Download MVI56E-MNETR
Transcript
Reference User Manual MVI56E-MNETR ♦ ControlLogix Platform Modbus TCP/IP Interface Module with Reduced Data Block 2 Edit the Module Properties. Select the REQUESTED PACKET INTERVAL value for scanning the I/O on the module. This value represents the minimum frequency that the module will handle scheduled events. This value should not be set to less than 1 millisecond. The default value is 5 milliseconds. Values between 1 and 10 milliseconds should work with most applications. 3 Save the module. Click OK to dismiss the dialog box. The CONTROLLER ORGANIZATION window now displays the module's presence. 4 5 6 7 Copy the Controller Tags from the sample program. Copy the User Defined Data Types from the sample program. Copy the Ladder Rungs from the sample program. Save and Download (page 48) the new application to the controller and place the processor in run mode. ProSoft Technology, Inc. August 31, 2009 Page 143 of 153