Download User Guide - ACS Group

Transcript
Pressure Switch
With the unit running, program a set point of 30ºF (-1ºC). Allow the process
temperature to drop under 100ºF (38ºC). When the process temperature reaches that
point, turn off the water supply. The pump should stop and the Low Water Pressure
indicator should illuminate. Turn the water supply on to reset the pressure switch.
Adjusting the Pressure Switch
The pressure switch used in your Water Temperature Control Unit is factory set at 16
psig (110.3 kPa/1.1 bars). However, if the process does not require the unit to operate at
250ºF (121ºC), you can adjust the switch to meet your process needs.
Tools Required
•
5/64 (#8) Hex Key
HAZARDOUS ELECTRICAL CURRENT PRESENT.
Maintain a safe ground and disconnect the power supply
before servicing the unit.
Make sure a qualified electrician makes electrical
connections; disconnect/lock out electricity using OSHA
20CFR 1910.147 standards when servicing the unit.
To adjust the pressure switch:
Figure 9
Compact and Upright Water Temperature Control Units