PowerFlex 700L
Active Converter Power Module
USER MANUAL
Firmware Version 3.xxx
Important User
Information
Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application, Installation and
Maintenance of Solid State Controls (Publication SGI-1.1 available from your local
Rockwell Automation sales office or online at http://www.rockwellautomation.com/
literature) describes some important differences between solid state equipment and
hard-wired electromechanical devices. Because of this difference, and also because of
the wide variety of uses for solid state equipment, all persons responsible for applying
this equipment must satisfy themselves that each intended application of this
equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or
consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with any
particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of
information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written
permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of safety
considerations.
!
WARNING: Identifies information about practices or
circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property
damage, or economic loss.
Important: Identifies information that is critical for successful application and
understanding of the product.
!
ATTENTION: Identifies information about practices or
circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard,
avoid a hazard, and recognize the consequences.
Shock Hazard labels may be located on or inside the equipment
(e.g., drive or motor) to alert people that dangerous voltage may be
present.
Burn Hazard labels may be located on or inside the equipment
(e.g., drive or motor) to alert people that surfaces may be at
dangerous temperatures.
Allen-Bradley, PowerFlex, DriveExplorer, DriveExecutive, and DPI are either registered trademarks or trademarks of Rockwell Automation, Inc.
PowerFlex 700L Active Converter Power Module User Manual
Summary of Changes
The information below summarizes the changes resulting from the firmware
v3.001 upgrade to this manual since its last release (June, 2006):
Description of New or Updated Information
To all pages, added a new footer containing:
Page(s)
Throughout
Manual
• Publication description (1st line).
• Publication number hyperlink underlined in blue (2nd line) linking to the date of the
publication on the back cover.
The back cover publication date line hyperlinks to the newest version of the publication
on Rockwell Automation’s Literature Library web site.
Added new information about the Active Converter operating as a Coupled unit (DPI
1-6
SLAVE) or as a Stand Alone unit (DPI MASTER).
Changed the following for Parameter 051 - [Option Select]:
3-6
• Bit 6 changed from “Reserved” to “VC Inverter.”
• Bit 7 changed from “Reserved” to “Prechg Cntrl.”
• The default changed from “xxxx xxxx xx00 0001” to “xxxx xxxx 0000 0001.”
Added new Parameter 105 - [Regen I Lmt].
Changed Parameter 153 - [CML Bandwidth] maximum value from “3000 Rad/sec” to
“4000 Rad/sec.”
Changed the description for Parameter 157 - [PF Bandwidth] to include that it should be
used only when unbalanced voltage compensation is enabled in Parameter 051 [Option Select].
Changed Parameter 162 - [Capacitance] maximum value from “32767 µF” to “65535 µF.”
Added new Parameter 170 - [Bus Capacitance].
Added new Bit 11 (High DC Link) to Parameter 214 - [Start Inhibit].
Changed Parameter 238 - [Fault Config] default from “xxxx xxx1 1110 1100” to
“xxxx xxx1 0110 1100.”
Added two new parameter groups which are only displayed and available in the
Communication File when the Converter is operated as a Stand Alone unit:
• Masks and Owners Group
– Parameter 340 - [Logic Mask]
– Parameter 341 - [Start Mask]
– Parameter 342 - [Fault Clr Mask]
– Parameter 343 - [Stop Owner]
– Parameter 344 - [Start Owner]
– Parameter 345 - [Fault Clr Owner]
• Security Group
– Parameter 346 - [Port Mask Act]
– Parameter 347 - [Write Mask Cfg]
– Parameter 348 - [Write Mask Act]
– Parameter 349 - [Logic Mask Act]
Added the following new fault codes:
•
•
•
•
•
•
•
•
•
•
•
•
•
3-9
3-11
3-11
3-12
3-12
3-14
3-15
3-18
4-3
70 – FiltCap Contactr
71 – Port 1 Adapter
72 – Port 2 Adapter
73 – Port 3 Adapter
74 – Port 4 Adapter
75 – Port 5 Adapter
76 – Port 6 Adapter
81 – Port 1 DPI Loss
82 – Port 2 DPI Loss
83 – Port 3 DPI Loss
84 – Port 4 DPI Loss
85 – Port 5 DPI Loss
86 – Port 6 DPI Loss
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
soc-ii
Summary of Changes
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Table of Contents
Preface
Overview
Who Should Use this Manual? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
What Is Not in this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LPM20 Liquid-Cooled AC Drive Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PowerFlex 700L Liquid-Cooled AC Drive Information . . . . . . . . . . . . . . . . . . . . . . .
PowerFlex 700 Vector Control Information (standard) . . . . . . . . . . . . . . . . . . . . . . . .
PowerFlex 700S Phase II Control Information (optional) . . . . . . . . . . . . . . . . . . . . . .
Reference Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Publications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Allen-Bradley Drives Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manual Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 1
Installation/Wiring
Removing the Active Converter Power Module Covers . . . . . . . . . . . . . . . . . . . . . . . . .
Removing the Active Converter Control Cassette . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Frame 2 and 3A Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Frame 3B Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring the Active Converter Control Cassette I/O Terminals . . . . . . . . . . . . . . . . . . . . .
I/O Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the Active Converter as a Coupled Unit vs. Standalone Unit . . . . . . . . . . . . . . .
Setting the DPI MASTER/SLAVE Switch (SW1) . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting an Active Converter Power Module to an Inverter Power Module . . . . . . . .
Frame 2 and 3A Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Frame 3B Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2
P-1
P-1
P-1
P-1
P-1
P-2
P-2
P-2
P-2
P-2
P-3
1-2
1-2
1-2
1-3
1-4
1-5
1-6
1-8
1-8
1-8
1-8
Start Up
Establishing Communication as a Coupled Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Accessing Active Converter Power Module Parameters. . . . . . . . . . . . . . . . . . . . . . . . 2-1
Verifying Feedback Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Exchanging Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
CIP Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Establishing Communication as a Stand Alone Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Accessing Active Converter Power Module Parameters. . . . . . . . . . . . . . . . . . . . . . . . 2-8
Verifying Feedback Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Converter Sequencing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Run On Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Run On PwrUp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Manual Cntrl . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Start Inhibit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Sequencing Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Control Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Current Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Line Voltage Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Frequency Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
Voltage Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
Current Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
PWM Carrier Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
ii
Table of Contents
Converter Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Converter Faults as a Coupled Unit (DPI SLAVE) . . . . . . . . . . . . . . . . . . . . . . . . . . .
Displaying the Fault Text. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Resetting Converter Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 3
2-17
2-17
2-17
2-18
Programming and Parameters
About Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
How Parameters are Organized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
File-Group-Parameter Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Numbered List View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Monitor File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Command File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Limit Config File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Dynamic Control File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Utility File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
Communication File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
Inputs & Outputs File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20
Parameter Cross Reference – by Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22
Parameter Cross Reference – by Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-23
Chapter 4
Troubleshooting
Faults and Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manually Clearing Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Clearing Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
4-1
4-1
4-1
4-4
4-4
Preface
Overview
The purpose of this manual is to provide you with the basic information
needed to wire and operate the PowerFlex 700 Active Converter Power
Module.
For information on ...
Who Should Use this Manual?
What Is Not in this Manual
Reference Materials
Manual Conventions
General Precautions
See page ...
P-1
P-1
P-2
P-2
P-3
Who Should Use this
Manual?
This manual is intended for qualified personnel. You must be able to wire
and operate Adjustable Frequency AC Drive devices. In addition, you must
have an understanding of the parameter settings and functions.
What Is Not in this Manual
This manual is designed to provide only basic active converter I/O wiring,
start-up, programming, and other related information.
LPM20 Liquid-Cooled AC Drive Installation
For information on installing LPM20 Liquid-Cooled AC drives, please refer
to LPM20 Liquid-Cooled Adjustable Frequency AC Drive Installation
Manual — (Publication No. 20N-IN001…).
PowerFlex 700L Liquid-Cooled AC Drive Information
For information on installing PowerFlex 700L Liquid-Cooled AC drives,
please refer to PowerFlex 700L Liquid-Cooled Adjustable Frequency AC
Drive User Manual — (Publication No. 20L-UM001…).
PowerFlex 700 Vector Control Information (standard)
For PowerFlex Liquid-Cooled AC drives equipped with standard PowerFlex
700 Vector Control, please refer to the PowerFlex 700 Adjustable Frequency
AC Drive User Manual — Series B (Publication No. 20B-UM002…) which
provides I/O wiring, start-up, programming, and vector control encoder
information.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
P-2
Overview
PowerFlex 700S Phase II Control Information (optional)
For PowerFlex Liquid-Cooled AC drives equipped with optional PowerFlex
700S Phase II Control, please refer to the PowerFlex 700S High
Performance AC Drive — Phase II Control User Manual (Publication No.
20D-UM006…) which provides I/O wiring, start-up, programming, and
other related information.
Reference Materials
Publications
Publications can be obtained online at
http://www.rockwellautomation.com/literature.
The following manuals are recommended for general drive information:
Title
Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives
Preventive Maintenance of Industrial Control and Drive System Equipment
Safety Guidelines for the Application, Installation, and Maintenance of Solid State
Control
A Global Reference Guide for Reading Schematic Diagrams
Guarding Against Electrostatic Damage
Publication
DRIVES-IN001…
DRIVES-TD001…
SGI-1.1
0100-2.10
8000-4.5.2
Allen-Bradley Drives Technical Support
Online: www.ab.com/support/abdrives
Manual Conventions
• In this manual we refer also to the PowerFlex 700 Active Converter
Power Module as Active Converter, converter or PowerFlex 700AC.
• To help differentiate parameter names and LCD display text from other
text, the following conventions will be used:
– Parameter Names will appear in [brackets].
For example: [DC Bus Voltage].
– Display Text will appear in “quotes.” For example: “Enabled.”
• The following words are used throughout the manual to describe an action:
Word
Can
Cannot
May
Must
Shall
Should
Should Not
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Meaning
Possible, able to do something
Not possible, not able to do something
Permitted, allowed
Unavoidable, you must do this
Required and necessary
Recommended
Not recommended
Overview
General Precautions
!
!
!
!
P-3
ATTENTION: This drive contains ESD (Electrostatic Discharge)
sensitive parts and assemblies. Static control precautions are
required when installing, testing, servicing or repairing this
assembly. Component damage may result if ESD control
procedures are not followed. If you are not familiar with static
control procedures, refer to Allen-Bradley publication 8000-4.5.2,
“Guarding Against Electrostatic Damage” or any other applicable
ESD protection handbook.
ATTENTION: An incorrectly applied or installed drive can
result in component damage or a reduction in product life. Wiring
or application errors, such as, undersizing the motor, incorrect or
inadequate AC supply, or excessive ambient temperatures may
result in malfunction of the system.
ATTENTION: Only qualified personnel familiar with adjustable
frequency AC drives and associated machinery should plan or
implement the installation, start-up, and subsequent maintenance
of the system. Failure to comply may result in personal injury and/
or equipment damage.
ATTENTION: To avoid an electric shock hazard, verify that the
voltage on the bus capacitors has discharged before performing
any work on the drive. After removing power to the drive, wait 5
minutes for the bus capacitors to discharge. Refer to the:
• LPM20 Liquid-Cooled Adjustable Frequency AC Drive
Installation Manual (Publication No. 20N-IN001…),
Figure 4.2, and measure the DC bus voltage at the locations
shown. The voltage must be zero.
• PowerFlex 700L Liquid-Cooled Adjustable Frequency AC
Drive User Manual (Publication No. 20L-UM001…), and
measure the DC bus voltage at the DC POSITIVE and DC
NEGATIVE test point sockets located on the front of the power
module. The voltage must be zero.
!
ATTENTION: Risk of injury or equipment damage exists. DPI
host products must not be directly connected together via 1202
cables. Unpredictable behavior can result if two or more devices
are connected in this manner.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
P-4
Overview
Notes:
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Chapter
1
Installation/Wiring
This chapter provides information on installing and wiring the PowerFlex
700 Active Converter Power Module.
For information on…
Removing the Active Converter Power Module Covers
Removing the Active Converter Control Cassette
Wiring the Active Converter Control Cassette I/O Terminals
See page…
1-2
1-2
1-4
Most start-up difficulties are the result of incorrect wiring. Every precaution
must be taken to assure that the wiring is done as instructed. All items must
be read and understood before the actual installation begins.
!
ATTENTION: The following information is merely a guide for
proper installation. Rockwell Automation, Inc. cannot assume
responsibility for the compliance or the noncompliance to any
code, national, local or otherwise for the proper installation of
this drive or associated equipment. A hazard of personal injury
and/or equipment damage exists if codes are ignored during
installation.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
1-2
Installation/Wiring
Removing the Active
Converter Power Module
Covers
All converter covers, regardless of drive frame size, are similarly removed
by unfastening the screws. A Frame 3B converter is shown as an example.
PORT
MOD
NET A
NET B
(4 Screws)
PowerFlex 700L
Liquid-Cooled AC Drive
Frame 3B Converter shown
Removing the Active
Converter Control Cassette
Regenerative PowerFlex 700L Liquid-Cooled AC drives use an Active
Converter Power Module equipped with a converter control cassette.
Frame 2 and 3A Drives
PowerFlex 700L Liquid-Cooled Frame 2 and 3A drives combine the Active
Converter and Inverter into a single Power Module. Figure 1.1 shows the
location and removal of the Active Converter control cassette to access its
terminal blocks for control wiring. (The Inverter control cassette is located
just above the Active Converter control cassette.)
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Installation/Wiring
1-3
Figure 1.1 Removing the Frame 2 and 3A Active Converter Control Cassette
Detail
Pin 1
40-Pin
Ribbon Cable
Synchronization Cable
(For use with 700S Phase II Control only)
Internal DPI Cable
P1
Synchronization Cable
(For use with 700 Vector Control only)
SH
LD
SH
LD
P2
Communications
Adapter Option
Frame 3B Drives
Figure 1.2 shows the location and removal of the Active Converter control
cassette to access its terminal blocks for control wiring. Frame 3B drives
have separate Converter Power Modules and Inverter Power Modules.
Figure 1.2 Removing the Frame 3B Active Converter Control Cassette
Synchronization Cable
(For use with coupled Inverter Power
Modules with 700S Phase II Control only)
Internal DPI Cable
Synchronization Cable
(For use with coupled Inverter Power
Modules with 700 Vector Control only)
40-Pin
Ribbon Cable
Pin 1
P1
P2
Detail
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
1-4
Installation/Wiring
Wiring the Active Converter
Control Cassette I/O
Terminals
All wiring should be installed in conformance with the applicable local,
national, and international codes (e.g., NEC/CEC). Signal wiring, control
wiring, and power wiring must be routed in separate conduits to prevent
interference with drive operation. Use grommets, when hubs are not
provided, to guard against wire chafing.
!
ATTENTION: Do not route signal and control wiring with
power wiring in the same conduit. This can cause interference
with drive operation. Failure to observe this precaution could
result in damage to, or destruction of, the equipment.
Important points to remember about I/O wiring:
• Use Copper wire only. Wire gauge requirements and recommendations
are based on 75 degrees C. Do not reduce wire gauge when using higher
temperature wire.
• Wire with an insulation rating of 600V or greater is recommended.
• Control and signal wires should be separated from power wires by at
least 0.3 meters (1 foot).
Important: I/O terminals labeled “(–)” or “Common” are not referenced to
earth ground and are designed to greatly reduce common mode
interference. Grounding these terminals can cause signal noise.
Terminal blocks P1 and P2, shown in Figure 1.1 and Figure 1.3, contain
connection points for all inputs, outputs, and power connections to the
Active Converter control cassette.
1. Remove the terminal block plug from the socket, and make connections.
2. Reinstall the terminal block plug when wiring is complete. The terminal
blocks have keys, which make it difficult to insert a terminal block plug
into the wrong socket.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Installation/Wiring
1-5
Figure 1.3 Active Converter Control Cassette I/O Terminal, Cable Connection, and
DPI SLAVE/MASTER Switch SW1 Locations
J1 40-Pin
Ribbon Cable
Header
Active Converter
Control PCB Assembly
SW1
J2 30-Pin
Ribbon Cable
Header
ON
J9 Synchronization
Cable Header
(700S Ph. II Control only)
ON
DPI SLAVE = OFF
DPI MASTER = ON
J4 Internal DPI
Cable Header
P1 I/O Terminals
(see Table 1.B for
terminal descriptions)
SW1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
P1-7 and P1-8
Synchronization
Cable Connection
(700 Vector Control only)
7
6
5
4
3
2
1
P1-13 and P1-14
Factory-Installed
Gate Kill Jumper
P2 I/O Terminals
(see Table 1.C for
terminal descriptions)
Voltage Feedback
Resistor PCB Assembly
I/O Terminal Blocks
Table 1.A Active Converter Control Board I/O Terminal Block Specifications
Name
Description
I/O Blocks
Signal and power
connections
(1)
Wire Size Range (1)
Maximum
Minimum
1.5 mm2
0.14 mm2
(16 AWG)
(28 AWG)
Maximum
0.25 N-m
(2.2 lb.-in.)
Torque
Recommended
0.22 N-m
(1.9 lb.-in.)
Maximum/minimum that the terminal block will accept - these are not recommendations.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
1-6
Installation/Wiring
Table 1.B Active Converter Control PCB Assembly P1 Terminal Descriptions
Pin
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Description
Comm Out +
Comm Out SOC Out +
SOC Out Comm In +
Comm In SOC In +
SOC In Aux Out N.O.
Aux Out Common
Analog In Signal
Analog In Common
Gate Enable
24 Vdc
Aux Input
Table 1.C Voltage Feedback Resistor PCB Assembly P2 Terminal Descriptions
Pin
7
4
1
Description
L3
L2
L1
Specific pins on P1 and P2 terminals require control wiring connections to
the Input Filter Bay. For wiring information, please refer to the PowerFlex
700L Liquid-Cooled Adjustable Frequency AC Drive User Manual
(Publication No. 20L-UM001…).
Using the Active Converter as a Coupled Unit vs. Standalone Unit
Frame 3B converter power structures may be ordered as a unit Coupled to
an inverter (DPI SLAVE), or as a Stand Alone unit (DPI MASTER). Frame
2 and Frame 3A power structures are always wired for the converter to be a
Coupled unit.
Coupled
Figure 1.4 shows the Active Converter wired to operate as a Coupled unit
(DPI SLAVE). In this configuration, the Converter is connected to a
PowerFlex 700L Inverter through DPI Port 6. When configured for "Run On
Start," the Converter is able to start and stop automatically as the Inverter is
started and stopped.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Installation/Wiring
1-7
Figure 1.4 Active Converter Operating as a Coupled Unit (DPI SLAVE)
Frame 3A with Converter as a
Coupled Unit (DPI SLAVE)
I
n
v
e
r
t
e
r
C
o
n
v
e
r
t
e
r
Frame 3B with Converter as a
Coupled Unit (DPI SLAVE)
C
o
n
v
e
r
t
e
r
HIM
I
n
v
e
r
t
e
r
HIM
Personal
Computer
Personal
Computer
1203-USB or 1203-SSS
Serial Converter
1203-USB or 1203-SSS
Serial Converter
Stand Alone
Figure 1.5 shows the Active Converter wired to operate as a Stand Alone
unit (DPI MASTER). In this configuration, the Converter may have a HIM
or any PowerFlex 7-Class network communication adapter (20-COMM-x)
connected. This may be preferred when the converter is to supply the DC
bus for a set of common bus inverters. When configured for "Run On Start,"
the precharge bypass contactor may be configured to close when the power
is turned on and the DC Bus voltage is stable (see Parameter 51 - [Option
Select]). The Converter starts and stops with commands from the HIM, the
1203-USB or 1203-SSS serial converter, or a 20-COMM-x network
communication adapter.
Figure 1.5 Active Converter Operating as a Stand Alone Unit (DPI MASTER)
Frame 3B with Converter as a
Stand Alone Unit (DPI MASTER)
C
o
n
v
e
r
t
e
r
HIM
196755-C01
193136
I
n
v
e
r
t
e
r
HIM
20-COMM-x
Personal
Computer
181046-C01
1203-USB or 1203-SSS
Serial Converter
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
1-8
Installation/Wiring
The Frame 3B Active Converter power module is ordered as a Stand Alone
unit (DPI SLAVE) by specifying equipment type P in the catalog number
(refer to the catalog number explanation in the PowerFlex 700L User
Manual).
The Stand Alone (DPI SLAVE) Active Converter is supported with Active
Converter firmware revision 3.001 (or higher).
To operate the Frame 3B Active Converter as a Stand Alone unit (DPI
SLAVE) the DPI MASTER/SLAVE switch (SW1) on the Active Converter
control board must be properly set. Refer to Setting the DPI MASTER/
SLAVE Switch (SW1) below for details.
Setting the DPI MASTER/SLAVE Switch (SW1)
Active Converters with version 2.006 (or lower) firmware are always
operated as a peripheral on DPI port 6. In this case, switch SW1 on the
Active Converter control PCB assembly (Figure 1.3) is set to OFF (DPI
SLAVE). Do not use the ON setting. For Active Converters with version
3.001 (or higher) firmware, switch SW1 is used to select between converter
operation as a Coupled unit (DPI SLAVE position) or as a Stand Alone unit
(DPI MASTER position).
Connecting an Active
Converter Power Module to
an Inverter Power Module
Frame 2 and 3A Drives
Coupling a Frame 2 or 3A Power Module is achieved by using two cables: a
DPI cable and a control synchronization cable. These cables are factory
installed.
Frame 3B Drives
Coupling a Frame 3B Active Converter Power Module to a Frame 3B
Inverter Power Module is achieved by using two cables: a DPI cable and a
control synchronization cable. For the Complete Drive equipment type,
these cables are factory installed. When Power Modules are purchased
separately, these cables are user installed. For information regarding these
cables and their installation, please refer to the PowerFlex 700L
Liquid-Cooled Adjustable Frequency AC Drive User Manual (Publication
No. 20L-UM001…), Chapter 3 in the “Synchronization Connections for
Frame B” section.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Chapter
2
Start Up
The start-up procedure built into the HIM addresses only the start up of the
inverter. This chapter describes how to start up the PowerFlex 700 Active
Converter Power Module.
For information on…
Establishing Communication as a Coupled Unit
Establishing Communication as a Stand Alone Unit
Converter Sequencing
Control Setup
Converter Faults
Establishing
Communication as a
Coupled Unit
See page…
2-1
2-8
2-12
2-14
2-17
When the Converter is set to operate as a Coupled unit (DPI SLAVE), the
first step after turning on power is to verify that you are able to
communicate with the unit and that it properly displays selected data.
Data is exchanged between the Inverter Power Module and Active
Converter Power Module to pass control and status information.
An example is given for how to communicate with the Active Converter
Power Module using a CIP message from a ControlLogix controller.
Accessing Active Converter Power Module Parameters
The Active Converter operates as a DPI peripheral on port 6. This section
describes how to access parameters in the Active Converter.
Using the HIM
1. On power up, the HIM displays the main menu and communicates with
the Inverter.
F->
Stopped
0.0
Auto
RPM
Main Menu:
Diagnostics
Parameter
Device Select
2. As you scroll down to “Device Select,” the HIM shows the following
indication. With “Device Select” highlighted, press the Enter key.
F->
Stopped
0.0
Auto
RPM
Main Menu:
Parameter
Device Select
Memory Storage
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
2-2
Start Up
3. The HIM displays that it is currently communicating with the Inverter on
DPI Port 0.
F->
Stopped
0.0
Auto
RPM
Device: Port 0
PowerFlex 700S 2
PowerFlex 700 AC
4. Press the Down arrow to scroll to “PowerFlex 700 AC.”
F->
Stopped
0.0
Auto
RPM
Device: Port 6
PowerFlex 700S 2
PowerFlex 700 AC
5. With “PowerFlex 700 AC” highlighted as shown in Step 4, press the
Enter key to start communicating with the Active Converter on DPI Port
6.
Port 6 Device
PowerFlex 700AC
Main Menu:
Diagnostics
Parameter
Device Select
– To examine the fault queue in the Active Converter, press the Up
Arrow to scroll to “Diagnostics” and press the Enter key.
– To begin examining parameters (with “Parameters” highlighted),
press the Enter key.
– To resume communication with the Inverter, press the Down Arrow to
scroll to “Device Select” and press the Enter key.
6. After accessing the Parameter menu, the display shows the File menu.
Press the Up or Down Arrow to select the desired file and press the Enter
key.
Port 6 Device
PowerFlex 700AC
FGP: File
Monitor
Command
Limit Config
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Start Up
2-3
7. The display then shows the groups of parameters in the selected file.
Press the Up or Down Arrow to select the desired group and press the
Enter key.
Port 6 Device
PowerFlex 700AC
FGP: Group
Current
Voltage
Power & Time
8. The display then shows the parameters in the selected group. Press the
Up or Down Arrow to select the desired parameter and press the Enter
key.
Port 6 Device
PowerFlex 700AC
FGP: Parameter
Rated Amps
Input Current R
Input Current S
9. The display then shows the value of the selected parameter and allows
for entry of a new value for parameters that are read/write.
Port 6 Device
PowerFlex 700AC
FGP:
Par
1
Rated Amps
705.0 Amps
[Alt] [View] - > Limits
Using DriveExplorer
When using DriveExplorer, the window shows the files and groups for the
Active Converter (left pane) and the parameters for the selected group (right
pane). Double-click a parameter in the right pane to edit it
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
2-4
Start Up
Using DriveExecutive
When using DriveExecutive, the Active Converter parameters are displayed
in a linear list. Uploading reads parameter values from all DPI peripherals
but downloading parameters only write to the Inverter. To download
parameter values to the Active Converter, you must first select the
Converter.
Verifying Feedback Parameters
Using the HIM, DriveExplorer or DriveExecutive, verify that reasonable
values are displayed for the following parameters in the Active Converter
Power Module:
• Line to Line Voltage – Verify converter parameters 11 - [Input Voltage
RS], 12 - [Input Voltage ST], and 13 - [Input Voltage TR] display a
reasonable Line to Line RMS Voltage. Verify the voltage imbalance
displayed in parameter 16 - [V Imbalance] does not exceed 5.0%.
• DC Link Voltage – Verify converter parameter 14 - [DcLink Voltage]
displays a reasonable DC Link Voltage.
• AC Line Frequency – Verify converter parameter 40 - [Line Frequency]
displays a reasonable AC Line Frequency.
• Ambient Temperatures – Verify converter parameter 30 - [Ambient
Temp] displays a reasonable ambient temperature. Verify parameter 32 [IGBT Junction Temp] displays the temperature of the liquid being
pumped through the coldplate.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Start Up
2-5
Exchanging Data
DPI Type 3 communication is used to exchange control and status
information between the Inverter and the Converter. This provides a
mechanism to start and stop the Converter as the Inverter is started and
stopped. It also transfers the minimum DC Link voltage required for the
given motor voltage to the Converter, and any Converter fault codes back to
the Inverter so all faults are maintained in the Inverter’s fault queue. The
data exchanged is displayed in these Active Converter parameters:
• 70 - [Converter Control]
• 71 - [Converter Status]
• 72 - [Converter Min Vdc]
• 73 - [Converter Fault]
No setup is required to configure the Type 3 communication. The Converter
requests a Type 3 connection at power up and, when the connection is
complete, Converter parameter 320 - [Connect Status] shows which
communication types are active. The use of Type 3 communication for
exchange of data is important in that none of the normal data links are used
for this communication. By default, all four sets of DPI data links remain
available for use in a 20-COMM-* adapter.
The automatic starting and stopping of the Active Converter requires the
Converter to be configured for “0 = Run On Start” using Converter
parameter 50 - [Start Config]. In this case, when the Inverter is started or
jogged, the Converter is enabled and the Inverter sequencing delays running
the Inverter for up to 500 milliseconds, allowing the Converter to close the
precharge bypass contactor. When the Inverter is stopped, the Converter
continues to run for the time configured in Converter parameter 53- [Turn
Off Delay]. On a subsequent start or jog, the Inverter does not need to wait
for the precharge to close if the Converter is still running.
Start
Jog
Inverter
Functions
Inverter Sequencing
Inverter
Communications
Inverter DPI Type 3
Producer / Consumer
Converter
Communications
Converter DPI Type 3
Producer / Consumer
PF700 AC
Parameters
Converter
Functions
AC 70 - [Converter Control]
AC 71 - [Converter Status]
AC 72 - [Converter Min Vdc]
AC 73 - [Converter Fault]
Converter Sequencing
Precharge
Contactor
Converter
Enable
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
2-6
Start Up
In addition to Type 3 communication, the 700S may optionally use DPI data
links to control the sequencing of the Converter from a Logix processor as
shown below. This requires the Converter to be configured for Manual
Control in Converter parameter 50 - [Start Config]. The reference for the
voltage loop may also be controlled by a Logix processor when Converter
parameter 160 - [Voltage Loop Sel] is set to Manual Ref.
The DPI data links between the Inverter and Converter are enabled by
setting Converter parameters 300 - [Data In A1] through 317 - [Data Out
D2] to the parameter number of the data to send or receive. When a DPI
data link is used by the Converter, that channel cannot be used by a different
communication card. The following example illustrates using DPI data links
between the Inverter and Converter.
Suppose Inverter parameter 666 is linked to Converter parameter 52 [Manual Control], Inverter parameter 667 is linked to Converter parameter
60 - [DcLink Reference], and Converter parameter 71 - [Converter Status] is
linked to Inverter parameter 657. This requires Converter data links to be
configured as follows:
• Active Converter parameter 306 [Data In D1] = 52
• Active Converter parameter 307 [Data In D2] = 60
• Active Converter parameter 316 [Data Out D1] = 71
This example shows Data Link D being used to communicate with the
Converter. The Converter supports DPI Data Links A, B, C, and D so any
group could be used as needed.
All the options for starting and stopping the Converter are explained in
greater detail in Converter Sequencing on page 2-12.
Logix
PF700 S
Parameters
S 666 - [DPI Data Out D1]
Inverter
Communications
Inverter DPI Data Link
Producer / Consumer
Converter
Communications
Converter DPI Data Link
Producer / Consumer
PF700 AC
Parameters
Converter
Functions
AC 52 - [Manual Control]
AC 71 - [Converter Status]
AC 60 - [DcLink Reference]
Converter Sequencing
Precharge
Contactor
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
S 657 - [DPI Data In D1]
S 667 - [DPI Data Out D2]
Converter
Enable
Start Up
2-7
CIP Messages
Parameters in the Converter may be accessed by a Logix processor using a
CIP message block. To read or write a parameter value you must
respectively perform a Get Attribute Single or Set Attribute Single message
to the DPI Parameter Object (Class 0x93). The Converter is in DPI Port 6,
so the instance is 22528 plus the parameter number. The value of the
parameter is accessed through Attribute 0x9 or 0xA. The example shown
below reads the value of Converter parameter 30 - [Ambient Temp].
Class Code
Hexadecimal
0x93
Decimal
147
Instances
Instances (Hex.)
0x0000 – 0x3FFF
0x4000 – 0x43FF
0x4400 – 0x47FF
0x4800 – 0x4BFF
0x4C00 – 0x4FFF
0x5000 – 0x53FF
0x5400 – 0x57FF
0x5800 – 0x5BFF
(Dec.)
0 – 16383
16384 – 17407
17408 – 18431
18432 – 19455
19456 – 20479
20480 – 21503
21504 – 22527
22528 – 23551
Device
Host
Adapter
DPI Port 1
DPI Port 2
DPI Port 3
DPI Port 4
DPI Port 5
DPI Port 6
Attributes
ID
0x9
0xA
Rule
Get/Set
Get/Set
Name
Parameter Value
Parameter Value
Data Type
Various
Various
Description
Value in NVS
Value in RAM
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
2-8
Start Up
Establishing
Communication as a Stand
Alone Unit
When the Converter is set to operate as a Stand Alone unit (DPI MASTER),
the first step after turning on power is to verify that you are able to
communicate with the unit and that it properly displays selected data.
Accessing Active Converter Power Module Parameters
Using the HIM
1. On power up, the HIM displays the AC Line Frequency, the Active
Current, and the DC Bus Voltage. The status text will display one of five
indications: Faulted, Start Inhibit, Ready, Running or Ride Through.
F->
Ready
Auto
59.97 Hz
0.00 Amps
664.20 Bus VDC
2. Access the parameters of the Converter by selecting Parameter on the
Main Menu.
F->
Ready
Auto
59.97 Hz
Main Menu:
Diagnostics
Parameter
Device Select
3. Parameters may then be accessed with the File, Group, Parameter menu,
F->
Ready
Auto
F->
59.97 Hz
Ready
59.97 Hz
FGP: File
Monitor
Command
Limit Config
FGP: File
Current
Voltage
Power & Time
Auto
F->
Ready
Auto
59.97 Hz
FGP: File
Rated Amps
Input Current R
Input Current S
or with a Numbered List.
F->
Ready
59.97 Hz
Parameter: #
Auto
1
Rated Amps
650.0 Amps
[Alt] [View] - > Limits
The start and stop buttons may start and stop the Converter. The stop button
may also be used to reset a fault in the Converter. The speed, jog, forward/
reverse, and auto/manual buttons are not functional.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Start Up
2-9
Using DriveExplorer or DriveExecutive
When using DriveExplorer or DriveExecutive, the Converter parameters are
displayed under Port 0 and are organized into the normal menu of Files,
Groups, and Parameters. The control bar can be opened to show a stop and
start push button.
Verifying Feedback Parameters
Using the HIM, DriveExplorer or DriveExecutive, verify that reasonable
values are displayed for the following parameters in the Active Converter
Power Module:
• Line to Line Voltage – Verify converter parameters 11 - [Input Voltage
RS], 12 - [Input Voltage ST], and 13 - [Input Voltage TR] display a
reasonable Line to Line RMS Voltage. Verify the voltage imbalance
displayed in parameter 16 - [V Imbalance] does not exceed 5.0%.
• DC Link Voltage – Verify converter parameter 14 - [DcLink Voltage]
displays a reasonable DC Link Voltage.
• AC Line Frequency – Verify converter parameter 40 - [Line Frequency]
displays a reasonable AC Line Frequency.
• Ambient Temperatures – Verify converter parameter 30 - [Ambient
Temp] displays a reasonable ambient temperature. Verify parameter 32 [IGBT Junction Temp] displays the temperature of the liquid being
pumped through the coldplate.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
2-10
Start Up
Using a 20-COMM-x Adapter
When a 20-COMM-x network communication adapter is connected to the
Converter, the Product Logic Command bits may be used to start and stop
the Converter and to reset a fault. All other bits are reserved. The Product
Logic Status bits may be used to determine the state of the Converter.
Converter Logic Command Word
Logic Bits
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0 Command
x Stop
x
Start
x
Reserved
Fault Reset
x
x
Description
0 = Not Stop
1 = Stop
0 = Not Start
1 = Start
0 = Not Fault Reset
1 = Fault Reset
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
x
x
x
x
x
x
x
x
x
x
x
Converter Logic Status Word
Logic Bits
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
0
x
Status
Ready
Running
Reserved
Reserved
Reserved
Reserved
Alarm
Fault
Description
0 = Not Ready
1 = Ready
0 = Not Running
1 = Running
0 = No Alarm
1 = Alarm
0 = No Fault
1 = Fault
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
The reference value from the 20-COMM-x adapter that is often used to
select the speed is not used in the Converter. The Converter is always
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Start Up
2-11
synchronized to the AC line frequency and does not have a speed reference.
The feedback value sent to the 20-COMM-x adapter is the measured AC
line frequency, where a value of 32767 corresponds to 100.00 Hz.
The Converter supports 16-bit data links so if all data links are configured in
the 20-COMM-x then the Connection Parameters in the Logix Processor
must be setup as shown here. This defines twelve 16-bit words sent from the
20-COMM-x to the Logix, and ten 16-bits words sent from the Logix to the
20-COMM-x.
The data is utilized as shown below:
Logix to 20-COMM-x
Word Output I/O
1
Logic Command
2
Reference (not used)
3
Datalink In A1
4
Datalink In A2
5
Datalink In B1
6
Datalink In B2
7
Datalink In C1
8
Datalink In C2
9
Datalink In D1
10
Datalink In D2
20-COMM-x to Logix
Word Input I/O
1
Not Used
2
Not Used
3
Logic Status
4
Feedback (AC line frequency)
5
Datalink Out A1
6
Datalink Out A2
7
Datalink Out B1
8
Datalink Out B2
9
Datalink Out C1
10
Datalink Out C2
11
Datalink Out D1
12
Datalink Out D2
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
2-12
Start Up
Converter Sequencing
The condition when to start and stop the Converter must be configured in
parameter 50 - [Start Config]. There are three ways to operate the
Converter: Run On Start, Run On Power Up, and Manual Control. This also
configures how the precharge bypass contactor operates.
Run On Start
When Converter parameter 50 - [Start Config] is set to “0 = Run On Start,”
the operation changes when the Converter is set as a Coupled unit (DPI
SLAVE) or a Stand Alone unit (DPI MASTER) using SW1 (Figure 1.3).
Coupled Unit (DPI SLAVE Setting)
When set as a Coupled unit (DPI SLAVE) and Run on Start is selected, then
starting and stopping the Converter is coordinated with starting and
stopping the Inverter. When the Inverter is started or jogged, the Converter
is enabled to turn on. When the Inverter is stopped or jog is released, the
Converter is stopped.
Stand Alone Unit (DPI MASTER Setting)
When set as a Stand Alone unit (DPI MASTER) and Run on Start is
selected, then the Converter may be started and stopped from the buttons on
a HIM, or by the Logic Command bits transmitted by a 20-COMM-x
adapter or 1203-USB or 1203-SSS device. The logic masks determine
which DPI ports are allowed to take control.
Precharge Bypass Operation
In Run On Start, the precharge can be configured to operate in one of two
ways as selected by parameter 51 - [Option Select], Bit 7 (Precharge
Control). By default, this option bit is turned off so the precharge bypass
contactor will be commanded to close at the time the Converter is
commanded to start, and the bypass contactor opens after the Converter is
commanded to stop. If the option bit is set, then the bypass contactor is
closed at power up after the DC bus is at steady state.
If there is a fault in the Converter, the precharge bypass contactor will open.
If the option bit is set, the bypass contactor is closed when the fault is reset.
The option bit also selects how long the Converter continues to run after it is
commanded to stop. If the option bit is turned off, then parameter 53 - [Turn
Off Delay] selects the time delay between the stop command and the time
when the converter is stopped and the bypass is opened. If the option bit is
turned on, then the Converter stops without a delay.
As a Coupled unit (DPI SLAVE), Run On Start with the precharge option
bit turned off is recommended for applications where the drive is left
powered up but the drive is not run for extended periods of time. With the
precharge bypass contactor open, the fan cooling the input reactor is turned
off.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Start Up
2-13
Run On PwrUp
When Converter parameter 50 - [Start Config] is set to “1 = Run On
PwrUp,” the precharge bypass contactor is automatically closed and the
Converter is enabled shortly after power is turned on.
The precharge will close as soon as the DC Link voltage is above the
minimum required level and it has reached steady state. The precharge will
remain closed when there is a fault in the Converter. When the fault is reset,
the Converter will go back into run. In this configuration, the coolant
circulating loop must be enabled when the Converter is enabled, even if the
Inverter is not in run. The auxiliary contacts on the precharge bypass could
be used to enable the circulating pump.
This mode of operation is recommended for applications where the drive is
powered down when it is to be stopped for an extended period of time.
Manual Cntrl
When Converter parameter 50 - [Start Config] is set to “2 = Manual Cntrl,”
the operation of the precharge bypass contactor and enabling of the
Converter is controlled by two bits in Converter parameter 52 - [Manual
Control]. The bits are normally level sensitive. Turning the bits on closes the
bypass contactor and enables the Converter. Turning the bits off opens the
bypass contactor and disables the Converter.
The exception is that if there is a fault, the bypass contactor is not allowed to
close. After a fault, the fault must be reset, and then a rising edge on bit 1 in
parameter 52 - [Manual Control] is required to re-enable the Converter. The
value in parameter 52 is not retentive; it is reset to zero on power up.
When operating as a Coupled unit (DPI SLAVE), the Inverter is not allowed
to start with the precharge open and the Inverter will fault if it started with
the Converter stopped. When operating as a Stand Alone unit (DPI
MASTER), the value in parameter 52 - [Manual Control] may be written by
a datalink and the value in parameter 72 - [Converter Status] may be read
with a datalink and used as part of the interlocks with Inverters.
Start Inhibit
If the Converter does not start when expected, refer to Converter parameter
214 - [Start Inhibit] to display the Start Inhibit conditions.
Sequencing Precautions
When operating as a Coupled unit (DPI SLAVE) that is supplying power to
a single Inverter, the built-in interlocks will not allow the Inverter to start
unless the Converter is running, and the Converter will not stop when the
Inverter is running. However, when the Converter is operated as a Stand
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
2-14
Start Up
Alone unit (DPI MASTER) and is supplying power to a common bus, extra
precaution must be taken.
!
ATTENTION: When operating as a Stand Alone unit (DPI
MASTER) or supplying power to a common bus, external logic
must be used to make sure the precharge bypass contactor is
closed and the Converter is running before running an Inverter.
Likewise, all Inverters must stop if the precharge opens or the
Converter stops.
Operating an Inverter with the precharge bypass open will overheat the
precharge resisters. Operating an Inverter with the Converter stopped will
draw non-sinusoidal current with peak current greater than rated and will
have significant harmonic distortion.
Control Setup
The following topics discuss parameters that should be reviewed when
starting up an Active Converter.
Current Limits
Converter parameter 100 - [Active I Lmt] defines the limit on active current.
This parameter defaults to 150% of Converter rated current. Current limit
for regeneration is set in parameter 105 - [Regen I Lmt]. This defaults to
-150% of Converter rated current. When in current limit, the Converter is
unable to regulate the DC link voltage. If the drive is motoring and the
Converter is in current limit, then the DC link will drop to the peak of the
AC line. If the drive is regenerating and the Converter is in current limit, the
DC link will rise and it is up to the Inverter to limit its regenerating current
to avoid a high bus fault.
The Converter parameter 71 - [Converter Status] word bit 4 (Bus Reg Ena)
turns on when the Converter is in current limit to command the Inverter to
enable its bus voltage regulators. When the Converter is active and Bus Reg
Ena is turned off, the bus voltage regulators in the Inverter are turned off.
Line Voltage Limits
The limits on line voltage may need to be adjusted to indicate abnormal
conditions. At low line voltages, the Converter will deliver greater amps to
produce the same power. If the possible range of input voltage would result
in a condition that would exceed the rated current, then the voltage limits
must be set to guard against this condition. The low voltage and high
voltage limits have timers associated with each limit to allow brief
excursions outside of normal operating conditions. See Converter
parameters 112 -[Low Vac Lmt] through 115 - [High Vac Time].
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Start Up
2-15
Frequency Limits
The PWM Carrier Frequency is fixed at 4 kHz and cannot be changed.
If operating on a generator, the normal range of acceptable AC line
frequencies may need to be expanded. The limit of the rate of change may
also need to be adjusted to allow the line synchronization to properly track
the changes in frequency. See Converter parameters 131 - [AC Low Freq
Lmt] through 135 - [AC Maximum dF/dt].
Voltage Loop
The voltage major loop uses Vdc Reference and Vdc Feedback to calculate
the required active current to maintain a constant DC bus voltage.
Voltage Reference Selection
Converter parameter 160 - [Voltage Loop Sel] selects the value used for the
DC Link voltage reference. One of two values may be chosen at this time;
“0 = Optimized Ref” and “1 = Manual Ref.” The Regen Only option is
reserved for future enhancements, and the Open Loop option is reserved for
manufacturing tests. A password must be entered to use the Open Loop
option.
When “0 = Optimize Ref” is selected, the value for the DC Link reference is
calculated as the minimum value for the given operating condition to reduce
switching losses and increase efficiency. The base value for DC Link
reference is 1.44 times the RMS AC line. For a 480 volt line, the DC link
reference starts at 692 Vdc. This is 2% above the peak of the AC line. In
applications where the maximum motor voltage is greater than the AC line,
the Converter can boost the DC link to a higher level. The Inverter
calculates the minimum required DC link for the present motor voltage and
transmits that value to Converter parameter 72 - [Converter Min Vdc]. As
the line voltage goes up and down and as the Inverter’s motor voltage goes
up and down, the DC Link reference goes up and down to match the
operating conditions.
This option is most useful when there are significant changes in the line
voltage. This option is not recommended for common bus applications
where multiple Inverters operate at different speeds.
When “1 = Manual Ref” is selected, the value for DC Link reference is the
value in parameter 60 - [DcLink Reference]. If the peak of the AC line
becomes greater than the entered value, then the AC line will over-ride to
keep the DC link reference at least 1.44 times the RMS AC line. This option
is intended for operating at a specific DC Link voltage, or in situations were
the Converter is regulating a common bus for multiple Inverters and an
external controlling device is calculating the required DC Link voltage.
The currently commanded DC Link voltage is displayed in parameter 161 [DcLink Command].
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
2-16
Start Up
Voltage Loop Tuning
The tuning of the voltage loop is a function of Converter parameter 162 [Capacitance], parameter 163 - [VML bandwidth], and parameter 164 [VML Damping]. In most cases, the default values for these three
parameters should not need to be adjusted. When multiple Inverters are on a
common bus, the combined DC link capacitance of the additional inverters
must be entered into parameter 170 - [Bus Capacitance].
Current Loop
The current minor loops regulate the active current as requested by the
voltage major loop, and the reactive current to produce the desired kVAR.
kVAR Control
KVAR Control can be used for power factor compensation.
When parameter 61- [kVAR Reference] is set to zero, the Converter will
regulate reactive current to maintain unity power factor. When a nonzero
value is entered, it requests the amount of kVAR to command. Negative
values are a lagging power factor and positive values are a leading power
factor. When no real current is being delivered by the Converter, the full
current rating of the Converter may be used to produce kVAR. As real
current increases, motoring or regenerating, the reactive current limit is
automatically reduced. The reactive current limit is displayed in parameter
158- [Reactive I Lmt]. The reactive current that is being commanded is
displayed in parameter 159- [Reactive I Cmd].
Current Loop Tuning
The tuning of the current loop is a function of Converter parameter 152 [Inductance], parameter 153 - [CML Bandwidth], and parameter 154 [CML Damping]. In most cases, the default values for these three
parameters should not need to be adjusted. If a non-standard input filter is
used, the new inductance needs to be entered. When the AC line voltage has
greater than 5% impedance, the CML bandwidth may need to be reduced.
PWM Carrier Synchronization
The converter has the option to synchronize its PWM carrier frequency to
the PWM carrier frequency of the inverter to reduce the common mode
voltage on the motor. This requires the Inverter carrier frequency to be set to
4 kHz.
PWM carrier synchronization is enabled by setting parameter 51- [Option
Select] bit 3 (PWM SyncRecv). After carrier synchronization is completed,
the Converter sets parameter 71 - [Converter Status] bit 9 (PWM
SyncLock). When PWM SyncRecv is set and sync is not locked, the
Converter is inhibited from starting. If sync is lost while the Converter is in
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Start Up
2-17
run, a fault is generated. This fault can be disabled in parameter 238 - [Fault
Config] bit 7 (PWM SyncLost).
When operating as a Stand Alone unit (DPI MASTER) and PWM Carrier
Synchronization is enabled, the Converter needs to know if it should
synchronize to a 700VC or a 700S. This selection is done in parameter 51 [Option Select] Bit 6 (700VC Invtr). This bit must be set for a 700VC and
cleared for a 700S. PWM carrier synchronization can only be done with one
inverter, so any other inverters on the common bus will have higher
common mode voltage.
Converter Faults
When set to operate as a Coupled unit (DPI SLAVE), any fault in the
Converter is passed to the Inverter so all the faults are recorded in the
Inverter fault queue. When set to operate as a Stand Alone unit (DPI
MASTER), the Converter maintains its own fault queue.
Converter Faults as a Coupled Unit (DPI SLAVE)
When using PowerFlex 700 Vector Control, the fault from the Converter is
added to a base number of 300, so all the Converter faults are numbered 301
to 399. The pop-up window on the HIM alerts the user to look at the fault
log in the PF700AC to get the specific fault text.
- Fault - F 340
F340 See PF700AC
Time Since Fault
00000:00:01
When using PowerFlex 700S Phase II Control, the faults from the Converter
are all combined into one fault code (F110) in the Inverter. The pop-up
window on the HIM alerts the user to look at the fault log in the PF700AC
to get the specific fault text.
- Fault - F 110
700L Cnv Faulted
Time Since Fault
00000:00:01
For a complete listing of Converter faults, descriptions, and actions, please
refer to Fault Descriptions on page 4-1.
Displaying the Fault Text
To view the fault queue in the Converter with a HIM, begin by using the
Device Select menu as described in Accessing Active Converter Power
Module Parameters on page 2-1.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
2-18
Start Up
1. Rather than selecting Parameters, use the Up arrow to select
“Diagnostics” and press the Enter key.
Port 6 Device
PowerFlex 700AC
Main Menu:
Diagnostics
Parameter
Device Select
2. The HIM then displays the Diagnostics menu. With “Events” selected,
press the Enter key.
Port 6 Device
PowerFlex 700AC
Diagnostics:
Events
Status Info
Device Version
3. The HIM then displays the Diag: Events menu. With “View Event
Queue” selected, press the Enter key.
Port 6 Device
PowerFlex 700AC
Diag: Events
View Event Queue
Clear Events
Clr Event Queue
4. The HIM then displays the Event queue where the specific fault text is
displayed. In this example screen, the Converter faulted because the AC
was lost and power dip ride through was not enabled.
Port 6 Device
PowerFlex 700AC
EvtQ#1:
E#
AC Line Lost
Accum:
40
0:00:00.001
Resetting Converter Faults
In most cases, faults in the Converter are reset by resetting the Inverter. If
the condition causing the fault is still present, then a second fault is
generated and recorded in the fault queue. The only exception is a
checksum fault in the Converter. A checksum fault in the Converter is reset
by doing a reset defaults in the Converter, and then reset the fault in the
Inverter.
Clearing the fault queue in the Inverter does not affect the event queue in the
Converter. The Converter event queue is cleared independently of the
Inverter fault queue.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Chapter
3
Programming and Parameters
This chapter provides a complete listing and description of the Active
Converter Power Module parameters. The parameters can be configured
(viewed/edited) using an LCD HIM (Human Interface Module). As a
convenient alternative, programming can also be performed using
DriveExecutive™ or DriveExplorer™ software and a personal computer.
For information on…
About Parameters
How Parameters are Organized
Monitor File
Command File
Limit Config File
Dynamic Control File
Utility File
Communication File
Inputs & Outputs File
About Parameters
See page…
3-1
3-2
3-4
3-6
3-9
3-11
3-13
3-17
3-20
To configure the Active Converter Power Module to operate in a specific
way, parameters may have to be set. Three types of parameters exist:
• ENUM Parameters
ENUM parameters allow a selection from 2 or more items. The LCD
HIM will display a text message for each item.
• Bit Parameters
Bit parameters have individual bits associated with features or
conditions. If the bit is 0, the feature is off or the condition is false. If the
bit is 1, the feature is on or the condition is true.
• Numeric Parameters
These parameters have a single numeric value (i.e. 0.1 Volts).
The example on the following page shows how each parameter type is
presented in this manual.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
3-2
Programming and Parameters
➎
Default:
0
“Ready”
Options:
0
1
“Ready”
“Factory”
Drive…
197
238
Ac Low Volt
Rated ÷ 4/Rated*1.5 Amps
0.1 Amps
Ac High Volt
Rated Amps*1.5
Min/Max:
Units:
Ac Low Freq
Default:
Ac High Freq
[Active I Lmt]]
Sets the current limit used when the IGBT overload is less than 90% of the IT fault
threshold.
[Reset to Defaults]
Resets all values in the Converter to the factory defaults.
“Ready” = A new value may be entered.
“Factory” = Parameters are reset.
[Fault Config]
A set of bits that select which conditions may generate faults.
High dFdt
100
I Imbalance
Values
V Imbalance
Parameter Name & Description
PWM SyncLost
No.
Inverter Flt
Current Group
LIMIT… File
➊ ➋ ➌ ➍
Default
x
x
1
0
1
1
0
1
1
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
UTILITY
Fault Queue
Bit
Definition
•
•
•
•
•
•
•
•
•
x
x
x
x
x
0 = Disabled
1 = Enabled
x = Reserved
Bit 0 (Ac Low Volt) – When this bit is set, Low AC Line Voltage will generate a fault.
Bit 1 (Ac High Volt) – When this bit is set, High AC Line Voltage will generate a fault.
Bit 2 (Ac Low Freq) – When this bit is set, Low AC Line Frequency will generate a fault.
Bit 3 (Ac High Freq) – When this bit is set, High AC Line Frequency will generate a fault.
Bit 4 (High dFdt) – When this bit is set, High dF/dt will generate a fault.
Bit 5 (I Imbalance) – When this bit is set, high current imbalance will generate a fault.
Bit 6 (V Imbalance) – When this bit is set, high voltage imbalance will generate a fault.
Bit 7 (PWM SyncLost) - When this bit is set, loss of PWM synchronization will generate a fault.
Bit 8 (Inverter Flt) - When this bit is set, the Converter will fault when the Inverter faults.
No. Description
➊ File – Lists the major parameter file category.
➋
➌
➍
➎
Group – Lists the parameter group within a file.
No. – Parameter number.
= Parameter value cannot be changed until Converter is stopped.
Parameter Name & Description – Parameter name as it appears on an LCD HIM, with a brief description of the parameters function.
Values – Defines the various operating characteristics of the parameter. Three types exist.
ENUM
Default:
Lists the value assigned at the factory. “Read Only” = no default.
Options:
Displays the programming selections available.
Bit
Bit:
Lists the bit place holder and definition for each bit.
Lists the value assigned at the factory. “Read Only” = no default.
Numeric
Default:
Min/Max: The range (lowest and highest setting) possible for the parameter.
Unit of measure and resolution as shown on the LCD HIM.
Units:
How Parameters are
Organized
The LCD HIM displays parameters in a File-Group-Parameter or Numbered
List view order. To switch display mode, access the Main Menu, press ALT,
then Sel while cursor is on the parameter selection.
File-Group-Parameter Order
This simplifies programming by grouping parameters that are used for
similar functions. The parameters are organized into 7 files. Each file is
divided into groups, and each group contains a set of parameters related to a
specific purpose.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Programming and Parameters
File
Group
Parameters
Monitor
Current
Rated Amps
Input Current R
Input Current S
Voltage
Rated Volts
010
Input Voltage RS 011
Input Voltage ST 012
Input Voltage TR 013
DcLink Voltage
DcLink Ripple
014
015
Power & Time
Rated Power
AC Line kW
Motoring kWh
Regen kWh
023
Lifetime kWh
024
Elapsed Run Time 025
Life Run Time
Life Power Time
Life Pwr Cycles
026
027
028
Monit
or
Command
Comm
and
Limit Config
Limit
001
002
003
020
021
022
Input Current T
Ground Current
Active Current
004
005
006
Reactive Current 007
I Imbalance
008
IT Overload
009
Temperature
Ambient Temp
030
IGBT Base Temp 031
IGBT Junct Temp 032
Frequency
Line Frequency
Min Line Freq
040
041
Max Line Freq
Min Max Persist
042
043
Change Line Freq 044
Start/Stop
Start Config
050
Option Select
051
Manual Control
052
Setpoints
DcLink Reference 060
kVAR Reference 061
Extern Cml Ref 062
Modulation Index 063
Modulation Freq
064
Data Exchange
Converter Control 070
Converter Status 071
Converter Min Vdc 072
Current
Active I Lmt
Active OL I Lmt
Reactive RateLmt 102
I Imbalance Lmt 103
I Imbalance Time 104
Regen I Lmt
105
AC Line Voltage
Ride Through Ena 110
Ride Through Sec 111
Low Vac Lmt
Low Vac Time
High Vac Lmt
High Vac Time
Temperature
Ambnt Temp Alrm 120
Ambnt Temp Trip 121
Frequency
100
101
3-3
V Imbalance
016
Turn Off Delay
053
Converter Fault
073
Config
Dynamic Control
Dynami
114
115
V Imbalance Lmt 116
V Imbalance Time 117
Base Temp Alrm 122
Base Temp Trip 123
Junct Temp Alrm 124
Junct Temp Trip 125
CldPlt Temp Alrm 126
PWM Frequency 130
AC Low Freq Lmt 131
AC Low Freq Time 132
AC High Freq Lmt 133
AC High Freq Time134
AC Maximum dF/dt135
Current Loop
Reduce Ilmt Sel
Active I Cmd
Inductance
150
151
152
CML Bandwidth
CML Damping
CML Ki
153
154
155
CML Kp
PF Bandwidth
Reactive I Lmt
Voltage Loop
Voltage Loop Sel 160
DcLink Command 161
Capacitance
162
VML Bandwidth
VML Damping
VML Ki
163
164
165
VML Kp
166
VML Kf
167
VML Reset Level 168
Parallel Config
169
Bus Capacitance 170
Drive Memory
Param Access Lvl 196
Reset to Defaults 197
Reset Meters
Language
200
201
Drive Checksum 203
Control SW Ver 204
Password
205
Diagnostics
Alarm Status
Start Inhibit
Fault Frequency
Fault Amps R
Fault Amps S
Fault Amps T
Fault Amps Q
Fault Amps D
Fault Volts RS
Fault Volts ST
223
224
225
226
227
Fault VoltsTR
Fault Volts Vdc
Fault Base Temp
Testpoint 1 Sel
Testpoint 1 Data
228
229
230
234
235
Testpoint 2 Sel
Testpoint 2 Data
236
237
Fault Queue
Fault Config
238
Fault Clear
239
Power Up Marker 242
Fault 1 Code
Fault 1 Time
Fault 2 Code
243
244
245
Fault 2 Time
Fault 3 Code
Fault 3 Time
246
247
248
Fault 4 Code
Fault 4 Time
Alarm Config
249
250
260
Datalinks
Data In A1
Data In A2
Data In B1
Data In B2
300
301
302
303
Data In C1
Data In C2
Data In D1
Data In D2
304
305
306
307
Data Out A1
Data Out A2
Data Out B1
Data Out B2
310
311
312
313
Data Out C1
Data Out C2
Data Out D1
Data Out D2
314
315
316
317
DPI Status
Connect Status
DPI Error Out
CS Msg Rx Cnt
320
321
322
CS Msg Tx Cnt 323
CS Timeout Cnt 324
CS Msg Bad Cnt 325
PC Msg Rx Cnt
PC Msg Tx Cnt
PC Timeout Cnt
326
327
328
CAN Bus Off Cnt
329
Masks & Owners Logic Mask
Start Mask
340
341
Fault Clr Mask
Stop Owner
342
343
Start Owner
Fault Clr Owner
344
345
Security
Port Mask Act
346
Write Mask Cfg
347
Write Mask Act
348
Logic Mask Act
349
Mux’ed Temps
IGBT NTC Temp1 330
IGBT NTC Temp2 331
IGBT NTC Temp3 332
c Contr
ol
Utility
112
113
156
157
158
Reactive I Cmd
159
Utility
Communication
Comm
unica
tion
Inputs & Outputs
Inputs
& Outpu
ts
211
214
220
221
222
IGBT NTC Temp4 333
Coldplate Temp1 334
IGBT NTC Temp5 335
IGBT NTC Temp6 336
IGBT NTC Temp7 337
IGBT NTC Temp8 338
Dig In Frc Data
Digital Inputs
Dig In Status
350
Dig In Frc Mask
Digital Outputs
Dig Out Status
360
Dig Out Frc Mask 361
351
Coldplate Temp2 339
352
Dig Out Frc Data 362
Numbered List View
All parameters are in numerical order.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
3-4
Programming and Parameters
Group
File
Monitor File
No.
Parameter Name & Description
Values
001
[Rated Amps]
When operating as a Coupled unit, displays the same rated current as the inverter
as the voltage class is changed.
[Input Current R]
[Input Current S]
[Input Current T]
Displays the measured RMS phase currents.
[Ground Current]
Displays the measured ground current.
Default:
Read Only
Min/Max:
Units:
0.0/3000.0
0.1 Amps
Default:
Read Only
Min/Max:
Units:
0.0/3000.0
0.1 Amps
Default:
Read Only
Min/Max:
Units:
Default:
0.0/3000.0
0.1 Amps
Read Only
Min/Max:
Units:
-3000.0/+3000.0
0.1 Amps
Default:
Read Only
Min/Max:
Units:
-3000.0/+3000.0
0.1 Amps
Default:
Read Only
Min/Max:
Units:
Default:
0.0/100.0
0.1%
Read Only
Min/Max:
Units:
0.0/100.0
0.1%
Default:
Read Only
Min/Max:
Units:
0.0/690.0
0.1 Vac
Default:
Read Only
Min/Max:
Units:
0.0/760.0
0.1 Vac
Default:
Read Only
Min/Max:
Units:
Default:
0.0/1225.0
0.1 Vdc
Read Only
Min/Max:
Units:
Default:
0.0/1225.0
0.1 Vdc
Read Only
Min/Max:
Units:
Default:
0.0/100.0
0.1%
Read Only
Min/Max:
Units:
Default:
0.00/3000.00
0.01 kW
Read Only
Min/Max:
Units:
-3000.0/+3000.0
0.1 kW
Default:
Read Only/Reset
Min/Max:
Units:
0.0/429496729.5
0.1 kWh
Default:
Read Only/Reset
Min/Max:
Units:
0.0/429496729.5
0.1 kWh
002
003
004
005
Current
006
007
008
MONITOR
009
010
Voltage
011
012
013
014
015
016
Power & Time
020
021
022
023
[Active Current]
Displays the measured active current. Positive values are motoring, negative values
are regeneration.
[Reactive Current]
Displays the measured reactive current. Positive is lagging, negative is leading
power factor.
[I Imbalance]
Displays the current imbalance calculated between phases R, S, and T.
[IT Overload]
Displays the accumulated IT overload. The Converter allows 110% for 60 seconds
and 150% for 3 seconds. Operating beyond these ratings will result in this
accumulator counting up to 100.0% and the generation of a fault. An alarm is turned
on when this parameter reaches 90.0 %, at which time the current limit can be
reduced until this parameter integrates down to 50.0%.
[Rated Volts]
When operating as a Coupled unit, displays the same rated voltage as the inverter
as the voltage class is changed.
[Input Voltage RS]
[Input Voltage ST]
[Input Voltage TR]
Displays the measured AC line-to-line RMS voltage.
[DcLink Voltage]
Displays the measured DC Link Voltage.
[DcLink Ripple]
Displays the measured voltage ripple on the DC Link.
[V Imbalance]
Displays the voltage imbalance calculated between phases R, S, and T.
[Rated Power]
Displays the Converter’s rated power.
[AC Line kW]
Displays the power flowing to and from the AC Line. Positive values indicate power
is from the line. Negative values indicate power is returned to the line.
[Motoring kWh]
Displays the accumulated positive kWh. This parameter may be reset with
parameter 200 - [Reset Meters].
[Regen kWh]
Displays the accumulated negative kWh. This parameter may be reset with
parameter 200 - [Reset Meters].
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Group
File
Programming and Parameters
No.
Parameter Name & Description
Values
024
[Life Time kWh]
Displays the lifetime accumulated kWh. This parameter cannot be reset.
Default:
Read Only
Min/Max:
Units:
Default:
0.0/429496729.5
0.1 kWh
Read Only/Reset
Min/Max:
Units:
0.0000/429496.7295
0.0001 Hr
Default:
Read Only
Min/Max:
Units:
0.0000/429496.7295
0.0001 Hr
Default:
Read Only
Min/Max:
Units:
0.0000/429496.7295
0.0001 Hr
Default:
Read Only
Min/Max:
Units:
0/4294967295
None
Default:
Read Only
Min/Max:
Units:
Default:
-40.0/+150.0
0.1°C
Read Only
Min/Max:
Units:
Default:
-40.0/+150.0
0.1°C
Read Only
Min/Max:
Units:
Default:
-40.0/+150.0
0.1°C
Read Only
Min/Max:
Units:
Default:
0.0/90.0
0.1 Hz
Read Only
Min/Max:
Units:
0.0/90.0
0.1 Hz
Default:
Read Only
Min/Max:
Units:
0.0/90.0
0.1 Hz
Default:
10.0 Sec
Min/Max:
Units:
0.0/60.0 Sec
0.1 Sec
Default:
Read Only
Min/Max:
Units:
0.0/20.0
0.1 Hz/s
Power & Time
025
026
027
028
Temperature
031
032
040
041
Frequency
MONITOR
030
042
043
044
[Elapsed Run Time]
Displays the accumulated amount of time the Converter has been in run. This
parameter can be reset with parameter 200 - [Reset Meters].
[Life Run Time]
Displays the accumulated amount of time the Converter has been in run. This
parameter cannot be reset.
[Life Power Time]
Displays the accumulated amount of time the Converter has been powered up. This
parameter cannot be reset to zero.
[Life Pwr Cycles]
Displays the accumulated number of times the Converter has been powered up.
This parameter cannot be reset to zero.
[Ambient Temp]
Displays the measured ambient temperature of the Converter.
[IGBT Base Temp]
Displays the measured IGBT base temperature.
[IGBT Junction Temp]
Displays the calculated IGBT junction temperature.
[Line Frequency]
Displays the measured line frequency.
[Min Line Freq]
Latches and displays the minimum measured line frequency. The minimum is held
for the time set with parameter 43 - [Min Max Persist].
[Max Line Freq]
Latches and displays the maximum measured line frequency. The maximum is held
for the time set with parameter 43 - [Min Max Persist].
[Min Max Persist]
Sets the persistence time of the minimum and maximum measured line frequency.
A value of zero results in the minimum and maximum never being reset.
[Change Line Freq]
Displays the measured change in line frequency in Hz/sec.
3-5
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
3-6
Programming and Parameters
Group
File
Command File
No.
Parameter Name & Description
Values
050
[Start Config]
Selects the method by which the Active Converter is started.
Default:
0
“Run On Start”
Options:
0
1
2
“Run On Start”
“Run On PwrUp”
“Manual Cntrl”
“Run On Start” = The Converter is started when the Inverter is put into run or
jogged. The Enable Converter Bit 0 in parameter 70 - [Converter Control] is used
to operate the precharge and enable the Converter.
“Run On PwrUp” = The precharge is closed and the Converter is automatically
enabled as soon as power is turned on and synchronization has been
completed.
Prechg Cntrl
VC Inverter
Sim ModFreq
Sim ModIndex
PWM SyncRecv
PWM SyncXmit
Unbal V Comp
AutoPhaseRot
051
“Manual Cntrl” = The bits in parameter 52 - [Manual Control] are used to operate
the precharge bypass contactor and enable the Converter.
[Option Select]
A set of bits to enable and disable features in the Converter.
Default
x
x
x
0
0
0
0
0
0
0
1
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Bit
Definition
x
x
x
x
x
0 = Disabled
1 = Enabled
x = Reserved
• Bit 0 (AutoPhaseRot) – Enables the Converter to adapt to ABC or ACB phase rotation. When this bit is cleared the Converter
requires ABC rotation.
• Bit 2 (PWM SyncXmit) – Enables the Converter to transmit its PWM synchronization signal to other Converters.
Start / Stop
COMMAND
• Bit 1 (Unbal V Comp) – Enables unbalanced voltage compensation.
• Bit 3 (PWM SyncRecv) – Enables the Converter to receive a PWM synchronization signal. This bit must be turned off if no PWM
synchronization cable is installed. When synchronization is completed, a bit is set in parameter 071 - [Converter Status]. If
synchronization is not completed, a bit is set in parameter 214 - [Start Inhibit]. If synchronization is ever lost, an alarm is turned on
in parameter 211 - [Alarm Status]. Loss of synchronization may be configured to result in a fault if enabled in parameter 238 [Fault Config].
• Bit 4 (Sim ModIndex) – Enables the Converter modulation test. This feature requires a password to operate.
• Bit 5 (Sim Mod Freq) – Enables the Converter frequency simulator. This feature requires a password to operate.
• Bit 6 (VC Inverter) – This bit is used only when the Converter is operating as a Stand Alone unit and Bit 3 (PWM SyncRecv) is
enabled. This bit selects between synchronizing to an inverter with PowerFlex 700 Vector Control or PowerFlex 700S Phase II
Control. This bit must be set if the inverter has PowerFlex 700 Vector Control or must remain off if the inverter has PowerFlex 700S
Phase II Control. This bit is not used when the Converter is operating as a Coupled unit.
Enable Cnvtr
Close Prechg
052
• Bit 7 (Prechg Cntrl) – When Run On Start is selected in parameter 50 [Start Config] and this bit is turned off, then the precharge
bypass contactor is closed when the unit is put into run. When Run On Start is selected and this bit is turned on, then the
precharge bypass contactor is closed at power up after the DC link has reached steady state. This reduces the time delay
between putting the unit in run and the DC link reaching its regulated level.
[Manual Control]
A set of bits to manual start and stop the Converter. These bits are used only when parameter 50 - [Start Config] is set to “2” (Manual
Cntrl).
Default
x
x
x
x
x
x
x
x
x
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Bit
Definition
x
x
x
x
x
0 = Disabled
1 = Enabled
x = Reserved
• Bit 0 (Close Prechg) – Closes the precharge bypass contactor.
• Bit 1 (Enable Cnvtr) – Enables the converter voltage and current loops.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Parameter Name & Description
Values
053
[Turn Off Delay]
This parameter is used when parameter 50 - [Start Config] is set to “0” (Run On
Start) to select how long to keep the Converter enabled after the Inverter is
stopped.
[DcLink Reference]
Sets the reference for the DC Link voltage when parameter 160 - [Voltage Loop
Sel] is set to “1” (Manual Ref).
[kVAR Reference]
Sets the reference for the kVAR to produce. Positive values are a leading power
factor and negative values are a lagging power factor.
[Extern Cml Ref]
Sets the current reference as calculated by an external voltage loop. Values are
scaled so 4096 corresponds to Converter rated current.
[Modulation Index]
Sets the modulation duty cycle when parameter 51 - [Option Select] Bit 4 Sim
ModIndex is enabled and the Converter is started.
[Modulation Freq]
Sets the simulated line frequency when parameter 51 - [Option Select] Bit 5 Sim
ModFreq is enabled and the Converter is started.
[Converter Control]
A set of bits sent from the Inverter to control the Converter.
Default:
5.0 Sec
Min/Max:
Units:
1.0/60.0 Sec
0.1 Sec
Default:
Rated*1.46 Vdc
Min/Max:
Units:
300.0/1100.0 Vdc
0.1 Vdc
Default:
0.0 KVAR
Min/Max:
Units:
–3000.0/+3000.0 KVAR
0.1 KVAR
Default:
0
Min/Max:
Units:
–8192/+8192
None
Default:
0.0%
Min/Max:
Units:
0.0/100.0%
0.1%
Default:
0.0 Hz
Min/Max:
Units:
0.0/60.0 Hz
0.1 Hz
060
Setpoints
061
062
COMMAND
063
064
Data Exchange
070
Enable Cnvtr
No.
700VC Invtr
Start / Stop Group
File
Programming and Parameters
Default
x
x
x
x
x
x
x
x
x
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Bit
Definition
x
x
x
x
x
3-7
0 = Disabled
1 = Enabled
x = Reserved
• Bit 0 (Enable Cnvtr) – This bit is set by the Inverter when the drive is started. When parameter 50 - [Start Config] is set to “0” (Run
on Start), setting this bit closes the precharge bypass and enables the Converter voltage and current loops.
• Bit 1 (700VC Invtr) – This bit is set when the Active Converter is communicating with an Inverter that has 700 Vector Control. It is
cleared when communicating with an Inverter that has 700S Phase II Control.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Programming and Parameters
Active I Lmt
Ac Ride Thru
Bus Reg Ena
Cnvtr Active
Prechg Closed
Ac Line Sync
Cnvtr Ready
0
0
0
0
0
0
0
0
0
0
0
0
Cnvtr Alarm
kVAR Lmt
[Converter Status]
A set of bits sent from the Converter to the Inverter to indicate status.
Regenerating
071
PWM SyncLock
Values
CML Comm Ok
Parameter Name & Description
Abort Decel
No.
Cnvtr Fault
Group
File
3-8
Default
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Bit
Definition
x
x
Read Only
0 = Disabled
1 = Enabled
x = Reserved
• Bit 0 (Cnvtr Ready) is set by the Converter when all inhibits are cleared.
• Bit 1 (Ac Line Sync) is set by the Converter when it is synchronized to the AC line.
• Bit 2 (Pchg Closed) indicates the status of the precharge bypass contactor.
• Bit 3 (Cnvtr Active) is set by the Converter when it is regulating.
• Bit 5 (Ac Ride Thru) is set by the Converter during a power dip ride through.
Data Exchange
COMMAND
• Bit 4 (Bus Reg Ena) is set by the Converter to enable the Inverter bus voltage regulator.
• Bit 6 (Active I Lmt) is set by the Converter when active current is limited.
• Bit 7 (kVAR Lmt) is set by the Converter when the requested KVAR is limited.
• Bit 8 (Regenerating) is set by the Converter when it is regenerating power to the AC line.
• Bit 9 (PWM SyncLock) is set by the Converter when the PWM carrier is locked to the external synchronization signal.
• Bit 10 (CML Comm Ok) is set by the Converter when a valid External CML reference is received.
• Bit 11 (Abort Decel) is set when the DC link drops below the voltage when the precharge must open. This signals the Inverter to
stop regulating the bus voltage by decelerating the motor and beginning a coast to stop.
• Bit 14 (Cnvtr Alarm) is set by the Converter when it has detected an alarm.
072
073
• Bit 15 (Cnvtr Fault) is set by the Converter when it has detected a fault.
[Converter Min Vdc]
Sets the minimum DC Link voltage required by the Inverter for the present
operating conditions. This value is calculated as (motor voltage * 1.44) and then
transferred to the Converter by Type 3 communication. This is used when the
voltage to the motor needs to be greater than the peak of the AC line voltage.
Under low line conditions, the Converter can boost the DC Link voltage above
the peak of the AC line.
[Converter Fault]
This parameter is used to pass a fault code from the Converter to the Inverter so
all Converter fault codes are logged in the Inverter’s fault queue.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Default:
0.0 Vdc
Min/Max:
Units:
0.0/1225.0 Vdc
0.1 Vdc
Default:
0
Min/Max:
Units:
0/399
None
Programming and Parameters
3-9
Group
File
Limit Config File
No.
Parameter Name & Description
Values
100
[Active I Lmt]
Sets the current limit used when the IGBT overload is less than 90% of the IT
fault threshold.
[Active OL I Lmt]
Sets the current limit used when the IGBT overload is more than 90% of the IT
fault threshold, and parameter 150 - [Reduce Ilmt Sel] is set to “1” (enabled).
[Reactive RateLmt]
Sets how fast reactive current will change.
Default:
Rated * 1.5 Amps
Min/Max:
Units:
Rated ÷ 4/Rated*1.5 Amps
0.1 Amps
Default:
Rated * 0.9 Amps
Min/Max:
Units:
Rated ÷ 4/Rated*1.5 Amps
0.1 Amps
Default:
100.0 A/sec
Min/Max:
Units:
Default:
10.0/3000.0 A/sec
0.1 A/sec
30.0%
Min/Max:
Units:
1.0/90.0%
0.1%
Default:
10.0 Sec
Min/Max:
Units:
1.0/10.0 Sec
0.1 Sec
Default:
-150.0%
Min/Max:
Units:
-150.0/0.0%
0.1%
Default:
0
“Disabled”
Options:
0
1
“Disabled”
“Enabled”
Default:
10.0 Sec
Min/Max:
Units:
0.1/600.0 Sec
0.1 Sec
Default:
340.0 Vac
Min/Max:
Units:
200.0/800.0 Vac
0.1 Vac
Default:
5.0 Sec
Min/Max:
Units:
0.1/30.0 Sec
0.1 Sec
Default:
Rated*1.1 Vac
Min/Max:
Units:
400.0/810.0 Vac
0.1 Vac
Default:
5.0 Sec
Min/Max:
Units:
0.1/30.0 Sec
0.1 Sec
Default:
10.0%
Min/Max:
Units:
1.0/20.0%
0.1%
101
Current
102
103
104
105
LIMIT CONFIG
110
[I Imbalance Lmt]
Sets the limit on phase current imbalance. A fault is generated if the calculated
imbalance is greater than this limit for the time defined in parameter 104 [I Imbalance Time].
[I Imbalance Time]
Sets the time delay in faulting on current imbalance between phases. A fault is
generated if the calculated imbalance is greater than the limit set by parameter
103 - [I Imbalance Lmt] for this amount of time.
[Regen I Lmt]
Sets the maximum phase current the unit will request when regenerating. Values
are entered as a percent of converter rated current. When the converter goes
into current limit while regenerating, the DC link will go up and the unit may fault
on DC Over Voltage if the condition is not externally corrected.
[Ride Through Ena]
Selects the options for power dip ride through.
“Disabled” = The Converter will fault on loss of AC line voltage and will not
automatically attempt to restart when power returns.
111
AC Line Voltage
112
113
114
115
116
“Enabled” = The Converter will enter Standby Mode, and wait for the AC line
voltage to return, and then automatically resume operation. If power is not
restored within the time defined in parameter 111 - [Ride Through Sec], a fault is
generated.
[Ride Through Sec]
Selects the longest power dip that will be allowed providing DC link voltage can
be maintained.
[Low Vac Lmt]
Sets the low limit on AC Line voltage. A fault or alarm may be generated when
the AC Line voltage is less than this limit for the time set by parameter 113 - [Low
Vac Time].
[Low Vac Time]
Sets the time delay in detecting low AC Line voltage. A fault or alarm may be
generated when the AC Line voltage is less than the limit set by parameter 112 [Low Vac Lmt] for this amount of time.
[High Vac Lmt]
Sets the high limit on AC Line voltage. A fault or alarm may be generated when
the AC Line voltage is greater than this limit for the time set by parameter 115 [High Vac Time].
[High Vac Time]
Sets the time delay in detecting high AC Line voltage. A fault or alarm may be
generated when the AC Line voltage is greater than the limit set by parameter
114 - [High Vac Lmt] for this amount of time.
[V Imbalance Lmt]
Sets the limit on voltage imbalance between phases. A fault or alarm may be
generated if the calculated imbalance is greater than this limit for the time set by
parameter 117 - [V Imbalance Time].
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Programming and Parameters
AC Line Voltage Group
File
3-10
No.
Parameter Name & Description
117
Default:
[V Imbalance Time]
Sets the time delay in detecting a voltage imbalance between phases. A fault or Min/Max:
alarm may be generated if the calculated imbalance is greater than the limit set Units:
by parameter 116 - [V Imbalance Limit] for this amount of time.
1.0 Sec
[Ambnt Temp Alrm]
Sets the alarm threshold for the maximum ambient temperature.
Default:
60.0°C
Min/Max:
Units:
Default:
30.0/105.0°C
0.1°C
Read Only
Min/Max:
Units:
Default:
40.0/150.0
0.1°C
70.0°C
Min/Max:
Units:
Default:
30.0/125.0°C
0.1°C
Read Only
Min/Max:
Units:
Default:
75.0/160.0
0.1°C
85.0°C
Min/Max:
Units:
Default:
75.0/150.0°C
0.1°C
Read Only
Min/Max:
Units:
75.0/175.0
120
121
Temperature
122
123
124
LIMIT CONFIG
125
126
130
Frequency
131
132
133
134
135
[Ambnt Temp Trip]
Displays the fault threshold for the maximum ambient temperature.
[Base Temp Alrm]
Sets the alarm threshold for the maximum IGBT base temperature.
[Base Temp Trip]
Displays the fault threshold for the maximum IGBT base temperature.
[Junct Temp Alrm]
Sets the alarm threshold for the maximum IGBT junction temperature.
[Junct Temp Trip]
Displays the fault threshold for the maximum IGBT junction temperature.
[CldPlt Temp Alrm]
Sets the alarm threshold for the minimum coldplate temperature.
[PWM Frequency]
Sets the PWM carrier frequency. The value is entered in kHz. When the power
structure allows more than one setting for the carrier frequency, the power must
be cycled off/on to have the new value take effect.
[AC Low Freq Lmt]
Sets the low frequency limit used by parameter 132 - [AC Low Freq Time].
[AC Low Freq Time]
Sets how long the line frequency must be less than the limit set by parameter
131 - [AC Low Freq Lmt] before a fault is generated.
[AC High Freq Lmt]
Sets the high frequency limit used by parameter 134 - [AC High Freq Time].
[AC High Freq Time]
Sets how long the line frequency must be greater than the limit set by parameter
133 - [AC High Freq Lmt] before a fault is generated.
[AC Maximum dF/dt]
Sets the maximum dF/dt that the AC converter will allow. A change in frequency
greater than this may generate a fault.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Values
1.0/10.0 Sec
0.1 Sec
Default:
0.1°C
40.0°C
Min/Max:
Units:
Default:
10.0/80.0°C
0.1°C
Rated kHz
Min/Max:
Units:
Set by the power structure
1 kHz
Default:
29.0 Hz
Min/Max:
Units:
Default:
27.0/93.0 Hz
0.1 Hz
5.0 Sec
Min/Max:
Units:
0.1/10.0 Sec
0.1 Sec
Default:
91.0 Hz
Min/Max:
Units:
Default:
27.0/93.0 Hz
0.1 Hz
5.0 Sec
Min/Max:
Units:
0.1/10.0 Sec
0.1 Sec
Default:
10.0 Hz/sec
Min/Max:
Units:
0.1/30.0 Hz/sec
0.1 Hz/sec
Programming and Parameters
3-11
Group
File
Dynamic Control File
No.
Parameter Name & Description
Values
150
[Reduce Ilmt Sel]
Enables the use of a reduced current limit when in overload.
Default:
1
“Disabled”
Options:
0
1
“Disabled”
“Enabled”
“Disabled” = The Converter current limit is always the value in parameter 100 [Active I Lmt].
151
152
DYNAMIC CONTROL
Current Loop
153
154
155
156
157
158
159
160
“Enabled” = The Converter current limit will switch to the value set by parameter
101 - [Active OL I Lmt] when in overload.
Default:
[Active I Cmd]
Min/Max:
Displays the commanded active current.
[Inductance]
Sets the input filter inductance. When set to non-zero, this value is used to
calculate the tuning coefficients for the current loop CML Ki and Kp.
[CML Bandwidth]
Sets the Current Minor Loop bandwidth. When set to non-zero, this value is
used to calculate the tuning coefficients for the current loop CML Ki and Kp.
[CML Damping]
Sets the Current Minor Loop damping. When set to non-zero, this value is used
to calculate the tuning coefficients for the current loop CML Ki and Kp.
[CML Ki]
Tunes the integral gain of the current loop.
[CML Kp]
Tunes the proportional gain of the current loop.
[PF Bandwidth]
Sets the bandwidth of the current regulator maintaining the desired power factor.
This is used only when parameter 051 - [Option Select] Bit 1 (Unbal V Comp) is
set to "1" to enable unbalanced voltage compensation.
[Reactive I Lmt]
Displays the calculated reactive current limit.
[Reactive I Cmd]
Displays the commanded reactive current.
[Voltage Loop Sel]
Selects the operation of the voltage loop.
Units:
Default:
-3276.7/+3276.7
0.1 Amps
Rated µH
Min/Max:
Units:
0/32767 µH
1 µH
Default:
1500 Rad/sec
Min/Max:
Units:
0/4000 Rad/sec
1 Rad/sec
Default:
1.6
Min/Max:
Units:
0.5/5.0
None
Default:
Drive Size Dependent
Min/Max:
Units:
Default:
0/32767
None
Drive Size Dependent
Min/Max:
Units:
Default:
0/32767
None
Drive Size Dependent
Min/Max:
Units:
0/4000
None
Default:
Read Only
Min/Max:
Units:
Default:
0.0/3000.0
0.1 Amps
Read Only
Min/Max:
Units:
Default:
-3000.0/+3000.0
0.1 Amps
0
“Optimize Ref”
Options:
0
1
2
3
“Optimize Ref” = Vdc reference is calculated to minimize switching losses,
based on the measured AC Line voltage and the minimum voltage required by
the Inverter.
Voltage Loop
Read Only
“Optimize Ref”
“Manual Ref”
“Regen Only”
“Open Loop”
“Manual Ref” = The value set by parameter 060 - [DcLink Reference] is used for
Vdc reference.
“Regen Only” = Reserved for future.
161
“Open Loop” = The Converter outputs a sinusoidal voltage synchronized to the
AC line with an amplitude set by parameter 063 - [Modulation Index]. This
feature requires a password to operate.
Default:
[DcLink Command]
Min/Max:
Displays the commanded DC Link voltage.
Units:
Read Only
0.0/1225.0
0.1 Vdc
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Programming and Parameters
Group
File
3-12
No.
Parameter Name & Description
Values
162
[Capacitance]
Sets the DC Link capacitance. When set to non-zero, this value is used to
calculate the tuning coefficients for the voltage loop VML Ki and Kp. In the case
of a Frame 2 or Frame 3A drive, this is the capacitance inside the drive. In the
case of a Frame 3B drive, it is the capacitance in the Converter and one Inverter.
The capacitance of any additional Inverters connected to a common bus must
be entered in parameter 170 - [Bus Capacitance].
[VML Bandwidth]
Sets the Voltage Major Loop bandwidth. When set to non-zero, this value is
used to calculate the tuning coefficients for the voltage loop VML Ki and Kp.
[VML Damping]
Sets the Voltage Major Loop damping. When set to non-zero, this value is used
to calculate the tuning coefficients for the voltage loop VML Ki and Kp.
[VML Ki]
Tunes the integral gain of the voltage loop.
Default:
Rated µF
Min/Max:
Units:
0/65535 µF
1 µF
Default:
400 Rad/sec
Min/Max:
Units:
0/800 Rad/sec
1 Rad/sec
Default:
1.6
Min/Max:
Units:
0.5/5.0
None
Default:
Drive Size Dependent
Min/Max:
Units:
Default:
0/32767
None
Drive Size Dependent
Min/Max:
Units:
Default:
0/32767
None
0
Min/Max:
Units:
Default:
0/32767
None
60.0 Vdc
Min/Max:
Units:
Default:
10.0/300.0 Vdc
0.1 Vdc
“Stand Alone”
0
Options:
0
1
2
3
4
0 µF
163
165
Voltage Loop
DYNAMIC CONTROL
164
166
167
168
169
170
[VML Kp]
Tunes the proportional gain of the voltage loop.
[VML Kf]
Tunes the feed forward gain of the voltage loop.
[VML Reset Level]
Sets the voltage error when to reset the integrator.
[Parallel Config]
Reserved for future.
Default:
[Bus Capacitance]
Min/Max:
Sets the additional capacitance connected to the DC link in a common bus
application. This value, in addition to the value of parameter 162 - [Capacitance], Units:
sets the tuning coefficient for the voltage loop VML Ki and Kp.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
“Stand Alone”
“Master of 1”
“Master of 2”
“Master of 3”
“Follower”
0/2000000000 µF
1 µF
Programming and Parameters
3-13
No.
Parameter Name & Description
Values
196
[Param Access Lvl]
Selects which parameters are accessible by the HIM.
“Basic” = A minimal subset of parameters are accessible on the HIM.
“Advanced” = All parameters are accessible on the HIM.
[Reset to Defaults]
Resets all values in the Converter to the factory defaults.
“Ready” = A new value may be entered.
“Factory” = Parameters are reset.
[Reset Meters]
Resets the elapsed kWh and run time parameters to zero.
Default:
0
“Basic”
Options:
0
1
“Basic”
“Advanced”
Default:
0
“Ready”
Options:
0
1
“Ready”
“Factory”
Default:
0
“Ready”
Options:
0
1
2
“Ready”
“kWh”
“Elapsed Time”
Default:
0
“Not Selected”
Options:
Default:
“Not Selected”
0
“English”
1
“French”
2
“Spanish”
3
“Italian”
4
“German”
5
“Portuguese”
7
“Dutch”
10
Read Only
Min/Max:
Units:
0/65535
None
Default:
Read Only
Min/Max:
Units:
Default:
0/65.535
None
0
Min/Max:
Units:
0/65535
None
Read Only
Diagnostic
Ac High Freq
Ac Low Freq
Ac High Volt
Ac Low Volt
x
0
0
0
0
0
0
0
0
0
0
0
0
0
Default
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
•
•
•
•
•
•
•
•
•
•
•
•
•
•
x
Ac High dFdt
Bit
Definition
I Imbalance
[Alarm Status]
A set of bits displaying the alarms active in the Converter.
V Imbalance
211
[Password]
Value entered here to enable protected feature.
IT Overload
205
Ambient Temp
UTILITY
204
[Drive Checksum]
Displays the checksum of all the parameters in the Converter. This provides a quick way
to know if any parameter has been changed.
[Control SW Ver]
Displays the software version of the Converter.
Base Temp
203
Junction Temp
201
“Ready” = A new value may be entered.
“kWh” = The kWh accumulators are reset to zero.
“Elapsed Time” = The Time accumulators are reset to zero.
[Language]
Selects the language in which all text is displayed.
Coldplate Temp
Drive Memory
200
PWM SyncLoss
197
Start Inhibit
Group
File
Utility File
0 = Disabled
1 = Enabled
x = Reserved
Bit 0 (Ac Low Volt) is set when the average AC line voltage is less than the limit in parameter 112 - [Low Vac Lmt].
Bit 1 (Ac High Volt) is set when the average AC line voltage exceeds the limit in parameter 114 - [High Vac Lmt].
Bit 2 (Ac Low Freq) is set when the AC line frequency is less than the limit in parameter 131 - [AC Low Freq Lmt].
Bit 3 (Ac High Freq) is set when the AC line frequency exceeds the limit in parameter 133 - [AC High Freq Lmt].
Bit 4 (Ac High dFdt) is set when the AC line frequency is changing faster than the limit in parameter 135 - [AC Maximum dF/dt].
Bit 5 (I Imbalance) is set when the phase current imbalance exceeds the limit in parameter 103 - [I Imbalance Lmt].
Bit 6 (V Imbalance) is set when the phase voltage imbalance is greater than the limit in parameter 116 - [V Imbalance Lmt].
Bit 7 (IT Overload) is set when the overload counter is greater than 90%.
Bit 8 (Ambient Temp) is set when the ambient temperature exceeds the limit in parameter 120 - [Ambnt Temp Alrm].
Bit 9 (Base Temp) is set when the IGBT base temperature exceeds the limit in parameter 122 - [Base Temp Alrm].
Bit 10 (Junction Temp) is set when the IGBT junction temperature exceeds the limit in parameter 124 - [Junct Temp Alrm].
Bit 11 (Coldplate Temp) is set when the coldplate temperature is less than the limit in parameter 126 - [CldPlt Temp Alrm].
Bit 12 (PWM SyncLoss) is set when PWM carrier synchronization is lost.
Bit 15 (Start Inhibit) is set when one or more start inhibits are present.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Programming and Parameters
Phased ACB
Single Phase
Ac High Freq
Ac Low Freq
Ac High Volt
Ac Low Volt
x
DC Link Low
x
High dv/dt
x
Pchg Open
[Start Inhibit]
A set of bits displaying the interlocks that inhibit the Converter from starting.
PWM Not Sync
214
Bit
Definition
Values
Reqst Maintd
Parameter Name & Description
High DC Link
No.
Faulted
Group
File
3-14
0
0
0
0
0
0
0
0
0
0
0
0
Default
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Read Only
0 = Disabled
1 = Enabled
x = Reserved
Diagnostic
UTILITY
•
•
•
•
•
•
220
221
222
223
224
225
226
227
228
229
Bit 0 (Ac Low Volt) is set when the average AC line voltage is less than the limit in parameter 112 - [Low Vac Lmt].
Bit 1 (Ac High Volt) is set when the average AC line voltage exceeds the limit in parameter 114 - [High Vac Lmt].
Bit 2 (Ac Low Freq) is set when the AC line frequency is less than the limit in parameter 131 - [AC Low Freq Lmt].
Bit 3 (Ac High Freq) is set when the AC line frequency exceeds the limit in parameter 133 - [AC High Freq Lmt].
Bit 4 (Single Phase) is set when an input phase is missing.
Bit 5 (Phased ACB) is set when an input phase voltage is phased ACB and parameter 051 - [Option Select] Bit 0 (AutoPhaseRot)
is not enabled.
• Bit 6 (DC Link Low) is set when DC Link voltage is too low to close the precharge bypass contactor.
• Bit 7 (High dv/dt) is set when DC Link dv/dt is too high to close the precharge bypass contactor.
• Bit 8 (Pchg Open) is set when the precharge bypass contactor is open and manual sequencing is selected.
• Bit 9 (PWM Not Sync) is set when Par 051 - [Option Select] Bit 3 (PWM SyncRecv) is turned on and synchronization is not completed.
• Bit 10 (Reqst Maintd) is set after a fault if the enable is not turned off. Restart requires a rising edge.
• Bit 11 (High DC Link) is set when Run On PwrUp is selected in parameter 50 - [Start Config] and the DC Link is greater than
1.44 times the value in parameter 114 - [High Vac Lmt]. On a 480 volt unit, parameter 114 - [High Vac Lmt] defaults to “528” so
inhibit Bit 11 (High DC Link) defaults to 760 volts.
• Bit 15 (Faulted) is set when the Converter is faulted.
Default:
Read Only
[Fault Frequency]
Min/Max: 0.0/100.0
Displays the AC line frequency at the time of the fault.
[Fault Amps R]
Displays phase R peak current at the time of the fault.
[Fault Amps S]
Displays phase S peak current at the time of the fault.
[Fault Amps T]
Displays phase T peak current at the time of the fault.
[Fault Amps Q]
Displays the real current at the time of the fault.
[Fault Amps D]
Displays the reactive current at the time of the fault.
[Fault Volts RS]
Displays the RMS line-to-line voltage between phase R and S at the time of the fault.
[Fault Volts ST]
Displays the RMS line-to-line voltage between phase S and T at the time of the fault.
[Fault Volts TR]
Displays the RMS line-to-line voltage between phase T and R at the time of the fault.
[Fault Volts Vdc]
Displays the DC Link voltage at the time of the fault.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Units:
Default:
0.1 Hz
Read Only
Min/Max:
Units:
Default:
-3276.7/+3276.7
0.1 Amps
Read Only
Min/Max:
Units:
Default:
-3276.7/+3276.7
0.1 Amps
Read Only
Min/Max:
Units:
Default:
-3276.7/+3276.7
0.1 Amps
Read Only
Min/Max:
Units:
Default:
-3276.7/+3276.7
0.1 Amps
Read Only
Min/Max:
Units:
Default:
-3276.7/+3276.7
0.1 Amps
Read Only
Min/Max:
Units:
Default:
0.0/3276.7
0.1 Vac
Read Only
Min/Max:
Units:
Default:
0.0/3276.7
0.1 Vac
Read Only
Min/Max:
Units:
Default:
0.0/3276.7
0.1 Vac
Read Only
Min/Max:
Units:
0.0/3276.7
0.1 Vdc
No.
Parameter Name & Description
Values
230
[Fault Base Temp]
Displays the IGBT base temperature at the time of the fault.
Default:
Read Only
Min/Max:
Units:
Default:
-40.0/+150.0
0.1°C
499
Min/Max:
Units:
Default:
0/65535
1
Read Only
Min/Max:
Units:
Default:
-2147483647/+2147483647
1
499
Min/Max:
Units:
Default:
0/65535
1
Read Only
Min/Max:
Units:
-2147483647/+2147483647
1
Ac Low Freq
Ac High Volt
Ac Low Volt
Default
x
x
1
0
1
1
0
1
1
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Fault Queue
UTILITY
Bit
Definition
239
242
243
244
245
246
3-15
[Fault Config]
A set of bits that select which conditions may generate faults.
Ac High Freq
238
[Testpoint 2 Data]
Displays the data selected in parameter 236 - [Testpoint 2 Sel].
High dFdt
237
[Testpoint 2 Sel]
Allows for access to other test points in the system.
I Imbalance
236
[Testpoint 1 Data]
Displays the data selected in parameter 234 - [Testpoint 1 Sel].
V Imbalance
235
[Testpoint 1 Sel]
Allows for access to other test points in the system.
PWM SyncLost
Diagnostic
234
Inverter Flt
Group
File
Programming and Parameters
x
x
x
x
x
0 = Disabled
1 = Enabled
x = Reserved
• Bit 0 (Ac Low Volt) – When this bit is set, low AC line voltage will generate a fault.
• Bit 1 (Ac High Volt) – When this bit is set, high AC line voltage will generate a fault.
• Bit 2 (Ac Low Freq) – When this bit is set, low AC line frequency will generate a fault.
• Bit 3 (Ac High Freq) – When this bit is set, high AC line frequency will generate a fault.
• Bit 4 (High dFdt) – When this bit is set, high dF/dt will generate a fault.
• Bit 5 (I Imbalance) – When this bit is set, high current imbalance will generate a fault.
• Bit 6 (V Imbalance) – When this bit is set, high voltage imbalance will generate a fault.
• Bit 7 (PWM SyncLost) – When this bit is set, loss of PWM synchronization will generate a fault.
• Bit 8 (Inverter Flt) – When this bit is set, a fault in the Inverter will fault the Converter.
Default:
[Fault Clear]
Options:
Resets faults and clears the fault queue.
“Ready” = A new value may be entered.
“Clear Faults” = A fault is reset.
“Clr Fault Que” = The fault queue is cleared.
Default:
[Power Up Marker]
Displays the elapsed time at power up. This is used to know if a fault occurred since the Min/Max:
Units:
last time power was applied.
Default:
[Fault 1 Code]
Min/Max:
Displays the most recent fault code detected.
[Fault 1 Time]
Displays the time stamp for the most recent fault detected.
[Fault 2 Code]
Displays the most second recent fault code detected.
[Fault 2 Time]
Displays the time stamp for the most second recent fault detected.
0
“Ready”
0
1
2
“Ready”
“Clear Faults”
“Clr Fault Que”
Read Only
0.0000/429496.7295
0.0001 Hrs
Read Only
Units:
Default:
0/65535
0
Read Only
Min/Max:
Units:
Default:
0.0000/429496.7295
0.0001 Hrs
Read Only
Min/Max:
Units:
Default:
0/65535
0
Read Only
Min/Max:
Units:
0.0000/429496.7295
0.0001 Hrs
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Programming and Parameters
No.
Parameter Name & Description
Values
247
[Fault 3 Code]
Displays the most third recent fault code detected.
Default:
Read Only
Min/Max:
Units:
Default:
0/65535
0
Read Only
Min/Max:
Units:
Default:
0.0000/429496.7295
0.0001 Hrs
Read Only
Min/Max:
Units:
Default:
0/65535
0
Read Only
Min/Max:
Units:
0.0000/429496.7295
0.0001 Hrs
I Imbalance
Ac High dFdt
Ac High Freq
Ac Low Freq
Ac High Volt
Ac Low Volt
x
V Imbalance
x
IT Overload
Fault Queue
UTILITY
Bit
Definition
Ambient Temp
[Alarm Config]
A set of bits to enable/disable alarm conditions that will initiate a Converter alarm.
Base Temp
260
[Fault 4 Time]
Displays the time stamp for the most fourth recent fault detected.
Junction Temp
250
[Fault 4 Code]
Displays the most fourth recent fault code detected.
Coldplate Temp
249
[Fault 3 Time]
Displays the time stamp for the most third recent fault detected.
PWM SyncLoss
248
Start Inhibit
Group
File
3-16
1
0
1
1
1
1
1
1
1
1
1
1
1
Default
1
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = Disabled
1 = Enabled
x = Reserved
• Bit 0 (Ac Low Volt) sets an alarm when the average AC line voltage is less than the limit in parameter 112 - [Low Vac Lmt].
• Bit 1 (Ac High Volt) sets an alarm when the average AC line voltage exceeds the limit in parameter 114 - [High Vac Lmt].
• Bit 2 (Ac Low Freq) sets an alarm when the AC line frequency is less than the limit in parameter 131 - [AC Low Freq Lmt].
• Bit 3 (Ac High Freq) sets an alarm when the AC line frequency exceeds the limit in parameter 133 - [AC High Freq Lmt].
• Bit 4 (Ac High dFdt) sets an alarm when the AC line frequency is changing faster than the limit in parameter 135 - [AC Maximum
dF/dt].
• Bit 5 (I Imbalance) sets an alarm when the phase current imbalance exceeds the limit in parameter 103 - [I Imbalance Lmt].
• Bit 6 (V Imbalance) sets an alarm when the phase voltage imbalance is greater than the limit in parameter 116 - [V Imbalance
Lmt].
• Bit 7 (IT Overload) sets an alarm when the Overload counter is greater than 90%.
• Bit 8 (Ambient Temp) sets an alarm when the ambient temperature exceeds the limit in parameter 120 - [Ambnt Temp Alrm].
• Bit 9 (Base Temp) sets an alarm when the IGBT base temperature exceeds the limit in parameter 122 - [Base Temp Alrm].
• Bit 10 (Junction Temp) sets an alarm when the IGBT junction temperature exceeds the limit in parameter 124 - [Junct Temp
Alrm].
• Bit 11 (Coldplate Temp) sets an alarm when the coldplate temperature is less than the limit in parameter 126 - [CldPlt Temp
Alrm].
• Bit 12 (PWM SyncLoss) sets an alarm when PWM carrier synchronization is lost.
• Bit 15 (Start Inhibit) sets an alarm when one or more start inhibits are present.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Programming and Parameters
3-17
[Data In A1] - Link A Word 1
[Data In A2] - Link A Word 2
Parameter number whose value will be written from a communications device data
table.
[Data In B1] - Link B Word 1
[Data In B2] - Link B Word 2
Parameter number whose value will be written from a communications device data
table.
[Data In C1] - Link C Word 1
[Data In C2] - Link C Word 2
Parameter number whose value will be written from a communications device data
table.
[Data In D1] - Link D Word 1
[Data In D2] - Link D Word 2
Parameter number whose value will be written from a communications device data
table.
[Data Out A1] - Link A Word 1
[Data Out A2] - Link A Word 2
Parameter number whose value will be written to a communications device data table.
[Data Out B1] - Link B Word 1
[Data Out B2] - Link B Word 2
Parameter number whose value will be written to a communications device data table.
[Data Out C1] - Link C Word 1
[Data Out C2] - Link C Word 2
Parameter number whose value will be written to a communications device data table.
[Data Out D1] - Link D Word 1
[Data Out D2] - Link D Word 2
Parameter number whose value will be written to a communications device data table.
[Connect Status]
A set of bits displaying which DPI communication types are in use by the Converter.
Default:
0 (0 = “Disabled”)
Min/Max:
Units:
0/399
1
Default:
0 (0 = “Disabled”)
Min/Max:
Units:
0/399
1
Default:
0 (0 = “Disabled”)
Min/Max:
Units:
0/399
1
Default:
0 (0 = “Disabled”)
Min/Max:
Units:
0/399
1
Default:
0 (0 = “Disabled”)
Min/Max:
Units:
0/399
1
Default:
0 (0 = “Disabled”)
Min/Max:
Units:
0/399
1
Default:
0 (0 = “Disabled”)
Min/Max:
Units:
0/399
1
Default:
0 (0 = “Disabled”)
Min/Max:
Units:
0/399
1
Datalinks
304
305
306
307
310
311
312
313
COMMUNICATION
314
315
316
317
320
Default
x
x
x
0
0
0
0
0
x
x
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Bit
Definition
x
x
x
x
x
Read Only
Type 0
302
303
Type 3
300
301
Type 4
Values
Type 5
Parameter Name & Description
Type 6
No.
Type 7
Group
File
Communication File
0 = Disabled
1 = Enabled
x = Reserved
• Bit 0 (Type 0) is set when Type 0 PC is connected.
• Bit 3 (Type 3) is set when Type 3 PC is connected.
• Bit 4 (Type 4) is set when Type 4 PC is connected.
DPI Status
• Bit 5 (Type 5) is set when Type 5 PC is connected.
• Bit 6 (Type 6) is set when Type 6 PC is connected.
321
322
323
324
• Bit 7 (Type 7) is set when Type 7 PC is connected.
[DPI Error Out]
Displays a counter that increments on a DPI error.
[CS Msg Rx Cnt]
Displays a counter that increments on a Client Server message received.
[CS Msg Tx Cnt]
Displays a counter that increments on a Client Server message transmitted.
[CS Timeout Cnt]
Displays a counter that increments on a Client Server message time out.
Default:
Read Only
Min/Max:
Units:
Default:
0/255
None
Read Only
Min/Max:
Units:
Default:
0/65535
None
Read Only
Min/Max:
Units:
Default:
0/65535
None
Read Only
Min/Max:
Units:
0/255
None
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Programming and Parameters
No.
Parameter Name & Description
Values
325
[CS Msg Bad Cnt]
Displays a counter that increments on a bad Client Server message.
Default:
Read Only
Min/Max:
Units:
Default:
0/255
None
Read Only
Min/Max:
Units:
Default:
0/65535
None
Read Only
Min/Max:
Units:
Default:
0/65535
None
Read Only
Min/Max:
Units:
Default:
0/255
None
Read Only
Min/Max:
Units:
0/65535
None
[Logic Mask]
Determines which ports can control the drive when parameter 348 - [Write Mask Act] Bit 15
is set to “1.” If the bit for a port is set to “0,” the port will have no control functions except for stop.
DPI Port 1
340
[CAN Bus Off Cnt]
Displays a counter that increments on when the CAN Bus is turned off.
DPI Port 2
329
[PC Timeout Cnt]
Displays a counter that increments on a Producer Consumer message time out.
DPI Port 3
328
[PC Msg Tx Cnt]
Displays a counter that increments on a Producer Consumer message transmitted.
DPI Port 4
327
[PC Msg Rx Cnt]
Displays a counter that increments on a Producer Consumer message received.
DPI Port 5
DPI Status
326
DPI Port 6
Group
File
3-18
Default
x
x
x
x
1
1
1
1
1
1
x
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
341
x
x
x
x
x
[Fault Clr Mask]
Controls which adapters can clear a fault.
343
[Stop Owner]
Displays adapters that are presently issuing a valid stop command.
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
x
x
x
0
0
0
0
0
0
x
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
x
x
x
x
x
0 = No Command
1 = Issuing Command
x = Reserved
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Host
[Start Owner]
Displays adapters that are presently issuing a valid start command.
[Fault Clr Owner]
Displays adapters that are presently clearing a fault.
[Port Mask Act]
Bits 0-6 indicate status for DPI port communication.
Bit 15 indicates when security software is controlling the parameter.
DPI Port 6
346
Read Only
x
Default
0
x
x
x
1
1
1
1
1
1
1
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Bit
Definition
Security
345
See [Logic Mask].
Default
Bit
Definition
Security (1)
See [Logic Mask].
342
344
0 = Control Masked
1 = Control Permitted
x = Reserved
The drive must be stopped to change this parameter.
[Start Mask]
Controls which adapters can issue start commands.
DPI Port 6
Masks & Owners (1)
COMMUNICATION
Bit
Definition
x
x
x
x
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
x
See [Stop Owner].
See [Stop Owner].
Read Only
0 = Not Active
1 = Active
x = Reserved
DPI Port 2
DPI Port 1
[Write Mask Cfg]
Enables/disables write access of parameters for DPI ports. Changes to this parameter only become
effective when power is cycled, the drive is reset, or Bit 15 of parameter 348 - [Write Mask Act]
transitions from “1” to “0.”
DPI Port 3
347
Default
x
x
x
x
1
1
1
1
1
1
x
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
x
x
DPI Port 6
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
0
x
x
x
1
1
1
1
1
1
x
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Security
Default
0 = Read Only
1 = Write Permitted
x = Reserved
x
x
x
x
x
Read Only
0 = Read Only
1 = Write Permitted
x = Reserved
DPI Port 6
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Read Only
[Logic Mask Act]
Indicates status of the logic mask for DPI ports. When Bit 15 is set, network security is controlling
the logic mask instead of parameter 340 - [Logic Mask].
Default
0
x
x
x
1
1
1
1
1
1
x
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Bit
Definition
(1)
x
The drive must be stopped to change this parameter.
[Write Mask Act]
Indicates status of write access for DPI ports. When Bit 15 is set, network security is controlling
the write mask instead of parameter 347 - [Write Mask Cfg].
Bit
Definition
349
x
Security
348
Security (1)
COMMUNICATION
Bit
Definition
x
3-19
Values
DPI Port 4
Parameter Name & Description
DPI Port 5
No.
DPI Port 6
Group
File
Programming and Parameters
x
x
x
x
x
0 = Control Masked
1 = Control Permitted
x = Reserved
The parameters in the Masks & Owners group and the Security group are displayed only when the Active Converter is operating as a Stand Alone unit. When the
Active Converter is operating as a Coupled unit, these parameters are reserved.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
3-20
Programming and Parameters
No.
Parameter Name & Description
Values
330
[IGBT NTC Temp1]
Displays the temperature measured in IGBT module 1.
Default:
Read Only
Min/Max:
Units:
Default:
-3276.7/+3276.7
0.1°C
Read Only
Min/Max:
Units:
Default:
-3276.7/+3276.7
0.1°C
Read Only
Min/Max:
Units:
Default:
-3276.7/+3276.7
0.1°C
Read Only
Min/Max:
Units:
Default:
-3276.7/+3276.7
0.1°C
Read Only
Min/Max:
Units:
Default:
-3276.7/+3276.7
0.1°C
Read Only
Min/Max:
Units:
Default:
-3276.7/+3276.7
0.1°C
Read Only
Min/Max:
Units:
Default:
-3276.7/+3276.7
0.1°C
Read Only
Min/Max:
Units:
Default:
-3276.7/+3276.7
0.1°C
Read Only
Min/Max:
Units:
Default:
-3276.7/+3276.7
0.1°C
Read Only
Min/Max:
Units:
-3276.7/+3276.7
0.1°C
Read Only
332
Mux’ed Temps
333
334
335
336
INPUTS & OUTPUTS
337
338
339
350
[IGBT NTC Temp2]
Displays the temperature measured in IGBT module 2.
[IGBT NTC Temp3]
Displays the temperature measured in IGBT module 3.
[IGBT NTC Temp4]
Displays the temperature measured in IGBT module 4.
[Coldplate Temp1]
Displays the temperature measured on the first coldplate.
[IGBT NTC Temp5]
Displays the temperature measured in IGBT module 5.
[IGBT NTC Temp6]
Displays the temperature measured in IGBT module 6.
[IGBT NTC Temp7]
Displays the temperature measured in IGBT module 7.
[IGBT NTC Temp8]
Displays the temperature measured in IGBT module 8.
[Coldplate Temp2]
Displays the temperature measured on the second coldplate.
[Dig In Status]
A set of bits displaying the status of the digital input.
Aux Input
331
Sel Switch
Group
File
Inputs & Outputs File
Default
x
x
x
x
x
x
x
x
x
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
x
x
x
x
x
0 = Disabled
1 = Enabled
x = Reserved
• Bit 0 (Aux Input) is set when Aux Input is on.
Aux Input
351
• Bit 1 (Sel Switch) is set when the DPI SLAVE/MASTER switch on the Active Converter control PCB assembly (Figure 1.3 on
page 1-5) is in the DPI MASTER position (Stand Alone operation).
[Dig In Frc Mask]
A set of bits to select which input bits are forced.
Sel Switch
Digital Inputs
Bit
Definition
Default
x
x
x
x
x
x
x
x
x
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Bit
Definition
x
x
x
x
x
0 = Disabled
1 = Enabled
x = Reserved
• Bit 0 (Aux Input) – Enables forcing of the Aux Input signal. This feature requires a password to operate.
• Bit 1 (Sel Switch) – Enables forcing of the DPI SLAVE/MASTER switch signal on the Active Converter control PCB assembly
(Figure 1.3 on page 1-5). This feature requires a password to operate.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
352
[Dig In Frc Data]
A set of bits to select the state of the input bits that are forced.
Default
x
x
x
x
x
x
x
x
x
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Bit
Definition
x
x
x
x
x
3-21
Values
Aux Input
Parameter Name & Description
Sel Switch
Group
No.
Digital Inputs
File
Programming and Parameters
0 = Disabled
1 = Enabled
x = Reserved
• Bit 0 (Aux Input) sets the state of the Aux Input signal when forcing is enabled. This feature requires a password to operate.
Cls Bypass
Aux Output
360
• Bit 1 (Sel Switch) sets the state of the DPI SLAVE/MASTER switch signal on the Active Converter control PCB assembly (Figure
1.3 on page 1-5) when forcing is enabled. This feature requires a password to operate.
Read Only
[Dig Out Status]
A set of bits displaying the status of the digital output.
Default
x
x
x
x
x
x
x
x
x
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
INPUTS & OUTPUTS
Bit
Definition
x
x
x
x
x
0 = Disabled
1 = Enabled
x = Reserved
• Bit 0 (Aux Output) is set when Aux Output is on.
Aux Output
• Bit 1 (Cls Bypass) is set when the precharge bypass contactor is closed.
[Dig Out Frc Mask]
A set of bits to select which output bits are forced.
Cls Bypass
Digital Outputs
361
Default
x
x
x
x
x
x
x
x
x
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Bit
Definition
x
x
x
x
x
0 = Disabled
1 = Enabled
x = Reserved
• Bit 0 (Aux Output) – Enables forcing of the Aux Output signal. This feature requires a password to operate.
Aux Output
• Bit 1 (Cls Bypass) – Enables forcing of the Cls Bypass signal. This feature requires a password to operate.
[Dig Out Frc Data]
A set of bits to select the state of the output bits that are forced.
Cls Bypass
362
Default
x
x
x
x
x
x
x
x
x
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Bit
Definition
x
x
x
x
x
0 = Disabled
1 = Enabled
x = Reserved
• Bit 0 (Aux Output) sets the state of the Aux Output signal when forcing is enabled. This feature requires a password to operate.
• Bit 1 (Cls Bypass) sets the state of the Cls Bypass signal when forcing is enabled. This feature requires a password to operate.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
3-22
Programming and Parameters
Parameter Cross Reference –
by Name
Parameter Name
AC High Freq Lmt
AC High Freq Time
AC Line kW
AC Low Freq Lmt
AC Low Freq Time
AC Maximum dF/dt
Active Current
Active I Cmd
Active I Lmt
Active OL I Lmt
Alarm Config
Alarm Status
Ambient Temp
Ambnt Temp Alrm
Ambnt Temp Trip
Base Temp Alrm
Base Temp Trip
Bus Capacitance
CAN Bus Off Cnt
Capacitance
Change Line Freq
CldPlt Temp Alrm
CML Bandwidth
CML Damping
CML Ki
CML Kp
Coldplate Temp1
Coldplate Temp2
Connect Status
Control SW Ver
Converter Contrl
Converter Fault
Converter MinVdc
Converter Status
CS Msg Bad Cnt
CS Msg Rx Cnt
CS Msg Tx Cnt
CS Timeout Cnt
Data In A1
Data In A2
Data In B1
Data In B2
Data In C1
Data In C2
Data In D1
Data In D2
Data Out A1
Data Out A2
Data Out B1
Data Out B2
Data Out C1
Data Out C2
Data Out D1
Data Out D2
DcLink Command
DcLink Reference
DcLink Ripple
DcLink Voltage
Dig In Frc Data
Dig In Frc Mask
Dig In Status
Dig Out Frc Data
Dig Out Frc Mask
Dig Out Status
DPI Error Out
Drive Checksum
Elapsed Run Time
Extern Cml Ref
Fault 1 Code
Fault 1 Time
Fault 2 Code
Fault 2 Time
Number
133
134
021
131
132
135
006
151
100
101
260
211
030
120
121
122
123
170
329
162
044
126
153
154
155
156
334
339
320
204
070
073
072
071
325
322
323
324
300
301
302
303
304
305
306
307
310
311
312
313
314
315
316
317
161
060
015
014
352
351
350
362
361
360
321
203
025
062
243
244
245
246
Group
Frequency
Frequency
Power & Time
Frequency
Frequency
Frequency
Current
Current Loop
Current
Current
Fault Queue
Diagnostics
Temperature
Temperature
Temperature
Temperature
Temperature
Voltage Loop
DPI Status
Voltage Loop
Frequency
Temperature
Current Loop
Current Loop
Current Loop
Current Loop
Mux’ed Temps
Mux’ed Temps
DPI Status
Drive Memory
Data Exchange
Data Exchange
Data Exchange
Data Exchange
DPI Status
DPI Status
DPI Status
DPI Status
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Voltage Loop
Setpoints
Voltage
Voltage
Digital Inputs
Digital Inputs
Digital Inputs
Digital Outputs
Digital Outputs
Digital Outputs
DPI Status
Drive Memory
Power & Time
Setpoints
Fault Queue
Fault Queue
Fault Queue
Fault Queue
Page
3-10
3-10
3-4
3-10
3-10
3-10
3-4
3-11
3-9
3-9
3-16
3-13
3-5
3-10
3-10
3-10
3-10
3-12
3-18
3-12
3-5
3-10
3-11
3-11
3-11
3-11
3-20
3-20
3-17
3-13
3-7
3-8
3-8
3-8
3-18
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-11
3-7
3-4
3-4
3-21
3-20
3-20
3-21
3-21
3-21
3-17
3-13
3-5
3-7
3-15
3-15
3-15
3-15
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Parameter Name
Fault 3 Code
Fault 3 Time
Fault 4 Code
Fault 4 Time
Fault Amps D
Fault Amps Q
Fault Amps R
Fault Amps S
Fault Amps T
Fault Base Temp
Fault Clear
Fault Clr Mask
Fault Clr Owner
Fault Config
Fault Frequency
Fault Volts RS
Fault Volts ST
Fault Volts TR
Fault Volts Vdc
Ground Current
High Vac Lmt
High Vac Time
I Imbalance
I Imbalance Lmt
I Imbalance Time
IGBT Base Temp
IGBT Junct Temp
IGBT NTC Temp1
IGBT NTC Temp2
IGBT NTC Temp3
IGBT NTC Temp4
IGBT NTC Temp5
IGBT NTC Temp6
IGBT NTC Temp7
IGBT NTC Temp8
Inductance
Input Current R
Input Current S
Input Current T
Input Voltage RS
Input Voltage ST
Input Voltage TR
IT Overload
Junct Temp Alrm
Junct Temp Trip
kVAR Ref
Language
Life Power Time
Life Pwr Cycles
Life Run Time
Life Time kWh
Line Frequency
Logic Mask
Logic Mask Act
Low Vac Lmt
Low Vac Time
Manual Sequence
Max Line Freq
Min Line Freq
Min Max Persist
Modulation Freq
Modulation Index
Motoring kWh
Option Select
Parallel Config
Param Access Lvl
Password
PC Msg Rx Cnt
PC Msg Timeout Cnt
PC Msg Tx Cnt
PF Bandwidth
Port Mask Act
Power Up Marker
PWM Frequency
Rated Amps
Rated Power
Rated Volts
Number
247
248
249
250
225
224
221
222
223
230
239
342
345
238
220
226
227
228
229
005
114
115
008
103
104
031
032
330
331
332
333
335
336
337
338
152
002
003
004
011
012
013
009
124
125
061
201
027
028
026
024
040
340
349
112
113
052
042
041
043
064
063
022
051
169
196
205
326
328
327
157
346
242
130
001
020
010
Group
Fault Queue
Fault Queue
Fault Queue
Fault Queue
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Fault Queue
Masks & Owners
Masks & Owners
Fault Queue
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Current
AC Line Voltage
AC Line Voltage
Current
Current
Current
Temperature
Temperature
Mux’ed Temps
Mux’ed Temps
Mux’ed Temps
Mux’ed Temps
Mux’ed Temps
Mux’ed Temps
Mux’ed Temps
Mux’ed Temps
Current Loop
Current
Current
Current
Voltage
Voltage
Voltage
Current
Temperature
Temperature
Setpoints
Drive Memory
Power & Time
Power & Time
Power & Time
Power & Time
Frequency
Masks & Owners
Security
AC Line Voltage
AC Line Voltage
Start/Stop
Frequency
Frequency
Frequency
Setpoints
Setpoints
Power & Time
Start/Stop
Voltage Loop
Drive Memory
Drive Memory
DPI Status
DPI Status
DPI Status
Current Loop
Security
Fault Queue
Frequency
Current
Power & Time
Voltage
Page
3-16
3-16
3-16
3-16
3-14
3-14
3-14
3-14
3-14
3-15
3-15
3-18
3-18
3-15
3-14
3-14
3-14
3-14
3-14
3-4
3-9
3-9
3-4
3-9
3-9
3-5
3-5
3-20
3-20
3-20
3-20
3-20
3-20
3-20
3-20
3-11
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-10
3-10
3-7
3-13
3-5
3-5
3-5
3-5
3-5
3-18
3-19
3-9
3-9
3-6
3-5
3-5
3-5
3-7
3-7
3-4
3-6
3-12
3-13
3-13
3-18
3-18
3-18
3-11
3-18
3-15
3-10
3-4
3-4
3-4
Parameter Name
Reactive Current
Reactive I Cmd
Reactive I Lmt
Reactive RateLmt
Reduce Ilmt Sel
Regen I Lmt
Regen kWh
Reset Meters
Reset to Defaults
Ride Through Ena
Ride Through Sec
Start Config
Start Inhibits
Start Mask
Start Owner
Stop Owner
Testpoint 1 Data
Testpoint 1 Sel
Testpoint 2 Data
Testpoint 2 Sel
Turn Off Delay
V Imbalance
V Imbalance Lmt
V Imbalance Time
VML Bandwidth
VML Damping
VML Kf
VML Ki
VML Kp
VML Reset Level
Voltage Loop Sel
Write Mask Act
Write Mask Cfg
Number
007
159
158
102
150
105
023
200
197
110
111
050
214
341
344
343
235
234
237
236
053
016
116
117
163
164
167
165
166
168
160
348
347
Group
Current
Current Loop
Current Loop
Current
Current Loop
Current
Power & Time
Drive Memory
Drive Memory
AC Line Voltage
AC Line Voltage
Start/Stop
Diagnostics
Masks & Owners
Masks & Owners
Masks & Owners
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Start/Stop
Voltage
AC Line Voltage
AC Line Voltage
Voltage Loop
Voltage Loop
Voltage Loop
Voltage Loop
Voltage Loop
Voltage Loop
Voltage Loop
Security
Security
Page
3-4
3-11
3-11
3-9
3-11
3-9
3-4
3-13
3-13
3-9
3-9
3-6
3-14
3-18
3-18
3-18
3-15
3-15
3-15
3-15
3-7
3-4
3-9
3-10
3-12
3-12
3-12
3-12
3-12
3-12
3-11
3-19
3-19
Programming and Parameters
Parameter Cross Reference –
by Number
Number
001
002
003
004
005
006
007
008
009
010
011
012
013
014
015
016
020
021
022
023
024
025
026
027
028
030
031
032
040
041
042
043
044
050
051
052
053
060
061
062
063
064
070
071
072
073
100
101
102
103
104
105
110
111
112
113
114
115
116
117
120
121
122
123
124
125
126
130
131
132
133
134
Parameter Name
Rated Amps
Input Current R
Input Current S
Input Current T
Ground Current
Active Current
Reactive Current
I Imbalance
IT Overload
Rated Volts
Input Voltage RS
Input Voltage ST
Input Voltage TR
DcLink Voltage
DcLink Ripple
V Imbalance
Rated Power
AC Line kW
Motoring kWh
Regen kWh
Life Time kWh
Elapsed Run Time
Life Run Time
Life Power Time
Life Pwr Cycles
Ambient Temp
IGBT Base Temp
IGBT Junct Temp
Line Frequency
Min Line Freq
Max Line Freq
Min Max Persist
Change Line Freq
Start Config
Option Select
Manual Sequence
Turn Off Delay
DcLink Reference
kVAR Ref
Extern Cml Ref
Modulation Index
Modulation Freq
Converter Contrl
Converter Status
Converter MinVdc
Converter Fault
Active I Lmt
Active OL I Lmt
Reactive RateLmt
I Imbalance Lmt
I Imbalance Time
Regen I Lmt
Ride Through Ena
Ride Through Sec
Low Vac Lmt
Low Vac Time
High Vac Lmt
High Vac Time
V Imbalance Lmt
V Imbalance Time
Ambnt Temp Alrm
Ambnt Temp Trip
Base Temp Alrm
Base Temp Trip
Junct Temp Alrm
Junct Temp Trip
CldPlt Temp Alrm
PWM Frequency
AC Low Freq Lmt
AC Low Freq Time
AC High Freq Lmt
AC High Freq Time
Group
Current
Current
Current
Current
Current
Current
Current
Current
Current
Voltage
Voltage
Voltage
Voltage
Voltage
Voltage
Voltage
Power & Time
Power & Time
Power & Time
Power & Time
Power & Time
Power & Time
Power & Time
Power & Time
Power & Time
Temperature
Temperature
Temperature
Frequency
Frequency
Frequency
Frequency
Frequency
Start/Stop
Start/Stop
Start/Stop
Start/Stop
Setpoints
Setpoints
Setpoints
Setpoints
Setpoints
Data Exchange
Data Exchange
Data Exchange
Data Exchange
Current
Current
Current
Current
Current
Current
AC Line Voltage
AC Line Voltage
AC Line Voltage
AC Line Voltage
AC Line Voltage
AC Line Voltage
AC Line Voltage
AC Line Voltage
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Frequency
Frequency
Frequency
Frequency
Frequency
Page
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-5
3-5
3-5
3-5
3-5
3-5
3-5
3-5
3-5
3-5
3-5
3-5
3-5
3-6
3-6
3-6
3-7
3-7
3-7
3-7
3-7
3-7
3-7
3-8
3-8
3-8
3-9
3-9
3-9
3-9
3-9
3-9
3-9
3-9
3-9
3-9
3-9
3-9
3-9
3-10
3-10
3-10
3-10
3-10
3-10
3-10
3-10
3-10
3-10
3-10
3-10
3-10
Number
135
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
196
197
200
201
203
204
205
211
214
220
221
222
223
224
225
226
227
228
229
230
234
235
236
237
238
239
242
243
244
245
246
247
248
249
250
260
300
301
302
303
304
305
306
307
310
311
312
313
314
315
316
317
320
321
322
Parameter Name
AC Maximum dF/dt
Reduce Ilmt Sel
Active I Cmd
Inductance
CML Bandwidth
CML Damping
CML Ki
CML Kp
PF Bandwidth
Reactive I Lmt
Reactive I Cmd
Voltage Loop Sel
DcLink Command
Capacitance
VML Bandwidth
VML Damping
VML Ki
VML Kp
VML Kf
VML Reset Level
Parallel Config
Bus Capacitance
Param Access Lvl
Reset to Defaults
Reset Meters
Language
Drive Checksum
Control SW Ver
Password
Alarm Status
Start Inhibits
Fault Frequency
Fault Amps R
Fault Amps S
Fault Amps T
Fault Amps Q
Fault Amps D
Fault Volts RS
Fault Volts ST
Fault Volts TR
Fault Volts Vdc
Fault Base Temp
Testpoint 1 Sel
Testpoint 1 Data
Testpoint 2 Sel
Testpoint 2 Data
Fault Config
Fault Clear
Power Up Marker
Fault 1 Code
Fault 1 Time
Fault 2 Code
Fault 2 Time
Fault 3 Code
Fault 3 Time
Fault 4 Code
Fault 4 Time
Alarm Config
Data In A1
Data In A2
Data In B1
Data In B2
Data In C1
Data In C2
Data In D1
Data In D2
Data Out A1
Data Out A2
Data Out B1
Data Out B2
Data Out C1
Data Out C2
Data Out D1
Data Out D2
Connect Status
DPI Error Out
CS Msg Rx Cnt
Group
Frequency
Current Loop
Current Loop
Current Loop
Current Loop
Current Loop
Current Loop
Current Loop
Current Loop
Current Loop
Current Loop
Voltage Loop
Voltage Loop
Voltage Loop
Voltage Loop
Voltage Loop
Voltage Loop
Voltage Loop
Voltage Loop
Voltage Loop
Voltage Loop
Voltage Loop
Drive Memory
Drive Memory
Drive Memory
Drive Memory
Drive Memory
Drive Memory
Drive Memory
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Diagnostics
Fault Queue
Fault Queue
Fault Queue
Fault Queue
Fault Queue
Fault Queue
Fault Queue
Fault Queue
Fault Queue
Fault Queue
Fault Queue
Fault Queue
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
Datalinks
DPI Status
DPI Status
DPI Status
Page
3-10
3-11
3-11
3-11
3-11
3-11
3-11
3-11
3-11
3-11
3-11
3-11
3-11
3-12
3-12
3-12
3-12
3-12
3-12
3-12
3-12
3-12
3-13
3-13
3-13
3-13
3-13
3-13
3-13
3-13
3-14
3-14
3-14
3-14
3-14
3-14
3-14
3-14
3-14
3-14
3-14
3-15
3-15
3-15
3-15
3-15
3-15
3-15
3-15
3-15
3-15
3-15
3-15
3-16
3-16
3-16
3-16
3-16
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
3-17
Number
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
360
361
362
Parameter Name
CS Msg Tx Cnt
CS Timeout Cnt
CS Msg Bad Cnt
PC Msg Rx Cnt
PC Msg Tx Cnt
PC Msg Timeout Cnt
CAN Bus Off Cnt
IGBT NTC Temp1
IGBT NTC Temp2
IGBT NTC Temp3
IGBT NTC Temp4
Coldplate Temp1
IGBT NTC Temp5
IGBT NTC Temp6
IGBT NTC Temp7
IGBT NTC Temp8
Coldplate Temp2
Logic Mask
Start Mask
Fault Clr Mask
Stop Owner
Start Owner
Fault Clr Owner
Port Mask Act
Write Mask Cfg
Write Mask Act
Logic Mask Act
Dig In Status
Dig In Frc Mask
Dig In Frc Data
Dig Out Status
Dig Out Frc Mask
Dig Out Frc Data
Group
DPI Status
DPI Status
DPI Status
DPI Status
DPI Status
DPI Status
DPI Status
Mux’ed Temps
Mux’ed Temps
Mux’ed Temps
Mux’ed Temps
Mux’ed Temps
Mux’ed Temps
Mux’ed Temps
Mux’ed Temps
Mux’ed Temps
Mux’ed Temps
Masks & Owners
Masks & Owners
Masks & Owners
Masks & Owners
Masks & Owners
Masks & Owners
Security
Security
Security
Security
Digital Inputs
Digital Inputs
Digital Inputs
Digital Outputs
Digital Outputs
Digital Outputs
3-23
Page
3-17
3-17
3-18
3-18
3-18
3-18
3-18
3-20
3-20
3-20
3-20
3-20
3-20
3-20
3-20
3-20
3-20
3-18
3-18
3-18
3-18
3-18
3-18
3-18
3-19
3-19
3-19
3-20
3-20
3-21
3-21
3-21
3-21
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
3-24
Programming and Parameters
Notes:
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Chapter
4
Troubleshooting
This chapter provides information to guide you in troubleshooting the
PowerFlex 700L Active Converter Power Module. Included is a listing and
description of faults (with possible solutions, when applicable) and alarms.
For information on …
Faults and Alarms
Manually Clearing Faults
Fault Descriptions
Clearing Alarms
Alarm Descriptions
Faults and Alarms
See page…
4-1
4-1
4-1
4-4
4-4
A fault is a condition that stops the Converter. There are two fault types.
Type
➀
➁
Fault Description
Reserved for future.
Non-Resettable
➂
User Configurable
This type of fault normally requires drive or motor repair. The cause of
the fault must be corrected before the fault can be cleared. The fault will
be reset on power up after repair.
These faults can be enabled/disabled to annunciate or ignore a fault
condition.
An alarm is a condition that, if left untreated, may stop the Converter. All
alarms are configurable using parameter 260 - [Alarm Config].
Manually Clearing Faults
Step
Key(s)
1. Press Esc to acknowledge the fault. The fault information will be removed so that
you can use the HIM.
Esc
2. Address the condition that caused the fault.
The cause must be corrected before the fault can be cleared.
3. After corrective action has been taken, clear the fault by one of these methods.
•
•
•
•
Fault Descriptions
Press Stop
Cycle drive power
Set parameter 239 - [Fault Clear] to “1 = Clear Faults.”
“Clear Faults” on the HIM Diagnostic menu.
The PowerFlex 700L Active Converter Power Module tests for many
different conditions to detect abnormal operation. The following Active
Converter faults are listed by name, fault code number, type, description of
the condition, and corrective action required by the user where applicable.
With the ability to connect larger frame size power structures in parallel,
each structure has independent fault detection to indicate the source of the
problem (for example, PS1 for Primary Converter and PS2 for Secondary
Converter).
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
4-2
Troubleshooting
Table 4.A Fault Types, Descriptions, and Actions
Fault
No.
HW Over Current
HW Over Voltage
1
2
HW Ground Fault
HW Disabled
HW Latch Error
3
4
5
Precharge Open
6
Precharge Closed
7
DPI Mstr ComLoss
Inverter Flt
8
9
PS1 DSAT Phase R
PS1 DSAT Phase S
PS1 DSAT Phase T
PS1 Over Current
PS1 Over Voltage
10
11
12
13
14
PS1 Asym DC Link
PS1 Power Supply
PS1 HW Disable
PS1 Latch Error
PS2 DSAT Phase R
PS2 DSAT Phase S
PS2 DSAT Phase T
PS2 Over Current
PS2 Over Voltage
15
16
17
18
20
21
22
23
24
PS2 Asym DC Link
PS2 Power Supply
PS2 HW Disable
PS2 Latch Error
25
26
27
28
PwrBd Incompat
PB Ver Corrupted
Default Corruptd
Rating Corrupted
New ControlBoard
Elapsed CheckSum
Param CheckSum
Param CheckSum B
Param CheckSum W
Param CheckSum L
30
31
32
33
34
35
36
37
38
39
Ac Line Lost
Ac Phase Lost
Ac Sync Low Vac
Ac Sync Low Freq
Ac Sync High Freq
Ac Sync Conflict
40
41
42
43
44
45
Type (1) Description
Converter Control Board Hardware Faults
Control board detected excessive phase current.
Control board detected excessive phase DC Link voltage.
➁
➁
➁
➁
Action
Verify AC line power quality.
Verify regenerating current limit is not
being exceeded.
Verify motor insulation.
Verify control board enable is present.
Contact Technical Support.
Control board detected a ground fault.
Control board detected phase current that did not sum to 0.
Control board detected excessive an unidentified fault.
Sequencing Faults
The precharge contactor opened when it was commanded closed. Verify operation of the precharge
contactor.
The precharge contactor closed when it was commanded open. Verify operation of the precharge
contactor.
Communication Faults
DPI communication with the Inverter was lost.
Verify DPI cable installation.
Inverter detected a fault.
Power Structure Faults
Power Structure 1 detected a Dsat fault on phase R. (2)
Contact Technical Support.
Power Structure 1 detected a Dsat fault on phase S. (2)
Contact Technical Support.
Power Structure 1 detected a Dsat fault on phase T. (2)
Contact Technical Support.
Power Structure 1 detected excessive phase current. (2)
Verify AC line power quality.
Power Structure 1 detected excessive DC Link voltage. (2)
Verify regenerating current limit is not
being exceeded.
Power Structure 1 detected an asymmetrical DC Link voltage. (2) Verify load balance resistors.
Power Structure 1 detected power supply out of tolerance. (2)
Replace power supply if problem persists.
Power Structure 1 detected excessive phase current. (2)
Verify drive enable is present.
Power Structure 1 detected an unidentified fault. (2)
Contact Technical Support.
Power Structure 2 detected a Dsat fault on phase R. (3)
Contact Technical Support.
Power Structure 2 detected a Dsat fault on phase S. (3)
Contact Technical Support.
Power Structure 2 detected a Dsat fault on phase T. (3)
Contact Technical Support.
Power Structure 2 detected excessive phase current. (3)
Verify AC line power quality.
Power Structure 2 detected excessive DC Link voltage. (3)
Verify regenerating current limit is not
being exceeded.
Power Structure 2 detected an asymmetrical DC Link voltage. (3) Verify load balance resistors.
Power Structure 2 detected power supply out of tolerance. (3)
Replace power supply if problem persists.
Power Structure 1 detected excessive phase current. (3)
Verify drive enable is present.
Power Structure 1 detected an unidentified fault. (3)
Contact Technical Support.
Non-Volatile Storage Faults
Power board incompatible with control board.
Load new file into power board.
Power board version number is corrupted.
Load new file into power board.
Power board parameter default data file is corrupted.
Load new file into power board.
Power board rating data file is corrupted.
Load new file into power board.
New Converter control board was detected.
Reset to defaults is required.
Elapsed operation data checksum is invalid at power up.
Reset to defaults is required.
Parameter data checksum is invalid at power up.
Reset to defaults is required.
Parameter data checksum error when writing a BYTE value.
Reset to defaults is required.
Parameter data checksum error when writing a WORD value.
Reset to defaults is required.
Parameter data checksum error when writing a LONG value.
Reset to defaults is required.
AC Line Synchronization Faults
AC line synchronization was lost when power turned off.
Verify proper input line voltage is present.
AC line synchronization was lost when phase was lost.
Verify proper input line voltage is present.
AC line synchronization was lost because voltage was low.
Verify proper input line voltage is present.
AC line synchronization was lost because frequency was low.
Verify proper input line voltage is present.
AC line synchronization was lost because frequency was high.
Verify proper input line voltage is present.
Conflict in AC line synchronization state machine.
Contact Technical Support.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Troubleshooting
Fault
PWM Sync Lost
No.
46
Type (1) Description
➂
PWM Carrier synchronization was lost.
Ac Low Voltage
50
➂
Ac High Voltage
51
➂
Ac Low Frequency
52
➂
Ac HighFrequency
53
➂
Ac High dFdt
Ac I Imbalance
54
55
➂
➂
Ac V Imbalance
56
➂
DcLink Low Volt
Ride Thru Expire
Ride Thru Expire
57
58
59
IT Over Load
Ambnt Over Temp
Base Over Temp
Junct Over Temp
Ntc Range Low
Ntc Range High
PS1 Fan Loss
PS1 Reactor Temp
PS2 Fan Loss
PS2 Reactor Temp
60
61
62
63
64
65
66
67
68
69
FiltCap Contactr
70
Port 1 Adapter
Port 2 Adapter
Port 3 Adapter
Port 4 Adapter
Port 5 Adapter
Port 6 Adapter
Port 1 DPI Loss
Port 2 DPI Loss
Port 3 DPI Loss
Port 4 DPI Loss
Port 5 DPI Loss
Port 6 DPI Loss
71
72
73
74
75
76
81
82
83
84
85
86
4-3
Action
Verify wiring of carrier synchronization
cable.
Variations in the AC Line Faults
AC line voltage was below the configured limit for the configured
time.
AC line voltage exceeded the configured limit for the configured
time.
AC line frequency was below the configured limit for the
configured time.
AC line frequency exceeded the configured limit for the configured
time.
Change in line frequency exceeded the configured limit.
AC current balance exceeded the configured limit for the
configured time.
AC voltage balance exceeded the configured limit for the
configured time.
DC link voltage was below the precharge open level.
Power dip ride through expired with precharge open.
Power dip ride through expired with precharge closed.
Overload Faults
Operating current levels exceeded the rated overload.
Measured ambient temperature exceeded the maximum limit.
IGBT base temperature exceeded the maximum limit.
IGBT junction temperature exceeded the maximum limit.
NTC temperature outside below rated temperature range.
NTC temperature outside above rated temperature range.
Power Structure 1 detected a circulating fan was lost. (2)
Power Structure 1 detected the reactor thermal switch opened. (2)
Power Structure 2 detected a circulating fan was lost. (3)
Power Structure 2 detected the reactor thermal switch opened. (3)
Input Filter Fault
The detected state (open/closed) of the input filter capacitor bank
contactor does not match the commanded state.
Stand Alone Unit (DPI MASTER) Faults
The communication card has detected a fault on the network. (4)
The communication card has detected a fault on the network. (4)
The communication card has detected a fault on the network. (4)
The communication card has detected a fault on the network. (4)
The communication card has detected a fault on the network. (4)
The communication card has detected a fault on the network. (4)
The DPI communication to a peripheral was lost. (4)
The DPI communication to a peripheral was lost. (4)
The DPI communication to a peripheral was lost. (4)
The DPI communication to a peripheral was lost. (4)
The DPI communication to a peripheral was lost. (4)
The DPI communication to a peripheral was lost. (4)
Verify proper input line voltage is present.
Verify proper input line voltage is present.
Verify proper input line voltage is present.
Verify proper input line voltage is present.
Verify proper input line voltage is present.
Verify proper input line voltage is present.
Verify proper input line voltage is present.
Verify proper input line voltage is present.
Verify proper input line voltage is present.
Verify proper input line voltage is present.
Verify proper input line voltage is present.
Verify required drive cooling is present.
Verify required drive cooling is present.
Check for open or shorted NTC device.
Check for open or shorted NTC device.
Verify internal circulating fans are turning.
Verify reactor cooling fans are turning.
Verify internal circulating fans are turning.
Verify reactor cooling fans are turning.
Verify wiring of filter capacitor contactor.
Check DPI device event queue and
corresponding fault information for the
device.
1. If adapter was not intentionally
disconnected, check wiring to the port.
Replace wiring, port expander,
adapters, Main Control Board, or
complete Converter as required.
2. Check HIM connection.
3. If an adapter was intentionally
disconnected and the [Logic Mask] bit
for that adapter is set to “1,” this fault
will occur. To disable this fault, set the
[Logic Mask] bit for the adapter to “0.”
(1)
(2)
(3)
(4)
See page 4-1 for a description of fault types.
These faults only apply to Frame 3 power structures.
These faults are reserved for future use.
These faults only apply when operating the Active Converter as a Stand Alone unit (DPI Master).
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
4-4
Troubleshooting
Table 4.B Fault Cross Reference – By Number
No. (1)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
20
21
(1)
Fault
HW Over Current
HW Over Voltage
HW Ground Fault
HW Disabled
HW Latch Error
Precharge Open
Precharge Closed
DPI Mstr ComLoss
Inverter Flt
PS1 DSAT Phase R
PS1 DSAT Phase S
PS1 DSAT Phase T
PS1 Over Current
PS1 Over Voltage
PS1 Asym DC Link
PS1 Power Supply
PS1 HW Disable
PS1 Latch Error
PS2 DSAT Phase R
PS2 DSAT Phase S
No. (1)
22
23
24
25
26
27
28
30
31
32
33
34
35
36
37
38
39
40
41
42
Fault
PS2 DSAT Phase T
PS2 Over Current
PS2 Over Voltage
PS2 Asym DC Link
PS2 Power Supply
PS2 HW Disable
PS2 Latch Error
PwrBd Incompat
PB Ver Corrupted
Default Corruptd
Rating Corrupted
New ControlBoard
Elapsed CheckSum
Param CheckSum
Param CheckSum B
Param CheckSum W
Param CheckSum L
Ac Line Lost
Ac Phase Lost
Ac Sync Low Vac
No. (1)
43
44
45
46
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
Fault
Ac Sync Low Freq
Ac Sync High Freq
Ac Sync Conflict
PWM Sync Lost
Ac Low Voltage
Ac High Voltage
Ac Low Frequency
Ac HighFrequency
Ac High dFdt
Ac I Imbalance
Ac V Imbalance
DcLink Low Volt
Ride Thru Expire
Ride Thru Expire
IT Over Load
Ambnt Over Temp
Base Over Temp
Junct Over Temp
Ntc Range Low
Ntc Range High
No. (1)
66
67
68
69
70
71
72
73
74
75
76
81
82
83
84
85
86
Fault
PS1 Fan Loss
PS1 Reactor Temp
PS2 Fan Loss
PS2 Reactor Temp
FiltCap Contactr
Port 1 Adapter
Port 2 Adapter
Port 3 Adapter
Port 4 Adapter
Port 5 Adapter
Port 6 Adapter
Port 1 DPI Loss
Port 2 DPI Loss
Port 3 DPI Loss
Port 4 DPI Loss
Port 5 DPI Loss
Port 6 DPI Loss
Fault numbers not listed are reserved for future use.
Clearing Alarms
Alarms are automatically cleared when the condition that caused the alarm
is no longer present.
Alarm Descriptions
All Active Converter alarms are configurable using parameter 260 - [Alarm
Config]. The status of the alarms can be viewed using parameter 211 [Alarm Status].
Table 4.C Alarm Descriptions for Parameter 211 - [Alarm Status] Bits
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Bit Definition
Ac Low Volt
Ac High Volt
Ac Low Freq
Ac High Freq
Ac High dFdt
I Imbalance
V Imbalance
IT Overload
Ambient Temp
Base Temp
Junction Temp
Coldplate Temp
PWM SyncLoss
Reserved
Reserved
Start Inhibit
Description
Bit 0 is set when the average AC Line Voltage is less than the limit in parameter 112 - [Low Vac Lmt].
Bit 1 is set when the average AC Line Voltage exceeds the limit in parameter 114 - [High Vac Lmt].
Bit 2 is set when the AC Line Frequency is less than the limit in parameter 131 - [AC Low Freq Lmt].
Bit 3 is set when the AC Line Frequency exceeds the limit in parameter 133 - [AC High Freq Lmt].
Bit 4 is set when the AC Line Frequency is changing faster than the limit in parameter 135 - [AC Maximum dF/dt].
Bit 5 is set when the phase current imbalance exceeds the limit in parameter 103 - [I Imbalance Lmt].
Bit 6 is set when the phase voltage imbalance is greater than the limit in parameter 116 - [V Imbalance Lmt].
Bit 7 is set when the Overload counter is greater than 90%.
Bit 8 is set when the ambient temperature exceeds the limit in parameter 120 - [Ambnt Temp Alrm].
Bit 9 is set when the IGBT base temperature exceeds the limit in parameter 122 - [Base Temp Alrm].
Bit 10 is set when the IGBT junction temperature exceeds the limit in parameter 124 - [Junct Temp Alrm].
Bit 11 is set when the coldplate temperature is less than the limit in parameter 126 - [CldPlt Temp Alrm].
Bit 12 is set when PWM carrier synchronization is lost.
Bit 15 is set when one or more start inhibits are present.
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Index
Numerics
700 Vector Control (standard) information
reference, P-1
700S Phase II Control (optional) information
reference, P-2
clearing
alarms, 4-4
faults, 4-1
CML Bandwidth parameter, 3-11
CML Damping parameter, 3-11
CML Ki parameter, 3-11
A
AC High Freq Lmt parameter, 3-10
AC High Freq Time parameter, 3-10
AC Line kW parameter, 3-4
AC Line Voltage Parameter Group, 3-9
AC Low Freq Lmt parameter, 3-10
AC Low Freq Time parameter, 3-10
Active Converter Power Module
fault descriptions, 4-1
parameters, 3-1
removing control cassette, 1-2
removing covers, 1-2
wiring control board I/O terminals, 1-4
CML Kp parameter, 3-11
Coldplate Temp1 parameter, 3-20
Coldplate Temp2 parameter, 3-20
Command File, 3-6
common mode interference, 1-4
Communication File, 3-17
configuring parameters, 3-1
Connect Status parameter, 3-17
Control SW Ver parameter, 3-13
conventions used in this manual, P-2
Converter Control parameter, 3-7
Converter Fault parameter, 3-8
Converter Min Vdc parameter, 3-8
Active Current parameter, 3-4
Converter Status, 3-8
Active I Cmd parameter, 3-11
cross-reference of parameters
by name, 3-22
by number, 3-23
Active I Lmt parameter, 3-9
Active OL I Lmt parameter, 3-9
alarm
clearing, 4-4
descriptions, 4-4
CS Msg Bad Cnt parameter, 3-18
Alarm Config parameter, 3-16
CS Timeout Cnt parameter, 3-17
Alarm Status parameter, 3-13
Current Lmt Gain parameter, 3-9
Ambient Temp parameter, 3-5
Current Lmt Val parameter, 3-9
Ambnt Temp Alrm parameter, 3-10
Current Loop Parameter Group, 3-11
Ambnt Temp Trip parameter, 3-10
Current Parameter Group, 3-4, 3-9
B
CS Msg Rx Cnt parameter, 3-17
CS Msg Tx Cnt parameter, 3-17
D
Base Temp Alrm parameter, 3-10
Data Exchange Parameter Group, 3-7
Base Temp Trip parameter, 3-10
Data In A1 parameter, 3-17
Bus Capacitance parameter, 3-12
Data In A2 parameter, 3-17
bus capacitors, discharging, P-3
Data In B1 parameter, 3-17
Data In B2 parameter, 3-17
C
Data In C1 parameter, 3-17
CAN Bus Off Cnt parameter, 3-18
Data In C2 parameter, 3-17
Capacitance parameter, 3-12
Data In D1 parameter, 3-17
capacitors - bus, discharging, P-3
Data In D2 parameter, 3-17
Change Line Freq parameter, 3-5
Data Out A1 parameter, 3-17
CldPlt Temp Alrm parameter, 3-10
Data Out A2 parameter, 3-17
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Index-2
Data Out B1 parameter, 3-17
Fault Amps S parameter, 3-14
Data Out B2 parameter, 3-17
Fault Amps T parameter, 3-14
Data Out C1 parameter, 3-17
Fault Clear parameter, 3-15
Data Out C2 parameter, 3-17
Fault Clr Mask parameter, 3-18
Data Out D1 parameter, 3-17
Fault Clr Owner parameter, 3-18
Data Out D2 parameter, 3-17
Fault Config parameter, 3-15
Datalinks Parameter Group, 3-17
fault descriptions for active converter, 4-1
DcLink Command parameter, 3-11
Fault Frequency parameter, 3-14
DcLink Reference parameter, 3-7
Fault Queue Parameter Group, 3-15
DcLink Ripple parameter, 3-4
Fault Volts RS parameter, 3-14
DcLink Voltage parameter, 3-4
Fault Volts ST parameter, 3-14
Diagnostic Parameter Group, 3-13
Fault Volts TR parameter, 3-14
Dig In Frc Data parameter, 3-21
Fault Volts Vdc parameter, 3-14, 3-15
Dig In Frc Mask parameter, 3-20
Digital Outputs Parameter Group, 3-20
File
Command, 3-6
Communication, 3-17
Dynamic Control, 3-11
Inputs & Outputs, 3-20
Limit Config, 3-9
Monitor, 3-4
Utility, 3-13
DPI Error Out parameter, 3-17
File-Group-Parameter, 3-2
DPI Status Parameter Group, 3-17
Frequency Parameter Group, 3-5, 3-10
Dig In Status parameter, 3-20
Dig Out Frc Data parameter, 3-21
Dig Out Frc Mask parameter, 3-21
Dig Out Status parameter, 3-21
Digital Inputs Parameter Group, 3-20
Drive Checksum parameter, 3-13
Drive Memory Parameter Group, 3-13
Dynamic Control File, 3-11
G
general precautions, P-3
Ground Current parameter, 3-4
E
editing parameters, 3-1
Elapsed Run Time parameter, 3-5
Electrostatic Discharge (ESD), P-3
Extern Cml Ref parameter, 3-7
F
Fault 1 Code parameter, 3-15
Fault 1 Time parameter, 3-15
Fault 2 Code parameter, 3-15
Fault 2 Time parameter, 3-15
Fault 3 Code parameter, 3-16
Fault 3 Time parameter, 3-16
Fault 4 Code parameter, 3-16
Fault 4 Time parameter, 3-16
Fault Amps D parameter, 3-14
Fault Amps Q parameter, 3-14
Fault Amps R parameter, 3-14
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Group - Parameter
AC Line Voltage, 3-9
Current, 3-4, 3-9
Current Loop, 3-11
Data Exchange, 3-7
Datalinks, 3-17
Diagnostic, 3-13
Digital Inputs, 3-20
Digital Outputs, 3-20
DPI Status, 3-17
Drive Memory, 3-13
Fault Queue, 3-15
Frequency, 3-5, 3-10
Masks & Owners, 3-18
Mux’ed Temps, 3-20
Power & Time, 3-4
Security, 3-18
Setpoints, 3-7
Start/Stop, 3-6
Temperature, 3-5, 3-10
Voltage, 3-4
Index-3
Voltage Loop, 3-11
Line Frequency parameter, 3-5
linear list of parameters, 3-23
H
High Vac Lmt parameter, 3-9
High Vac Time parameter, 3-9
Logic Mask Act parameter, 3-19
Logic Mask parameter, 3-18
Low Vac Limit parameter, 3-9
Low Vac Time parameter, 3-9
I
LPM20 liquid-cooled AC drive installation
information reference, P-1
I Imbalance Lmt parameter, 3-9
I Imbalance parameter, 3-4
IGBT Base Temp parameter, 3-5
IGBT Junction Temp parameter, 3-5
IGBT NTC Temp1 parameter, 3-20
IGBT NTC Temp2 parameter, 3-20
IGBT NTC Temp3 parameter, 3-20
IGBT NTC Temp4 parameter, 3-20
IGBT NTC Temp5 parameter, 3-20
IGBT NTC Temp6 parameter, 3-20
IGBT NTC Temp7 parameter, 3-20
IGBT NTC Temp8 parameter, 3-20
Inductance parameter, 3-11
Input Current R parameter, 3-4
Input Current S parameter, 3-4
M
Manual Control parameter, 3-6
manual conventions, P-2
Masks & Owners Parameter Group, 3-18
Min Line Freq parameter, 3-5
Min Max Persist parameter, 3-5
Modulation Freq parameter, 3-7
Modulation Index parameter, 3-7
Monitor File, 3-4
Motoring kWh parameter, 3-4
Mux’ed Temps Parameter Group, 3-20
O
Input Current T parameter, 3-4
Option Select parameter, 3-6
Input Voltage RS parameter, 3-4
Output Powr Fctr parameter, 3-4
Input Voltage ST parameter, 3-4
Input Voltage TR parameter, 3-4
P
Inputs & Outputs File, 3-20
Parallel Config parameter, 3-12
IT Overload parameter, 3-4
Param Access Lvl parameter, 3-13
J
Junct Temp Alrm parameter, 3-10
Junct Temp Trip parameter, 3-10
K
kVAR Reference parameter, 3-7
L
Language parameter, 3-13
Life Power Time parameter, 3-5
Life Pwr Cycles parameter, 3-5
Life Run Time parameter, 3-5
Life Time kWh parameter, 3-5
parameter cross-reference
by name, 3-22
by number, 3-23
parameter linear list, 3-23
Parameters
AC High Freq Lmt, 3-10
AC High Freq Time, 3-10
AC Line kW, 3-4
AC Low Freq Lmt, 3-10
AC Low Freq Time, 3-10
Active Current, 3-4
Active I Cmd, 3-11
Active I Lmt, 3-9
Active OL I Lmt, 3-9
Alarm Config, 3-16
Alarm Status, 3-13
Ambient Temp, 3-5
Limit Config File, 3-9
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Index-4
Ambnt Temp Alrm, 3-10
Ambnt Temp Trip, 3-10
Base Temp Alrm, 3-10
Base Temp Trip, 3-10
Bus Capacitance, 3-12
CAN Bus Off Cnt, 3-18
Capacitance, 3-12
Change Line Freq, 3-5
CldPlt Temp Alrm, 3-10
CML Bandwidth, 3-11
CML Damping, 3-11
CML Ki, 3-11
CML Kp, 3-11
Coldplate Temp1, 3-20
Coldplate Temp2, 3-20
Connect Status, 3-17
Control SW Ver, 3-13
Converter Control, 3-7
Converter Fault, 3-8
Converter Min Vdc, 3-8
Converter Status, 3-8
CS Msg Bad Cnt, 3-18
CS Msg Rx Cnt, 3-17
CS Msg Tx Cnt, 3-17
CS Timeout Cnt, 3-17
Current Lmt Gain, 3-9
Current Lmt Val, 3-9
Data In A1, 3-17
Data In A2, 3-17
Data In B1, 3-17
Data In B2, 3-17
Data In C1, 3-17
Data In C2, 3-17
Data In D1, 3-17
Data In D2, 3-17
Data Out A1, 3-17
Data Out A2, 3-17
Data Out B1, 3-17
Data Out B2, 3-17
Data Out C1, 3-17
Data Out C2, 3-17
Data Out D1, 3-17
Data Out D2, 3-17
DcLink Command, 3-11
DcLink Reference, 3-7
DcLink Ripple, 3-4
DcLink Voltage, 3-4
Dig In Frc Data, 3-21
Dig In Frc Mask, 3-20
Dig In Status, 3-20
Dig Out Frc Data, 3-21
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Dig Out Frc Mask, 3-21
Dig Out Status, 3-21
DPI Error Out, 3-17
Drive Checksum, 3-13
Elapsed Run Time, 3-5
Extern Cml Ref, 3-7
Fault 1 Code, 3-15
Fault 1 Time, 3-15
Fault 2 Code, 3-15
Fault 2 Time, 3-15
Fault 3 Code, 3-16
Fault 3 Time, 3-16
Fault 4 Code, 3-16
Fault 4 Time, 3-16
Fault Amps D, 3-14
Fault Amps Q, 3-14
Fault Amps R, 3-14
Fault Amps S, 3-14
Fault Amps T, 3-14
Fault Clear, 3-15
Fault Clr Mask, 3-18
Fault Clr Owner, 3-18
Fault Config, 3-15
Fault Frequency, 3-14
Fault Volts RS, 3-14
Fault Volts ST, 3-14
Fault Volts TR, 3-14
Fault Volts Vdc, 3-14, 3-15
Ground Current, 3-4
High Vac Lmt, 3-9
High Vac Time, 3-9
I Imbalance, 3-4
I Imbalance Lmt, 3-9
IGBT Base Temp, 3-5
IGBT Junction Temp, 3-5
IGBT NTC Temp1, 3-20
IGBT NTC Temp2, 3-20
IGBT NTC Temp3, 3-20
IGBT NTC Temp4, 3-20
IGBT NTC Temp5, 3-20
IGBT NTC Temp6, 3-20
IGBT NTC Temp7, 3-20
IGBT NTC Temp8, 3-20
Inductance, 3-11
Input Current R, 3-4
Input Current S, 3-4
Input Current T, 3-4
Input Voltage RS, 3-4
Input Voltage ST, 3-4
Input Voltage TR, 3-4
IT Overload, 3-4
Index-5
Junct Temp Alrm, 3-10
Junct Temp Trip, 3-10
kVAR Reference, 3-7
Language, 3-13
Life Power Time, 3-5
Life Pwr Cycles, 3-5
Life Run Time, 3-5
Life Time kWh, 3-5
Line Frequency, 3-5
Logic Mask, 3-18
Logic Mask Act, 3-19
Low Vac Limit, 3-9
Low Vac Time, 3-9
Manual Control, 3-6
Min Line Freq, 3-5
Min Max Persist, 3-5
Modulation Freq, 3-7
Modulation Index, 3-7
Motoring kWh, 3-4
Option Select, 3-6
Output Powr Fctr, 3-4
Parallel Config, 3-12
Param Access Lvl, 3-13
Password, 3-13
PC Msg Rx Cnt, 3-18
PC Msg Tx Cnt, 3-18
PC Timeout Cnt, 3-18
PF Bandwidth, 3-11
Port Mask Act, 3-18
Power Up Marker, 3-15
PWM Frequency, 3-10
Rated Amps, 3-4
Rated Power, 3-4
Reactive Current, 3-4
Reactive I Cmd, 3-11
Reactive I Lmt, 3-11
Reactive RateLmt, 3-9
Reduce Ilmt Sel, 3-11
Regen I Lmt, 3-9
Regen kWh, 3-4
Reset Meters, 3-13
Reset to Defaults, 3-13
Ride Through Sec, 3-9
Speed Mode, 3-6
Start Inhibit, 3-14
Start Mask, 3-18
Start Owner, 3-18
Stop Owner, 3-18
Testpoint 1 Data, 3-15
Testpoint 1 Sel, 3-15
Testpoint 2 Data, 3-15
Testpoint 2 Sel, 3-15
Turn Off Delay, 3-7
V Imbalance, 3-4
V Imbalance Lmt, 3-9
V Imbalance Time, 3-10
VML Bandwidth, 3-12
VML Damping, 3-12
VML Kf, 3-12
VML Ki, 3-12
VML Kp, 3-12
VML Reset Level, 3-12
Voltage Loop Sel, 3-11
Write Mask Act, 3-19
Write Mask Cfg, 3-19
Password parameter, 3-13
PC Msg Rx Cnt parameter, 3-18
PC Msg Tx Cnt parameter, 3-18
PC Timeout Cnt parameter, 3-18
PF Bandwidth parameter, 3-11
Port Mask Act parameter, 3-18
Power & Time Parameter Group, 3-4
Power Up Marker parameter, 3-15
PowerFlex 700 Vector Control (standard)
information reference, P-1
PowerFlex 700S Phase II Control (optional)
information reference, P-2
PowerFlex Liquid-Cooled AC Drive installation
information reference, P-1
precautions, general, P-3
PWM Frequency parameter, 3-10
R
Rated Amps parameter, 3-4
Rated Power parameter, 3-4
Reactive Current parameter, 3-4
Reactive I Cmd parameter, 3-11
Reactive I Lmt parameter, 3-11
Reactive RateLmt parameter, 3-9
Reduce Ilmt Sel parameter, 3-11
reference literature, P-2
Regen I Lmt parameter, 3-9
Regen kWh parameter, 3-4
removing active converter control cassette, 1-2
removing active converter power module covers,
1-2
Reset Meters parameter, 3-13
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
Index-6
Reset to Defaults parameter, 3-13
Voltage Parameter Group, 3-4
Ride Through Sec parameter, 3-9
W
S
web site for reference literature, P-2
Setpoints Parameter Group, 3-7
wiring active converter control cassette I/O
terminals, 1-4
Speed Mode parameter, 3-6
Write Mask Act parameter, 3-19
Start Inhibit parameter, 3-14
Write Mask Cfg parameter, 3-19
Security Parameter Group, 3-18
Start Mask parameter, 3-18
Start Owner parameter, 3-18
Start/Stop Parameter Group, 3-6
static discharge (ESD), P-3
Stop Owner parameter, 3-18
T
technical support, P-2
Temperature Parameter Group, 3-5, 3-10
terminal block wire size
I/O - Active Converter Control Board, 1-5
Testpoint 1 data parameter, 3-15
Testpoint 1 Sel parameter, 3-15
Testpoint 2 data parameter, 3-15
Testpoint 2 Sel parameter, 3-15
troubleshooting, 4-1
Turn Off Delay parameter, 3-7
U
Utility File, 3-13
V
V Imbalance Lmt parameter, 3-9
V Imbalance parameter, 3-4
V Imbalance Time parameter, 3-10
Vector Control (standard) information reference,
P-1
VML Bandwidth parameter, 3-12
VML Damping parameter, 3-12
VML Kf parameter, 3-12
VML Ki parameter, 3-12
VML Kp parameter, 3-12
VML Reset Level parameter, 3-12
Voltage Loop Parameter Group, 3-11
Voltage Loop Sel parameter, 3-11
PowerFlex 700L Active Converter Power Module User Manual
Publication PFLEX-UM002D-EN-P
U.S. Allen-Bradley Drives Technical Support - Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: [email protected], Online: www.ab.com/support/abdrives
www.rockwellautomation.com
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA,Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium,Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong,Tel: (852) 2887 4788, Fax: (852) 2508 1846
Publication PFLEX-UM002D-EN-P – December, 2007