Download Specifications
Transcript
VAV Boxes and Controls Replacement in Academic Building at Gordon College Barnesville, Georgia C V data (known pressure drops vs. flow curves through heat exchanger). If no provision is available for actual flow measurements as listed above, balancing shall be performed by the temperature differential method, but the temperature differential method shall be performed only after specified air balancing has been completed. Pump flow rates shall be measured by flow meters, balancing valves with flow taps, or differential pressure measurements. B. 3.12 A. Adjustments: All hydronic circuits shall be adjusted by the use of the specified balancing valves. All balancing valves shall be permanently marked after balancing is completed so they may be returned to the correct position if disturbed. TOLERANCES Set HVAC system airflow and water flow rates within the following tolerances: 1. 2. 3. 4. 3.13 Supply, Return, and Exhaust Fans and Equipment with Fans: Plus 10 percent to minus 10 percent. Air Outlets and Inlets: Plus 10 percent to minus 10 percent. Heating-Water Flow Rate: Plus 10 percent to minus 10 percent. Cooling-Water Flow Rate: Plus 10 percent to minus 5 percent. REPORTING A. Initial Construction-Phase Report: Based on examination of the Contract Documents as specified in "Examination" Article, prepare a report on the adequacy of design for systems' balancing devices. Recommend changes and additions to systems' balancing devices to facilitate proper performance measuring and balancing. Recommend changes and additions to HVAC systems and general construction to allow access for performance measuring and balancing devices. B. Status Reports: As Work progresses, prepare reports to describe completed procedures, procedures in progress, and scheduled procedures. Include a list of deficiencies and problems found in systems being tested and balanced. Prepare a separate report for each system and each building floor for systems serving multiple floors. 3.14 CERTIFIED FINAL TAB REPORT A. General: Typewritten, or computer printout in letter-quality font, on standard bond paper, in three-ring binder, tabulated and divided into sections by tested and balanced systems. B. Include a certification sheet in front of binder signed and sealed by the certified testing and balancing engineer. 1. C. Include a list of instruments used for procedures, along with proof of calibration. General Report Data: In addition to form titles and entries, include the following data in the final report, as applicable: 1. 2. 3. 4. Title page. Name and address of TAB firm and telephone number. Project name. Project location. 15950 - 8