Download Manual - Tempatron
Transcript
4 - Operation EHit Conf Output Configuration Back to operator mode éno bloc é100 Ht.f.C CT High range (available if at least one alarm is Htr) 10…100 éOFF Ht.on Back to the 1st parameter AlM=Conf CT decimal point (available if at least one alarm is Htr) Off / On Tab. 1 Input type Value Description éInp. 32…1112°F tc. j 0…600°C 32…1112°F tc. l 0…600°C 32…2192°F tc. K 0…1200°C 32…2912°F tc. s 0…1600°C 0…1600°C 32…2912°F tc. r -200…400°C -328…752°F tc. t Custom range on request cuSt rtd1 -200…600°C -328…1112°F rtd2 -99.9...300.0°C -99.9…572.0°F del.t -50.0…50.0°C -58.0…122.0°F MU 0…50 mV 0=5 0…5 Volt Engineering 1=5 1…5 Volt 0…10 Volt units 0=10 0…20 mA 0=20 4=20 4…20 mA Tab. 2 Engineering units Value Description éUnit none None °C Centigrade Degrees °f Fahrenheit Degrees MA mA MU mV U Volt bar bar psI PSI rh Rh ph Ph Tab. 3 Setpoint type Value Description érs.p.C. loc Local only reM Remote only l=r Local/remote only loc.t Local - trim reM.t Remote - trim Tab. 4 Rem. Setpoint Retransmission Value Description 0=5 0…5 Volt 1=5 1…5 Volt 0=10 0…10 Volt 0=20 0…20 mA 4=20 4…20 mA Tab. 5 Control type Value Description Of.re Reverse action Of.di Direct action pid.d Direct action pid.r Reverse action U.dir Direct action U.reU Reverse action H.C.ln Linear H.C.Ol Oil charac. H.C.H2 Water charac. érs.In éO.r.ty éOI.ty On - Off P.I.D. Modulating valves Heat/ Cool Tab. 6 Heat control output Value Description éH.C.OP Off Not used rI Relay 1 Digital signal log SSR drive 0=5 0…5 Volt 1=5 1…5 Volt Analogue 0=10 0…10 Volt signal 0=20 0…20 mA 4=20 4…20 mA Tab. 7 Cool control output Value Description éC.C.OP Off not used r2 relay 2 Digital signal log SSR drive 0=5 0…5 Volt 1=5 1…5 Volt Analogue 0=10 0…10 Volt signal 0=20 0…20 mA 4=20 4…20 mA Tab. 8 Digital Inputs function éIl1 Value Description éIl2 Not used Off l=r Local/remote A.Man Auto/manual s.p.1 1st stored Setpoint s.p.2 2nd stored Setpoint keb.I Keypad slo.1 s.p. slope disable H.pU Measure hold r.=H. Run/stop of a program Tab. 9 Alarm type Value Off fs.H fs.l deU.H deU.l band Htr lba éAl1 éAl2 Description éAl3 éAl4 Not used Active high Absolute Active low Active high Deviation Active low Band Out active Heater Break Active high Loop break alarm (Al1 only) 18