VAV Boxes and Controls Replacement in Academic Building at Gordon College
Barnesville, Georgia
C V data (known pressure drops vs. flow curves through heat exchanger). If no provision is
available for actual flow measurements as listed above, balancing shall be performed by the
temperature differential method, but the temperature differential method shall be performed
only after specified air balancing has been completed. Pump flow rates shall be measured by
flow meters, balancing valves with flow taps, or differential pressure measurements.
B.
3.12
A.
Adjustments: All hydronic circuits shall be adjusted by the use of the specified balancing
valves. All balancing valves shall be permanently marked after balancing is completed so they
may be returned to the correct position if disturbed.
TOLERANCES
Set HVAC system airflow and water flow rates within the following tolerances:
1.
2.
3.
4.
3.13
Supply, Return, and Exhaust Fans and Equipment with Fans: Plus 10 percent to minus
10 percent.
Air Outlets and Inlets: Plus 10 percent to minus 10 percent.
Heating-Water Flow Rate: Plus 10 percent to minus 10 percent.
Cooling-Water Flow Rate: Plus 10 percent to minus 5 percent.
REPORTING
A.
Initial Construction-Phase Report: Based on examination of the Contract Documents as
specified in "Examination" Article, prepare a report on the adequacy of design for systems'
balancing devices. Recommend changes and additions to systems' balancing devices to
facilitate proper performance measuring and balancing. Recommend changes and additions to
HVAC systems and general construction to allow access for performance measuring and
balancing devices.
B.
Status Reports: As Work progresses, prepare reports to describe completed procedures,
procedures in progress, and scheduled procedures. Include a list of deficiencies and problems
found in systems being tested and balanced. Prepare a separate report for each system and each
building floor for systems serving multiple floors.
3.14
CERTIFIED FINAL TAB REPORT
A.
General: Typewritten, or computer printout in letter-quality font, on standard bond paper, in
three-ring binder, tabulated and divided into sections by tested and balanced systems.
B.
Include a certification sheet in front of binder signed and sealed by the certified testing and
balancing engineer.
1.
C.
Include a list of instruments used for procedures, along with proof of calibration.
General Report Data: In addition to form titles and entries, include the following data in the
final report, as applicable:
1.
2.
3.
4.
Title page.
Name and address of TAB firm and telephone number.
Project name.
Project location.
15950 - 8