E1000
K1
K2
Running command
0
0
Stop
K1
1
0
Forward running
K2
0
1
Reverse running
1
1
Stop
FWD
REV
CM
2. Two-line operation mode 2: when this mode is used, FWD is enable terminal, the direction is controlled by
REV terminal.
For example: “FWD” terminal-----“open”: stop, “closed”: running;
“REV” terminal-----“open”: forward running, “closed”: reverse running;
“CM” terminal-----common port
K1
K2
Running command
0
0
Stop
0
1
Stop
K1
1
0
Forward running
K2
1
1
Reverse running
FWD
REV
CM
3. Three-line operation mode 1:
In this mode, X terminal is enable terminal, the direction is
controlled by FWD terminal and REV terminal. Pulse signal is valid.
Stopping command is enable by opening X terminal.
SB2
FWD
SB3
X
SB1
SB3: stop button
REV
SB2: forward button
CM
SB1: reverse button
4. Three-line operation mode 2:
In this mode, X terminal is enable terminal, running command is
controlled by FWD terminal. The running direction is controlled by
REV terminal, and stopping command is enable by opening X
terminal.
SB1: Running button
SB1
SB2
K1
SB2: Stop button
K1: direction switch. Open stands for forward running; close
stands for reverse running.
·38·
FWD
X
REV
CM