in architectures where panel PX2612 or PROFIBUS network is not used, the CPU will remain in its current state. In this case, if the failure occurs in the half-cluster active, system downtime occurs. Double Failure without Unavailability Causing a Switchover Some components are doubled in each half-cluster, this way, before causing a switchover, both must fail: NX5001 modules (PROFIBUS masters) in redundant configuration, configured in vital failure mode. NX5000 modules (Ethernet) in configurations with NIC Teaming (redundancy managed by the user). 253