Download Single Stage Compressor Controller User Manual
Transcript
SSCC Configuration Chapter 5 15: Anti-Surge Control General Configuration List 15 defines general properties for anti-surge control that are independent from the primary and secondary anti-surge PID loops. These general configuration properties are used for the following controls. • Anti-surge valve control value limits • Anti-surge valve slew rate limits • Ant-surge valve position deviation alarming • Anti-surge PID loop min/max selection • Anti-surge PID loop tracking The following table identifies the configuration parameters, range limits, and initial values. Table 45 - Parameter List 15: Anti-Surge Control General Configuration No. Description Range Initial Value 01 Anti-surge PID Loop Output Min/Max Select Type. Choices: 0 = Minimum select 1 = Maximum select 0 or 1 1 02 Not Running Control Value, % open. 0…100 The anti-surge valve is set to this control value whenever the compressor is “Not Running” or “Unloaded.” This value overrides the PID output values calculated by the primary or secondary antisurge PID loops. If this value exceeds the min or max CV limits expressed in parameters 7 and 8, the min/max limited value is used under the “Not Running” or “Unloaded” condition. 100 03 PID Track Margin, % Open. When both the primary and secondary anti-surge PID loops are configured, this value sets the tracking limit for the PID loop that is not producing the selected output. This keeps the noncontrolling loop from winding up and moving away from the control value by more than a PID track margin. For example, if the PID track margin is set to 10%, the select type is set to “Maximum,” the compressor is Running and Loaded, the primary PID loop output is max selected and at 60%, and the secondary PID loop output is 55% and reducing. If the secondary loop output reduces below 50% (60% - 10%) the secondary output is limited (tracks) at 50%. If the primary loop output increases to 61%, the secondary loop tracking rises to 51% (61% - 10%). 0…100 5 04 Anti-surge Valve Location. Choices 0 = Blow-Off valve 1 = Recycle Valve This setting is used to modify the representation of the anti-surge valve connections on the Process Overview page of the Operator screen. 0 or 1 1 05 Open Slew Rate, %/sec. Limits the opening rate of the control value. Normally, the anti-surge opening slew rate is set to allow fast opening. 0…999999 100 06 Close Slew Rate %/sec. Limits the closing rate of the control value. Normally, the anti-surge closing slew rate is set to close the valve slowly. 0…999999 2 07 Control Value Max Limit % Open. Sets the max limit for the control value for the valve. 0…100 100 Rockwell Automation Publication 1711-UM002A-EN-P - September 2012 User-configured Value 69