4 - Operation
EHit
Conf
Output
Configuration
Back
to operator mode
éno
bloc
é100
Ht.f.C
CT High range
(available if at least one
alarm is Htr)
10…100
éOFF
Ht.on
Back to the
1st parameter
AlM=Conf
CT decimal point
(available if at least one
alarm is Htr)
Off / On
Tab. 1 Input type
Value Description
éInp.
32…1112°F
tc. j 0…600°C
32…1112°F
tc. l 0…600°C
32…2192°F
tc. K 0…1200°C
32…2912°F
tc. s 0…1600°C
0…1600°C
32…2912°F
tc. r
-200…400°C
-328…752°F
tc. t
Custom
range
on
request
cuSt
rtd1 -200…600°C -328…1112°F
rtd2 -99.9...300.0°C -99.9…572.0°F
del.t -50.0…50.0°C -58.0…122.0°F
MU 0…50 mV
0=5 0…5 Volt
Engineering
1=5 1…5 Volt
0…10
Volt
units
0=10
0…20
mA
0=20
4=20 4…20 mA
Tab. 2 Engineering units
Value Description
éUnit
none None
°C Centigrade Degrees
°f Fahrenheit Degrees
MA mA
MU mV
U Volt
bar bar
psI PSI
rh Rh
ph Ph
Tab. 3 Setpoint type
Value Description
érs.p.C.
loc Local only
reM Remote only
l=r Local/remote only
loc.t Local - trim
reM.t Remote - trim
Tab. 4 Rem. Setpoint
Retransmission
Value Description
0=5 0…5 Volt
1=5 1…5 Volt
0=10 0…10 Volt
0=20 0…20 mA
4=20 4…20 mA
Tab. 5 Control type
Value Description
Of.re Reverse action
Of.di Direct action
pid.d Direct action
pid.r Reverse action
U.dir Direct action
U.reU Reverse action
H.C.ln Linear
H.C.Ol Oil charac.
H.C.H2 Water charac.
érs.In
éO.r.ty
éOI.ty
On - Off
P.I.D.
Modulating
valves
Heat/
Cool
Tab. 6 Heat control output
Value Description
éH.C.OP
Off Not used
rI Relay 1
Digital signal
log SSR drive
0=5 0…5 Volt
1=5 1…5 Volt
Analogue
0=10 0…10 Volt
signal
0=20 0…20 mA
4=20 4…20 mA
Tab. 7 Cool control output
Value Description
éC.C.OP
Off not used
r2 relay 2
Digital signal
log SSR drive
0=5 0…5 Volt
1=5 1…5 Volt
Analogue
0=10 0…10 Volt
signal
0=20 0…20 mA
4=20 4…20 mA
Tab. 8 Digital Inputs function
éIl1
Value Description
éIl2
Not
used
Off
l=r Local/remote
A.Man Auto/manual
s.p.1 1st stored Setpoint
s.p.2 2nd stored Setpoint
keb.I Keypad
slo.1 s.p. slope disable
H.pU Measure hold
r.=H. Run/stop of a program
Tab. 9 Alarm type
Value
Off
fs.H
fs.l
deU.H
deU.l
band
Htr
lba
éAl1 éAl2
Description
éAl3 éAl4
Not used
Active high
Absolute
Active low
Active high
Deviation
Active low
Band
Out active
Heater Break
Active high
Loop break alarm (Al1 only)
18